Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ARRANGE FOR REINSPECTION REGAR | NO ENTRY, EXTERIOR INSPECTION ONLY. ARRANGE FOR INTERIOR INSPECTION TO VERIFY OCCUPANCY AND DETECTORS. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
REGISTER/SECURE/INSURE-VACANT | REGISTER, INSURE AND SECURE VACANT BUILDING WITHIN 30 DAYS OF IT BECOMING VACANT, OR WITHIN 30 DAYS AFTER ASSUMING OWNERSHIP OF AN EXISTING VACANT BUILDING. (13-12-125) BUILDING MUST BE KEPT IN COMPLIANCE WITH ALL VACANT BUILDING REQUIREMENTS. (13-12-135) SEE VACANT BUILDING ORDINANCE AND REGISTRATION FORM AT WWW.CITYOFCHICAGO.ORG/BUILDINGS. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | 1) WEST ELEVATION, NORTH-WEST CORNER, TOP OF THE ELEVATION, LARGE SECTION OF METAL ROOFING MATERIAL, DETACHED, HANGING OVER PUBLIC WAY; 2) WEST ELEVATION, NORTH-WEST CORNER, 4TH FLOOR, LARGE SECTION OF MASONRY, OUT OF PLUMB, SEPARATING, PULLING AWAY FROM STRUCTURE, OVER PUBLIC WAY. OBTAIN PLANS AND PERMIT FOR REPAIRS. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
PROVIDE SIDEWALK SHED F/PROTCT | IMMEDIATELY PROVIDE SIDEWALK SHED FOR PROTECTION OF PROPERTY AND PASSERSBY FROM UNSAFE CONDITIONS, AS FOLLOWS: 1) WEST ELEVATION, NORTH-WEST CORNER, TOP OF THE ELEVATION, LARGE SECTION OF METAL ROOFING MATERIAL, DETACHED, HANGING OVER PUBLIC WAY; 2) WEST ELEVATION, NORTH-WEST CORNER, 4TH FLOOR, LARGE SECTION OF MASONRY, OUT OF PLUMB, SEPARATING, PULLING AWAY FROM STRUCTURE, OVER PUBLIC WAY. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
TIME EXPIRATION | TIME EXPIRATION REINSTATE OLD PERMIT #953611 BEFORE COMMENCING ANY CONSTRUCTION WORK | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
COMPLETE WORK | COMPLETE WORK AS REQUIRED PER APPROVED REINSTATED PLANS AND PERMITS | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
WORK W/ EXPIRED/REVOKED PERMIT | REINSTATEMENT OF PERMIT EXPIRED #953611 | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | REAR EXTERIOR WALL (1) WEST ELEVATION JULIET BALCONIES SEVERE RUSTING OF PIECES (2) WEST ELEVATION UNDERSIDE OF BAY WINDOW FLOOR STRUCTURE EXPOSED WOOD OPEN TO WEATHER ELEMENTS | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
REPAIR FLOOR | FLOORING OF BUILDING IMPROPER CONNECTIONS OF FLOOR CANTERLEVERIED OUT OVER PUBLIC SIDE WALK MISSING PROPER CONNECTIONS | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
MAINTAN BLDG IN SAFE CONDITION | MAINTAIN VACANT BUILDING | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
POST OWNER NAME OF VACNT BLDG | POST OWNER/MANAGEMENT ID (NOT P.O. BOX) SIGN ON VACANT PROPERTY | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | ARRANGE PREMISE INSPECTIONMOST APARTMENTS - NO RESPONSE, UNVERIFIED DETECTORS, CONDITIONS AND OCCUPANCY. UNABLE TO INSPECT INTERIOR STAIRWAYS. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | SOUTH ELEVATION / EXTERIOR WALL / REMOVE NUISANCE - GRAFFITI ON WALL. | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |
SEE INSPECTOR COMMENTS | REMOVE LOAD SIDE NEUTRAL BONDS IN ALL SUB PANELS14E-2-250.24(A)(5) | 1427 N SEDGWICK ST | PERMIT | FAILED | View |
SEE INSPECTOR COMMENTS | LOOSE OUITLETS THROUGHOUT 14E-4-406.5(A) | 1427 N SEDGWICK ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | CORRECTLY WIRE ALL DEVICES. CANNOT BE USED FOR NEUTRAL CONTINUITY 14E-3_300.12(B) | 1427 N SEDGWICK ST | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 1427 N SEDGWICK ST | PERMIT | FAILED | View | |
ARRANGE COMPLETED PERMIT INSP. | 1427 N SEDGWICK ST | PERMIT | PASSED | View | |
SEE INSPECTOR COMMENTS | FAILURE TO HAVE ROUGH INSPECTION 13-12-17 | 1427 N SEDGWICK ST | PERMIT | FAILED | View |
SEE INSPECTOR COMMENTS | FAILURE TO HAVE ROUGH INSPECTION 13-12-17 | 1427 N SEDGWICK ST | PERMIT | PASSED | View |
SEE INSPECTOR COMMENTS | REMOVE LOAD SIDE NEUTRAL BONDS IN ALL SUB PANELS14E-2-250.24(A)(5) | 1427 N SEDGWICK ST | PERMIT | PASSED | View |
OPEN | 1427 N SEDGWICK ST | PERMIT | PASSED | View | |
PROVIDE | PROVIDE PER SECTION CODE 13-96-020, 13-96-840 FOR REAR STEEL PORCH | 1427 N SEDGWICK ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | LOOSE OUITLETS THROUGHOUT 14E-4-406.5(A) | 1427 N SEDGWICK ST | PERMIT | FAILED | View |
SEE INSPECTOR COMMENTS | CORRECTLY WIRE ALL DEVICES. CANNOT BE USED FOR NEUTRAL CONTINUITY 14E-3_300.12(B) | 1427 N SEDGWICK ST | PERMIT | FAILED | View |
PROVIDE | REAR OF BUILDING / 4 STORY IRON PORCH - RUSTED BEAMS AND CONNECTION, RUSTED AND BENT TREADS. FAILED TO ADEQUATELY MAINTAIN FIRE ESCAPES, SIGN STRUCTURES, ANTENNAE, CANOPIES, MARQUEES, FLAGPOLES, METAL CORNICES, SMOKESTACKS, WINDOW WASHING AND EXTERIOR MAINTENANCE SYSTEMS, AND OTHER METAL STRUCTURES PERMANENTLY INSTALLED ON THE EXTERIOR OF A BUILDING. PROVIDE CRITICAL EXAMINATION REPORT ON EXPOSED METAL STRUCTURES BY A REGISTERED DESIGN PROFESSIONAL WITHIN 2 YEARS AFTER ITS INSTALLATION AND AT LEAST ONCE EVERY 5 YEARS AFTER THE INITIAL INSPECTION. THE REGISTERED DESIGN PROFESSIONAL MUST PREPARE THE SIGNED AND SEALED WRITTEN REPORT ON THE EXTERNAL STRUCTURAL CONDITION AND INTEGRITY OF THE EXPOSED METAL STRUCTURE AND PROVIDE TO OWNER. EXISTING FIRE ESCAPES AND FIRE ESCAPE STAIRWAY MAY NOT BE REMOVED WITHOUT A PERMIT AND APPROVAL BY THE BUILDING OFFICIAL AND FIRE CODE OFFICIAL. SEND REPORTS TO: DEPARTMENT OF BUILDINGS CODE COMPLIANCE GROUP, 2045 W. WASHINGTON BLVD. CHICAGO, IL 60612. (14A-6-603.3 THROUGH 14A-6-603.3.4, 14X-5-505.12, 14R-3-307, 14R-3-307.6 AND 14A-4-404.8) | 1427 N SEDGWICK ST | PERIODIC | FAILED | View |