| Violation | Inspector Comments | Address | Category | Status | View |
|---|---|---|---|---|---|
| CHIMNEY | CHIMNEY WASHED OUT MORTAR AND SPALLED | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| CHIMNEY CAPPING | CHIMNEY CAP WASHED OUT MORTAR AND SPALLED | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| INSTALL SMOKE DETECTORS | SMOKE DETECTORS PROVIDE IN BASEMENT | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| CARB MONOX DETECT IN RESID | CARBON MONOXIDE DETECTORS PROVIDE IN BASEMENT. | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR. MASONRY WALL AT GARAGE EAST ELEVATION DAMAGED MORTAR JOINTS. SOUTH ELEVATION. | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| REPAIR/REBUILD GARAGE OR SHED | GARAGE REPAIR REPLACE THE SERVICE DOOR. | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| REPAIR GUTTER | GUTTER REPAIR ON GARAGE AT ALLEY SIDE OPEN END CAP SOUTH | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| SECURE RACEWAY | FRONT OF BASEMENT - STRAP AND SECURE ALL LOOSE OR IMPROPERLY SUPPORTED CONDUIT | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| CORRODED CONDUIT & EQUIP | REMOVE OR REPLACE RUSTED 1/2" CONDUIT ON WEST EXTERIOR NEXT TO METER BANK | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| SEAL CONDUIT OPENING | SEAL AROUND SECTION CABLES ENTERING BRICK WALL BELOW METER BANK ON WEST EXTERIOR | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| INSTALL ILLUMINATION | PROPERLY ILLUMINATE FRONT AREA OF BASEMENT | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| SEE INSPECTOR COMMENTS | FITTINGS FOR CONDUIT ON SOUTH AND WEST EXTERIOR ARE NOT SUITABLE FOR OUTDOOR USE - SHOULD BE COMPRESSION TYPE FITTINGS (18-27-110.11) | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| UNAPPROVED CORDS | 3RD FLOOR APARTMENT - REMOVE EXTENSION CORD FROM KITCHEN RECEPTACLE TO MICROWAVE IN FURNACE CLOSET | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| PROPER SIZE GRD ELECTRODE COND | INSTALL PROPER SIZE GROUNDING CONDUCTOR FOR 200AMP SERVICE - SHOULD BE #4 AWG COPPER IN 3/4" TW CONDUIT | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| NO PERMIT WIRING | OBTAIN PERMIT FOR IMPROPERLY INSTALLED CONDUIT FOR ALL FURNACES IN ALL UNITS INSTALLED WITHOUT PERMIT- TAKE FITTINGS USED - NOT APPROVED | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| SEE INSPECTOR COMMENTS | PERMIT REQUIRED TO CORRECT ALL ELECTRICAL VIOLATIONS- (13-12-360) | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| INSTALL COVERS | INSTALL COVER ON OPEN JUNCTION BOX ON SOUTH EXTERIOR OF GARAGE (ABOVE DOOR) | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |
| PROVIDE GFCI PROTECTION FOR ALL KITCHEN COUNTERTOP RECEPTACLES SPECIFICALLY 1ST FLOOR KITCHEN - AT RIGHT OF SINK AND 3RD FLOOR KITCHEN - ALL COUNTERTOP RECEPTACLES (18-27-570.8) | 8124 S MARYLAND AVE | COMPLAINT | PASSED | View |