Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SUBMIT 2 COPY MAINTENANCE RPT | SUBMIT REPORTS AS REQUIRED BY EXTERIOR WALL ORDINANCE.LAST REPORT FILED IS THE 2002 CRITICAL.SHORT FORMS REQUIRED EVERY OTHER YEAR AFTER CRITICAL EXAMS.THE SHORT FORM DUE NO LATER THAN 11/1/2004 HAS NOT BEEN FILED AS OF 2/22/2006 | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
LIFE SAFETY EVALUATION PLAN | LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
REPAIR H/W DR INTERLOCK PASS | ALL FLOORS. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
REP/REPL DEF DRIVE MACH FRT | 434 W ROSCOE ST | PERIODIC | FAILED | View | |
TEST G & S ALL ELE | EV005887 | 434 W ROSCOE ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | 3RD AND 4TH FLOOR STAIRWELL DOORS WILL NOT CLOSE ALL THE WAY. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BUILDING NOT REGISTERED FROM 2006 THRU 2007 | 434 W ROSCOE ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR-(1) WEST ELEVATION SOUTHWEST CORNER WIRE MESH TEMPORARY HOLDING LOOSE DAMAGE BRICK (2) WEST ELEVATION AT LIGHT WELL AREA NORTHWEST CORNER (2ND RETURN) WIRE MESH TEMPORARY HOLDING LOOSE, DAMAGED BRICK (3) PLANS AND PERMITS FOR REPAIRS (4) EAST ELEVATION SEVERE STRUCTURAL CRACKS (5) ALL ELEVATIONS STRUCTURAL CRACKS OF BRICK, SPALLING, SEVERE WASHED OUT MORTAR. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
SYSTEM II | 18-27-700.3 (A) PROVIDE EMERGENCY SYSTEM COMPLAINT FOR HIGH RISE OVER 80 AND UNDER 300 NO EXISTING EMERGENCY PRESENTLY DANGEROUS AND HAZARDOUS | 434 W ROSCOE ST | COMPLAINT | PASSED | View |
DEFECTIVE PENDANT FIXTURE | BASEMENT SPLICES AND EXPOSED WIRING,LAMP GUARDS | 434 W ROSCOE ST | COMPLAINT | PASSED | View |
ADD BRANCH CIRCUITS | MUST PROVIDE AT LEAST ONE-20 AMP CIRCUIT FOR EACH RESIDENCE 18-27-570.10 | 434 W ROSCOE ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | 434 W ROSCOE ST | PERMIT | PASSED | View | |
SEND EX. METAL LETTER | EXPOSED METAL LETTER | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
REMOVE RUST | REMOVE RUST (TREADS) | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
USE NEW BOLTS OR RODS | NEW BOLTS OR RODS (TREADS) | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
PROTECT METAL MEMBERS | PROTECT METAL MEMBERS | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR-(1) WEST ELEVATION SOUTHWEST CORNER WIRE MESH TEMPORARY HOLDING LOOSE DAMAGE BRICK (2) WEST ELEVATION AT LIGHT WELL AREA NORTHWEST CORNER (2ND RETURN) WIRE MESH TEMPORARY HOLDING LOOSE, DAMAGED BRICK (3) PLANS AND PERMITS FOR REPAIRS (4) EAST ELEVATION SEVERE STRUCTURAL CRACKS (5) ALL ELEVATIONS STRUCTURAL CRACKS OF BRICK, SPALLING, SEVERE WASHED OUT MORTAR. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR EMERGENCY PHONE PANEL HANDLE TO OPEN | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR RESTRICTOR ON PASSENGER | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL RESTRICTOR ON FREIGHT CAR | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL CAPACITY PLATES - BOTH ELEVATORS | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL PROPER ACCESS TO MACHINE DECKS - NO TOE HOLES | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COMPLETE CANOPY ON FREIGHT ELEVATOR - FALL PROTECTION | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PORIVDE BULB PROTECTION - FREIGHT ELEVATOR | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIX BAD MACHINE OIL LEAK - FRIEGHT ELEVATOR | 434 W ROSCOE ST | PERIODIC | PASSED | View |
ARRANGE FOR REINSPECTION REGAR | INTERIOR OF BUILDING NO RESPONSE,UNVERIFIED COMPLAINT OF CABLE LINES HANGING OFF BUILDING.UNVERIFIED DETECTORS AND CONDITIONS. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | SOUTH AT 1ST - ABOVE GARAGE DOOR AND ABOVE CORRIDOR ENTRANCE - STONE SECTIONS LOOSE WITH MISSING MORTAR. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | BUIDING INNER INTERIOR - NO RESPONSE - UNABLE TO VERIFY DETECTORS AND CONDITIONS. UNABLE TO INSPECT INTERIOR STAIRWAYS , FIRE ESCAPES , GARAGE , AND MECHANICAL ROOMS. UNABLE TO VERIFY COMPLIANCE OF PREVIOUS VIOLATION WRITTEN ON 01 / 12 / 2009. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE MACHINE ON FRT. ELEVATOR | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM AND DOCUMENT CATEGORY 5 TEST | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROGRAM EMERGENCY PHONE | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR DOOR RESTRICTORS | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | UPGRADE FIREMAN'S SERVICE TO COMPLY WITH CHICAGO BUILDING CODE 18-30-320 (1/1/2017) | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | NEW MACHINE CAR CANT RUN | 434 W ROSCOE ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR PHONE | 434 W ROSCOE ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL FACIA 1ST FLR PASNGR HATCH DOOR SIDE | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL GLASS IN VISION PANELS DOOR AND BACK WALL CAB PASNGR | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR DOOR RESTRICTORS PASENGER CAR | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE RECALL NOT WORKING | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ADDITIONAL LIGHTING MACH. RM AND PIT ALSO INSTALL PIT LADDER AND LIGHT WITH EMERGENCY SWITCH IN PIT | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE EQUIPMENT FROM MACH ROOM NOT BEING USED OLD MOTORS ROTATING ELEMENTS ETC. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BULB PROTCTION AND MORE LIGHTING MACH. RM | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MACH. RM ROOF LEAKING BACK OF FRT CAR CONTROLLER | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CURRENT FIRE TEST LOG MACH. RM. | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAT-1 BOTH CARS | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PACTCH HOISTWAY AND MACHINE ROOM 2HR FIRE RATED | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CHANGE MAIN LINE DISCONNECT HEAVY DUTY AND ADD 110 VOLT DEDICATED DISCONNECT . | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CANT ALL LEDGESIN HOISTWAY | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE WATER FROM ELEVATOR PIT | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DO COMPLETE SAFETY TEST | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE MACHINE ROOM DOOR TO FIRE RATED DOOR | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL MORE LIGHTS AND GFI RECEPTACLES IN MACHINE ROOM AND ELEVATOR PITS | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DO A COMPLETE FIRE SERVICE TEST AND SMKE TEST | 434 W ROSCOE ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL AIR CONDITIONING TO MACHINE ROOM | 434 W ROSCOE ST | PERMIT | FAILED | View |
REPAIR EX. MET. | ENGINEER REPORT | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
PROPER SIZE GRD ELECTRODE COND | 434 W ROSCOE ST | COMPLAINT | PASSED | View | |
REMOVE ALL FOREIGN SYSTEMS FROM SWITCH BOARD ROOM 18-27-110.26 | 434 W ROSCOE ST | COMPLAINT | PASSED | View | |
SEE INSPECTOR COMMENTS | PROVIDE THREE HOUR RATING FOR SWITCH BOARD ROOM ENCLOSURE AND TWO HOUR RATING FOR EACH FLOOR TENANT LOAD DISTRIBUTION 18-27-230.70 | 434 W ROSCOE ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 5 TEST AND SEND FORMS TO THE CITY | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | POST CURRENT CERTIFICATES | 434 W ROSCOE ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECURE EMERGENCY ESCAPE EXIT AT TOP OF PASSENGER CAB | 434 W ROSCOE ST | PERIODIC | PASSED | View |
PROVIDE | FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) | 434 W ROSCOE ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FRT NO CAR TOP INSPECTION OPERATION | 434 W ROSCOE ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAT1 AND 5 TEST | 434 W ROSCOE ST | PERMIT | PASSED | View |