Chicago Building Violations Data: 16 Violations
Violation Inspector Comments Address Category Status View
CONNECT VENT LINE THIS PERTAINS TO ALL FIVE (5) LIEBERT UNITS IN THE 12TH FL COMPUTER ROOM.(13-192-520,13-190-720) 550 W JACKSON BLVD PERIODIC PASSED View
ARRANGE FOR RE-INSPECTION CONCERNING COMPLIANCE WITH A PENDING NOTICE OF VIOLATIONS. 550 W JACKSON BLVD PERIODIC PASSED View
ARRANGE FOR RE-INSPECTION WORK IN PROGRESS 550 W JACKSON BLVD PERMIT PASSED View
1) ALL REFRIGERANT TUBING THAT IS INSTALLED IN A PLENUM CEILING MUST BE CONTAINED IN A SEALED CONDUIT OR RACEWAY THAT IS VENTED TO THE OUTSIDE ATMOSPHERE AND APPROVED BY THE BUREAU OF REFRIGERATION.REFRIGERANT TUBING THAT IS NOT CONTAINED IS NOT ALLOWED IN A PLENUM CEILING.2) ALL JOINTS IN A REFRIGERATION SYSTEM MUST BE BRAZED. THREADED AND MECHANICAL JOINTS ARE NOT ALLOWED.3) PROVIDE A STRUCTURAL ANALYSIS LETTER FOR THE PLACEMENT OF THE REFRIGERATING EQUIPMENT IN THE SECOND FLOOR MACHINE ROOM.4) ONCE THE REFRIGERANT TUBING IS PROPERLY INSTALLED IN A CONDUIT OR RACEWAY IN THE PLENUM CEILING PROVIDE AN EMERGENCY FIREMANS DUMP SYTEM FOR THE TWO(2) 18 TON REFRIGERATING SYTEMS LOCATED IN THE 2ND FLOOR MACHINE ROOM.5)PROVIDE THE PROPER REFRIGERANT SENSOR IN THE MACHINE ROOM FOR 410A REFRIGERANT.6) PROVIDE A TEST OF THE EMERGENCY SYTEM IN THE MACHINE ROOM IN THE PRESENCE OF A CITY OF CHICAGO REFRIGERATION INSPECTOR. 550 W JACKSON BLVD PERMIT FAILED View
ARRANGE FOR RE-INSPECTION CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 8:00-9:00AM 550 W JACKSON BLVD PERMIT PASSED View
1) ALL REFRIGERANT TUBING THAT IS INSTALLED IN A PLENUM CEILING MUST BE CONTAINED IN A SEALED CONDUIT OR RACEWAY THAT IS VENTED TO THE OUTSIDE ATMOSPHERE AND APPROVED BY THE BUREAU OF REFRIGERATION.REFRIGERANT TUBING THAT IS NOT CONTAINED IS NOT ALLOWED IN A PLENUM CEILING.(18-29-602.2.1)2) ALL JOINTS IN A REFRIGERATION SYSTEM MUST BE BRAZED. THREADED AND MECHANICAL JOINTS ARE NOT ALLOWED.(18-28-1107.4.4)3) PROVIDE A STRUCTURAL ANALYSIS LETTER FOR THE PLACEMENT OF THE REFRIGERATING EQUIPMENT IN THE SECOND FLOOR MACHINE ROOM.(13-52-060,13-52-080)4) ONCE THE REFRIGERANT TUBING IS PROPERLY INSTALLED IN A CONDUIT OR RACEWAY IN THE PLENUM CEILING PROVIDE AN EMERGENCY FIREMANS DUMP SYTEM FOR THE TWO(2) 18 TON REFRIGERATING SYTEMS LOCATED IN THE 2ND FLOOR MACHINE ROOM.(18-28-1106.12)5)PROVIDE THE PROPER REFRIGERANT SENSOR IN THE MACHINE ROOM FOR 410A REFRIGERANT.(18-28-1105.5)6) PROVIDE A TEST OF THE EMERGENCY SYTEM IN THE MACHINE ROOM IN THE PRESENCE OF A CITY OF CHICAGO REFRIGERATION INSPECTOR.(18-28-1105.6) 550 W JACKSON BLVD PERMIT PASSED View
FRIREMAN'S DUMP INSTALL A HAND OPERATED RERFIGERANT RELIEF VALVE(FIREMANS DUMP) FOR EACH 18 TON DAIKIN UNIT LOCATED IN THE 2ND FLOOR SERVER ROOM.(18-28-1106.12) 550 W JACKSON BLVD PERIODIC PASSED View
PROVIDE 1) A TEST OF THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE 2ND FLOOR SERVER ROOM. THE LEAK DETECTOR MUST BE CERTIFIED FOR 410A REFRIGERANT.(18-28-1105.6)2) STRUCTURAL REVIEW STATING THAT THE NEW DAIKIN EQUIPMENT IN THE 2ND FLOOR SERVER ROOM DOES NOT EXCEED THE FLOOR LOAD RATING.(13-52-060,13-52-080) 550 W JACKSON BLVD PERIODIC PASSED View
ARRANGE FOR RE-INSPECTION CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 8:00-9:00AM 550 W JACKSON BLVD PERIODIC PASSED View
REPAIR OR REPLACE 1) THE REFRIGERANT TUBING THAT IS CURRENTLY INSTALLED IN THE PLENUM CEILING. FOR THE TUBING TO REMAIN IN THE PLENUM CEILING IT MUST BE INSTALLED IN A PRESSURE TIGHT CONDUIT OR RACEWAY THAT IS VENTED TO THE OUTSIDE ATMOSPHERE. THE CONDUIT/RACEWAY THAT IS INSTALLLED IN THE PLENUM CEILING MUST BE APPROVED BY THIS BUREAU BEFORE INSTALLATION.(18-28-602.1)2) THE JOINTS IN THE REFRIGERATION SYSTEM THAT ARE NOT BRAZED.SOLDERED JOINTS AND MECHANICAL JOINTS ARE NOT ALLOWED.(18-28-1107.4.4) 550 W JACKSON BLVD PERIODIC PASSED View
FIRE EXTNGSHR RECHARGE & TAG FLOOR 17/ ROOM 1700 - ANSUL SYSTEM HAS EXPIRED TAG(2011). 550 W JACKSON BLVD COMPLAINT PASSED View
FRIREMAN'S DUMP INSTALL A HAND OPERATED RERFIGERANT RELIEF VALVE(FIREMANS DUMP) FOR EACH 18 TON DAIKIN UNIT LOCATED IN THE 2ND FLOOR SERVER ROOM.(18-28-1106.12) 550 W JACKSON BLVD PERIODIC PASSED View
PROVIDE 1) A TEST OF THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE 2ND FLOOR SERVER ROOM. THE LEAK DETECTOR MUST BE CERTIFIED FOR 410A REFRIGERANT.(18-28-1105.6)2) STRUCTURAL REVIEW STATING THAT THE NEW DAIKIN EQUIPMENT IN THE 2ND FLOOR SERVER ROOM DOES NOT EXCEED THE FLOOR LOAD RATING.(13-52-060,13-52-080) 550 W JACKSON BLVD PERIODIC PASSED View
REPAIR OR REPLACE 1) THE REFRIGERANT TUBING THAT IS CURRENTLY INSTALLED IN THE PLENUM CEILING. FOR THE TUBING TO REMAIN IN THE PLENUM CEILING IT MUST BE INSTALLED IN A PRESSURE TIGHT CONDUIT OR RACEWAY THAT IS VENTED TO THE OUTSIDE ATMOSPHERE. THE CONDUIT/RACEWAY THAT IS INSTALLLED IN THE PLENUM CEILING MUST BE APPROVED BY THIS BUREAU BEFORE INSTALLATION.(18-28-602.1)2) THE JOINTS IN THE REFRIGERATION SYSTEM THAT ARE NOT BRAZED.SOLDERED JOINTS AND MECHANICAL JOINTS ARE NOT ALLOWED.(18-28-1107.4.4) 550 W JACKSON BLVD PERIODIC PASSED View
ARRANGE FOR RE-INSPECTION CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 8:00-9:00AM 550 W JACKSON BLVD PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR PHASE 2 OPERATION TO FUNCTION ONLY WITH THE KEY SWITCH IN THE ON POSITION AFTER CHECKING "DOOR HOLD". CARS 1-8 550 W JACKSON BLVD PERMIT PASSED View