Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-08-30 @ 5:00 PM
PIN: 20114010550000
Property Address: 5110 S KENWOOD AVE
City - Zip: CHICAGO - 60615
2023 Property Class: 391
2023 Township: 70 - Hyde Park
2023 Neighborhood: 70020
2023 Tax District: 70131
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 42 Violations
Violation Inspector Comments Address Category Status View
SUBMIT 2 COPY MAINTENANCE RPT FILE REPORTS AS REQUIRED BY EXTERIOR WALL ORDINANCE.LAST CRITICAL FILED FOR 2002 AND THE SHORT FORM DUE NO LATER THAN 11/1/2005 HAS NOT BEEN FILED AS OF 2/23/2006 5110 S KENWOOD AVE COMPLAINT FAILED View
OWNER OR LICENSED CONTRACTOR 5110 S KENWOOD AVE PERIODIC PASSED View
LEAKING BOILER TUBES #1 KEWANEE FB. 5110 S KENWOOD AVE PERIODIC PASSED View
TEST G & S ALL ELE 5 YEAR FULL LOAD. (EV003187) 5110 S KENWOOD AVE PERIODIC PASSED View
OPEN TYPE VIOLATION MAKE EMERGENCY PHONES OPERATIONAL (INSTALL) 2.27.1.1 2.27.1.1.13. 18-30-010, 13-20-120. EV003187 5110 S KENWOOD AVE PERIODIC PASSED View
STOP/REMOVE NUISANCE PENTHOUSE / ELEVATOR MACHINE ROOM BEING USE AS STORAGE ROOM - SEE USED AND DISCARDED DOORS AND CHANDELIER LIGHTS. BOILER ROOM - STORED WOOD BOARDS AROUND DUCT SHAFT. REMOVE ALL STORAGE. 5110 S KENWOOD AVE PERIODIC PASSED View
I-A I-B I-C AND II FIRE RESIST PENT HOUSE - WINDOWS COVERED WITH PLYWOOD BOARDS IN INSIDE AND VINY SIDINGS ON OUTSIDE. INTERIOR STAIRWELL CEILING - PLYWOOD BOARD, WITH WOOD STUDS. STORAGE CLOSET, NEAR LAUNDRY ROOM - HOLE ON CEILING COVERED WITH WOOD BOARD. REMOVE ALL COMBUSTIBLE STRUCTURES AND MATERIALS. 5110 S KENWOOD AVE PERIODIC PASSED View
PIPE OPENING W/NONCOMBUST MATL PENTHOUSE - OPENINGS AND PIPE PENETRATIONS SEALED WITH SPRAY FOAM. 10TH FLOOR / ELECTRIC CONDUIT WIRE BOX - OPEN 2" DIAMETER PIPES TO BE CAPPED OR SEALED. ALL FLOORS, NEAR FIRE ESCAPE DOORS - CONDUIT CABLE PENETRATION HOLES SEALED WITH BLACK SUBSTANCE. 2ND FLOOR CORRIDOR, NEAR 207 - CABLE PENETRATIONS SEALED WITH SPRAY FOAM. 1ST FLOOR / FIRE PUMP ROOM - WALLS AND CEILING PIPE PENETRATIONS, WITH LOOSE BRICKS. BOILER ROOM AND STORAGE CLOSET, NEAR LAUNDRY ROOM - PIPE PENETRATIONS SEALED WITH SPRAY FOAMS. REMOVE ALL EXPANDABLE SPRAY FOAMS, AND SEAL ALL OPENINGS WITH PROPER FIRE-STOPPING MATERIALS SUCH AS FIRE CAULK, WITH MINERAL WOOL BACK-UP. SUBMIT DOCUMENTATION THAT FIRE-STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARD. 5110 S KENWOOD AVE PERIODIC PASSED View
CLASS B DOOR IN STAIRWELL PENTHOUSE - STAIRWELL DOOR TO ELEVATOR MACHINE ROOM BROKEN. 5110 S KENWOOD AVE PERIODIC PASSED View
2-HR STAIR ENCLOSURE, 4+ STORY PENTHOUSE / STAIRWELL - PLYWOOD BOARDS CEILING, WITH OPENING. 10TH FLOOR / STAIRWELL - OPENING ON WALL, WITH NON FIRE-RATED ACCESS PANEL DOOR. 5110 S KENWOOD AVE PERIODIC PASSED View
REPAIR INTERIOR STAIR SYSTEM 10TH FLOOR TO PENTHOUSE / INTERIOR STAIRWAY - TREADS AND RISERS RUSTING AND SEPARATING. 5110 S KENWOOD AVE PERIODIC PASSED View
REPAIR/REPLACE SMOKE DETECTORS SOME UNITS, INCLUDING 805, 807 AND 907 - SMOKE DETECTORS - OUT OF SERVICE, WITH LOW AND MISSING BATTERIES. 5110 S KENWOOD AVE PERIODIC PASSED View
SELF-CLOSE DOOR >4 STORY RES. DOORS NOT CLOSING AND LATCHING PROPERLY: 305, 605 (DOOR RUBBING ON RUG), 607, 610, 807, 808, 901 (WEATHER STRIPPING) AND 907. 5110 S KENWOOD AVE PERIODIC PASSED View
OBSTRUCTIONS IN EXIT WAY REMOVE OBSTRUCTION ON EXIT WAY: 605 - DOOR RUBBING ON THROW RUGS. 205 - EXIT WAY OBSTRUCTED BY LOOSE AND HANGING CABLES - TRIPPING HAZARD. 5110 S KENWOOD AVE PERIODIC PASSED View
INSTALL SMOKE DETECTORS BIKE ROOM - SMOKE DETECTOR - MISSING. 5110 S KENWOOD AVE PERIODIC PASSED View
1HR PUB.CORRIDOR IN MULT. D.U. STORAGE CLOSET, NEAR LAUNDRY ROOM - BREECHED WALLS, WITH CLAY TILES LOOSE AND WASHED OUT MORTAR. 5110 S KENWOOD AVE PERIODIC PASSED View
2-HR HEATING PLANT ENCLOSURE MASONRY WALL BETWEEN CORRIDOR AND BOILER ROOM BREECHED, AND USED AS TRASH CHUTE OPENING INTO BOILER ROOM. 5110 S KENWOOD AVE PERIODIC PASSED View
2HR SEP FOR STORAGE >100SF SEPARATE TRASH ROOM FROM BOILER ROOM WITH 2-HOUR ENCLOSURE AND CLASS B DOOR ASSEMBLY. TRASH ROOM MUST BE EQUIPPED WITH FIRE SPRINKLERS. PLANS AND PERMIT REQUIRED. 5110 S KENWOOD AVE PERIODIC PASSED View
PLANS & PERMITS REQ - CONTRCTR GARBAGE STORAGE ROOM CONSTRUCTED BETWEEN MAINTENCE ROOM AND CORRIDOR WALLS WITHOUT A PERMIT. NO VENTILATION; AND ENCLOSED WALL OPENED INTO CORRIDOR AND MISSING DOOR. SUBMIT PLANS AND OBTAIN PERMIT FOR RENOVATION. 5110 S KENWOOD AVE PERIODIC PASSED View
DOOR SWING IN DIR. OF TRAVEL LAUNDRY ROOM - DOOR SWINGS IN OPPOSITE DIRECTION OF EGRESS. 5110 S KENWOOD AVE PERIODIC PASSED View
PROVIDE NO FIRE SEPARATION BETWEEN ELECTRIC " MAIN" SERVICE DISCONNECTS AND LAUNDRY ROOM. PROVIDE 3-HOUR ENCLOSURE AND CLASS A DOOR ASSEMBLY FOR MAIN SERVICE DISCONNECTING MEANS PER SECTION CODE 18-27-230.2 (B)(2). 5110 S KENWOOD AVE PERIODIC PASSED View
INSTALL EXIT SIGN BIKE ROOM, LAUNDRY ROOM AND BOILER ROOM - EXIT SIGNS - MISSING. 5110 S KENWOOD AVE PERIODIC PASSED View
REPAIR DOOR HARDWARE 1ST FLOOR / CORRIDOR: DOOR RUBBING ON FLOOR AND MISSING LATCH 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR PHONES 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR ALARM BELL IN CAR #2 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM FIRE SERVICE PHASE II MANDATE 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA WEST ELEVATOR MAIN DRIVE SHEAVE SHOWS GROOVE WEAR.REPAIR/REPLACE 5110 S KENWOOD AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CITY OF CHICAGO FIRE SERVICE MANDATE UPGRADE ON BOTH ELEVATORS. 5110 S KENWOOD AVE PERIODIC FAILED View
SELF-CLOSE CLASS B FIRE DOOR ELEVATOR MACHINE ROOM - DOOR LABEL MISSING. ALL FLOORS: ELECTRIC CLOSETS, NEAR STAIRWELL DOORS, CHIMNEY WALL, NEAR REAR EMERGENCY EXIT DOOR, AND 5TH, 7TH, 9TH AND 10TH FLOORS / TELEPHONE CLOSETS - ACCESS PANEL DOORS MISSING. 1ST FLOOR / GARBAGE ROOM - DOOR MISSING. 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY 1 TEST 5110 S KENWOOD AVE PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY 1 AND CATEGORY 5 TESTS ON BOTH ELEVATORS 5110 S KENWOOD AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR EMERGENCY PHONES 5110 S KENWOOD AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR ELEVATOR #1 5110 S KENWOOD AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR ALARM BELLS 5110 S KENWOOD AVE PERIODIC FAILED View
INT WALL/CEILING CHIP PLASTER 1ST FLOOR FOYER / CEILINGS - CRACKED WITH WATER DAMAGE. STAIRWAY A - CHIPPED AND LOOSE PAINT. 10TH FLOOR HALLWAY CEILING - WATER DMAGD TILE. 5110 S KENWOOD AVE COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION INTERIOR OF APTS. - NO ENTRY, UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO VERIFY COMPLAINTS AT APTS 101 AND 108 FOR MOLD. 5110 S KENWOOD AVE COMPLAINT FAILED View
INSTALL EXTRA SMOKE DETECTORS TOP OF 10 FLOOR STAIRWAY / ADDITIONAL SMOKE DETECTOR - NEEDED. 5110 S KENWOOD AVE COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG LAUNDRY ROOM / FIRE EXTINGUISHER - MISSING TAG. 5110 S KENWOOD AVE COMPLAINT FAILED View
HOLDOPEN DEVICE, STAIR 3+ FLRS 1ST FLOOR HALLWAY AND LAUNDRY ROOM DOORS - HELD OPEN WITH WOOD WEDGES. 5110 S KENWOOD AVE COMPLAINT FAILED View
HEAT UNIT ADEQUATELY 60° AT TIME OF INSPECTION 12:35, HEAT IS OFF RADIATORS COLD. 5110 S KENWOOD AVE COMPLAINT FAILED View
HEAT UNIT ADEQUATELY 5110 S. / APT. 202 / LIVINGROOM AND BEDROOM TEMP WAS - 60 DEGREES AT 4:40PM. HEATING SYSTEM IS ON AT THE TIME OF INSPECTION, HEAT IS INSUFFICIENT. 5110 S KENWOOD AVE COMPLAINT FAILED View
HEAT UNIT ADEQUATELY 5110 S. / APT. 202 / LIVINGROOM AND BEDROOM TEMP WAS - 60 DEGREES AT 4:40PM. HEATING SYSTEM IS ON AT THE TIME OF INSPECTION, HEAT IS INSUFFICIENT. 5110 S KENWOOD AVE COMPLAINT CLOSED View