Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
DEFECTIVE FIXTURES | DANGEROUS AND HAZARDS WATER LEAKING INTO LIGHT FIXTURES AT KITCHEN AND BASEMENT OF UNIT E | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | REPLACE LOOSE AND DEFECTIVE LIGHT FIXTURES AT REAR EXTERIOR DOORS OF UNITS E AND B | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | CLOSE OPEN ELECTRICAL PANELS AND JUNCTION BOX AT GARAGE D&H | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | REMOVE DOUBLE TERMINATING AT BREAKERS IN PANEL_18-27-110.14) | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | AT OPEN JUNCTION BOX AT GARAGE | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
DEFECTIVE METER EQUIPMENT | PROPERLY SUPPORT LOOSE METER CABINET AT UNIT C | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING NO OWNERS I D SIGN POSTED. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR GUTTER | SOUTH ELEVATION,DOWNSPOUT,RUSTY WITH HOLE AT GRADE. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | NORTH ELEVATION,BASEMENT WINDOW,BROKEN PANE. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR FLOOR | LIVING ROOM AND 2ND FLOOR BATHROOM FLOORS,WEAK. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
COVER OUTLETS AND JBS | 1ST FLOOR GITCHEN OUT LET,MISSING COVER. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
EXPOSED WIRING | KITCHEN LIGHT OVER SINK,EXPOSED WIRES. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | 2ND FLOOR CLOSET LIGHT FIXTURE,LOOSE AND HANGING. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | 2ND FLOOR SMOKE DETECTOR,LOW BATTERY. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | BASEMENT AREA,2 ROOM BUILT, 2 BY 4 STUDS WITH DRYWALL,NO PERMIT NO FILE. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | BULLET HOLES IN VARIOUS LOCATIONS AT WEST ELEVATION. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
PRV BALLCOCK,VB,OR AIR GAP | SILLCOCK NORTH ELEVATION. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | UNIT E REAR BURGLAR SCISSORS GATE WITH PADLOCK. DANGEROUS AND HAZARDOUS. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | DEFECTIVE LIGHT FIXTURE AT THE REAR OF E, NEED TO SUPPORT LIGHT AND INSTALL A COVER. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | UNIT D STORM DOOR GLASS BROKEN. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO INTERIOR. UNVERIFIED OCCUPANCY , DETECTORS, OR LIVING CONDITIONS. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SUPPLEMENTAL GROUND | MISSING SUPPLEMENTAL GROUND TO UNITS A AND B . DANGEROUS CONDITION. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SUPPLY HOT WTR MIN TEMP 120DEG | 6901 / UNIT A / HOT WATER - SUPPLIED AT ONLY 80F AT TIME OF INSPECTION. CB154027 - HOT OR TEMPERED WATER - PROVIDE (14X-9-905.2, 14X-9-905.2.1AND 14X-9-905.5) | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
INSTALL SMOKE DETECTORS | 6901 / UNIT A / SMOKE DETECTORS - MISSING. CB197019 - SMOKE ALARMS / DETECTORS - INSTALL (14X-5-504.8, 14X-5-504.8.4,14B-9-907.2.10.1 THROUGH 14B-9-907.2.10.7, AND 14R-11-1104) | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
SAFE WORKING CONDITIONS | 6901 / UNIT A / BOILER - OUT OF SERVICE AT TIME OF INSPECTION. CB132046 - SAFE WORKING CONDITIONS (14X-3-305.1, 14X-8-804.1 THRU 14X-8-804.4 AND 14X-8-804.5) | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | 6901 / UNIT A / CRBON MONOXIDE DETECTORS - MISSING. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | NORTH ELEVATION AT C AND D / WINDOWS - BROKEN PANES. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EAVES | BUILDING / EAVES - MISSING CAPPING. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR DOWNSPOUT | SOUTH ELEVATION / DOWNSPOUT - MISSING BOTTOM 8 FOOT SECTION. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF UNITS - NO ENTRY, UNVERIFIED DETCTORS, CONDITIONS AND OCCUPANCY. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | NORTH ELEVATION / EXTERIOR WALL - MASONRY FRACTURES. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | BUILDING INTERIOR - NO RESPONSE - UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO INSPECT INTERIOR STAIRWAYS. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
STRAP SERVICE CONDUIT | PROPERLY SUPPORT LOOSE SERVICE CONDUITS - UNIT A,B,C,D | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
DEBRIS, EXCESSIVE | 6901 S./ - UNIT C. - NORTH LANDSCAPED AREA - REFUSE ACCUMULATION. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | 6001 UNIT C - NORTH ELEVATION - BROKEN GLASS PANE. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR WINDOW SILLS | 6901 S./ - UNIT C.- NORTH WINDOW SILL - WASHED OUT MORTAR. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - NO RESPONSE, UNABLE TO TO VERIFY DETECTORS AND INTERIOR CONDITIONS. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO INTERIOR OF PROPERTY. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | MISSING OWNER POSTING. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | SOUTH WINDOW WELL COVER MISSING PROVIDE PROPER COVER. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPLCE WINDOW PANES, PLEXGLAS | NORTH 1ST FLOOR WINDOW PANE HAS BULLET HOLES UNIT # C | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | NORTH ENTRY DOOR HAS BULLET HOLE UNIT # C | 6901 S EAST END AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR HARDWARE | SECURITY DOOR MISSING DEAD-BOLT/ HANDLE. | 6901 S EAST END AVE | COMPLAINT | FAILED | View |