Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SUBMIT 2 COPY MAINTENANCE RPT | FILE REPORTS AS REQUIRED BY EXTERIOR WALL ORDINANCE.LAST CRITICAL FILED FOR 2002 AND THE SHORT FORM DUE NO LATER THAN 11/1/2005 HAS NOT BEEN FILED AS OF 2/23/2006 | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 5110 S KENWOOD AVE | PERIODIC | PASSED | View | |
LEAKING BOILER TUBES | #1 KEWANEE FB. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
TEST G & S ALL ELE | 5 YEAR FULL LOAD. (EV003187) | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | MAKE EMERGENCY PHONES OPERATIONAL (INSTALL) 2.27.1.1 2.27.1.1.13. 18-30-010, 13-20-120. EV003187 | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
STOP/REMOVE NUISANCE | PENTHOUSE / ELEVATOR MACHINE ROOM BEING USE AS STORAGE ROOM - SEE USED AND DISCARDED DOORS AND CHANDELIER LIGHTS. BOILER ROOM - STORED WOOD BOARDS AROUND DUCT SHAFT. REMOVE ALL STORAGE. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
I-A I-B I-C AND II FIRE RESIST | PENT HOUSE - WINDOWS COVERED WITH PLYWOOD BOARDS IN INSIDE AND VINY SIDINGS ON OUTSIDE. INTERIOR STAIRWELL CEILING - PLYWOOD BOARD, WITH WOOD STUDS. STORAGE CLOSET, NEAR LAUNDRY ROOM - HOLE ON CEILING COVERED WITH WOOD BOARD. REMOVE ALL COMBUSTIBLE STRUCTURES AND MATERIALS. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
PIPE OPENING W/NONCOMBUST MATL | PENTHOUSE - OPENINGS AND PIPE PENETRATIONS SEALED WITH SPRAY FOAM. 10TH FLOOR / ELECTRIC CONDUIT WIRE BOX - OPEN 2" DIAMETER PIPES TO BE CAPPED OR SEALED. ALL FLOORS, NEAR FIRE ESCAPE DOORS - CONDUIT CABLE PENETRATION HOLES SEALED WITH BLACK SUBSTANCE. 2ND FLOOR CORRIDOR, NEAR 207 - CABLE PENETRATIONS SEALED WITH SPRAY FOAM. 1ST FLOOR / FIRE PUMP ROOM - WALLS AND CEILING PIPE PENETRATIONS, WITH LOOSE BRICKS. BOILER ROOM AND STORAGE CLOSET, NEAR LAUNDRY ROOM - PIPE PENETRATIONS SEALED WITH SPRAY FOAMS. REMOVE ALL EXPANDABLE SPRAY FOAMS, AND SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE CAULK, WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE-STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARD. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
CLASS B DOOR IN STAIRWELL | PENTHOUSE - STAIRWELL DOOR TO ELEVATOR MACHINE ROOM BROKEN. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | PENTHOUSE / STAIRWELL - PLYWOOD BOARDS CEILING, WITH OPENING. 10TH FLOOR / STAIRWELL - OPENING ON WALL, WITH NON FIRE-RATED ACCESS PANEL DOOR. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
REPAIR INTERIOR STAIR SYSTEM | 10TH FLOOR TO PENTHOUSE / INTERIOR STAIRWAY - TREADS AND RISERS RUSTING AND SEPARATING. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
REPAIR/REPLACE SMOKE DETECTORS | SOME UNITS, INCLUDING 805, 807 AND 907 - SMOKE DETECTORS - OUT OF SERVICE, WITH LOW AND MISSING BATTERIES. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
SELF-CLOSE DOOR >4 STORY RES. | DOORS NOT CLOSING AND LATCHING PROPERLY: 305, 605 (DOOR RUBBING ON RUG), 607, 610, 807, 808, 901 (WEATHER STRIPPING) AND 907. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
OBSTRUCTIONS IN EXIT WAY | REMOVE OBSTRUCTION ON EXIT WAY: 605 - DOOR RUBBING ON THROW RUGS. 205 - EXIT WAY OBSTRUCTED BY LOOSE AND HANGING CABLES - TRIPPING HAZARD. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | BIKE ROOM - SMOKE DETECTOR - MISSING. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | STORAGE CLOSET, NEAR LAUNDRY ROOM - BREECHED WALLS, WITH CLAY TILES LOOSE AND WASHED OUT MORTAR. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
2-HR HEATING PLANT ENCLOSURE | MASONRY WALL BETWEEN CORRIDOR AND BOILER ROOM BREECHED, AND USED AS TRASH CHUTE OPENING INTO BOILER ROOM. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
2HR SEP FOR STORAGE >100SF | SEPARATE TRASH ROOM FROM BOILER ROOM WITH 2-HOUR ENCLOSURE AND CLASS B DOOR ASSEMBLY. TRASH ROOM MUST BE EQUIPPED WITH FIRE SPRINKLERS. PLANS AND PERMIT REQUIRED. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
PLANS & PERMITS REQ - CONTRCTR | GARBAGE STORAGE ROOM CONSTRUCTED BETWEEN MAINTENCE ROOM AND CORRIDOR WALLS WITHOUT A PERMIT. NO VENTILATION; AND ENCLOSED WALL OPENED INTO CORRIDOR AND MISSING DOOR. SUBMIT PLANS AND OBTAIN PERMIT FOR RENOVATION. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
DOOR SWING IN DIR. OF TRAVEL | LAUNDRY ROOM - DOOR SWINGS IN OPPOSITE DIRECTION OF EGRESS. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
PROVIDE | NO FIRE SEPARATION BETWEEN ELECTRIC " MAIN" SERVICE DISCONNECTS AND LAUNDRY ROOM. PROVIDE 3-HOUR ENCLOSURE AND CLASS A DOOR ASSEMBLY FOR MAIN SERVICE DISCONNECTING MEANS PER SECTION CODE 18-27-230.2 (B)(2). | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
INSTALL EXIT SIGN | BIKE ROOM, LAUNDRY ROOM AND BOILER ROOM - EXIT SIGNS - MISSING. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
REPAIR DOOR HARDWARE | 1ST FLOOR / CORRIDOR: DOOR RUBBING ON FLOOR AND MISSING LATCH | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR PHONES | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ALARM BELL IN CAR #2 | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM FIRE SERVICE PHASE II MANDATE | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WEST ELEVATOR MAIN DRIVE SHEAVE SHOWS GROOVE WEAR.REPAIR/REPLACE | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CITY OF CHICAGO FIRE SERVICE MANDATE UPGRADE ON BOTH ELEVATORS. | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | ELEVATOR MACHINE ROOM - DOOR LABEL MISSING. ALL FLOORS: ELECTRIC CLOSETS, NEAR STAIRWELL DOORS, CHIMNEY WALL, NEAR REAR EMERGENCY EXIT DOOR, AND 5TH, 7TH, 9TH AND 10TH FLOORS / TELEPHONE CLOSETS - ACCESS PANEL DOORS MISSING. 1ST FLOOR / GARBAGE ROOM - DOOR MISSING. | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TEST | 5110 S KENWOOD AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 AND CATEGORY 5 TESTS ON BOTH ELEVATORS | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR EMERGENCY PHONES | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ELEVATOR #1 | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ALARM BELLS | 5110 S KENWOOD AVE | PERIODIC | FAILED | View |
INT WALL/CEILING CHIP PLASTER | 1ST FLOOR FOYER / CEILINGS - CRACKED WITH WATER DAMAGE. STAIRWAY A - CHIPPED AND LOOSE PAINT. 10TH FLOOR HALLWAY CEILING - WATER DMAGD TILE. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF APTS. - NO ENTRY, UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO VERIFY COMPLAINTS AT APTS 101 AND 108 FOR MOLD. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
INSTALL EXTRA SMOKE DETECTORS | TOP OF 10 FLOOR STAIRWAY / ADDITIONAL SMOKE DETECTOR - NEEDED. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | LAUNDRY ROOM / FIRE EXTINGUISHER - MISSING TAG. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
HOLDOPEN DEVICE, STAIR 3+ FLRS | 1ST FLOOR HALLWAY AND LAUNDRY ROOM DOORS - HELD OPEN WITH WOOD WEDGES. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
HEAT UNIT ADEQUATELY | 60° AT TIME OF INSPECTION 12:35, HEAT IS OFF RADIATORS COLD. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |
HEAT UNIT ADEQUATELY | 5110 S. / APT. 202 / LIVINGROOM AND BEDROOM TEMP WAS - 60 DEGREES AT 4:40PM. HEATING SYSTEM IS ON AT THE TIME OF INSPECTION, HEAT IS INSUFFICIENT. | 5110 S KENWOOD AVE | COMPLAINT | FAILED | View |