The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
TEST G & S PASS ELE | C & D CARS. | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
OBTAIN PERMIT FOR PASS ELE | B CAR. | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
REP/REPL DEF ALARM BELL PASS | EMERGENCY PHONE D CAR. | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
REPL GOVERNOR ROPE PASS | C & D CARS. | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
REMOVE DEBRIS FROM PIT PASS | ALL CARS. | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | 1. REPAIR ALL PASSENGER ELEVATOR DOOR RESTRICTING DEVICES. (13-156-201) 2. PERFORM ANNUAL PRESSURE RELIEF TESTS FOR A & B PASSENGER ELEVATORS; SEAL & TAG VALVES; SUBMIT TEST REPORT TO CITY OF CHICAGO ELEVATOR BUREAU 1005.2A. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | 1. REPAIR ALL PASSENGER ELEVATOR DOOR RESTRICTING DEVICES. (13-156-201) 2. PERFORM ANNUAL PRESSURE RELIEF TESTS FOR A & B PASSENGER ELEVATORS; SEAL & TAG VALVES; SUBMIT TEST REP | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | PHASE II FIRE SERVICE SHOULD NOT BECOME ACTIVE BY PULLING MAINLINE DISCONNECT. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | INSTALL DOOR GIBS WHERE MISSING AND BEND DOWN FIRE TABS. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | INSTALL COTTER PIN IN CWT, ROD (BOTTOM). | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | DOOR RESTRICTOR TO OPERATE PROPERLY. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | SECURE FASCIA AND/OR INSTALL DUST COVERS. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | REPLACE DEFECTIVE BOTTOM ACCESS SWITCH. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | INSTALL A TOE GUARD ON PLATFORM. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | CARTOP FIRE SERVICE JEWEL MUST WORK. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | IF PROVIDED, LOBBY POSTION INDICATOR MUST WORK. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | ELIMINATE HARSH RIDE BETWEEN 1 AND B (RAILS). 18-30-010, 13-20-120 100292485. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | INSTALL COFFER PIN IN CART, ROD (BOTTOM). | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | ELIMINATE HARSH RIDE BETWEEN 1 AND B (RAILS). 18-30-010, 13-20-120. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATORS A & B HYD.CYL.SHALL CONFORM TO CHICAGO BUILDING CODE SECTION 18-30-100 TEXT, ANSI 17.1.2007 3.18.3.4-8.6.5.8(A) 8.6.5.8(B) | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATORS A & B HYD.CYL.SHALL CONFORM TO C.B.C.SECTION 18-30-100 TEXT, ANSI 17.1.2007 3.18.3.4-8.6.5.8(A) 8.6.5.8(B) | 6130 N SHERIDAN RD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | TEST FIRE SERVICE AND SMOKE RECALL | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | A-CAR - REMOVE SPRINKLER FROM OVERHEAD AND PATCH HOLE | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL CAR ID'S ON ALL DOOR FRAMES | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | LABEL ALL HYDRAULIC LINES IN BUILDING | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: INSTALL FIRE TABS ON CAR DOORS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: SECURE PIT LADDER. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN ELEVATOR PITS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: CHECK REAR DOOR OPEN LIMIT IN FIRE SERVICE MODE. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: INSCRIBED CODE DATA TAG REQUIRED ON CONTROLLER OR DISCONNECT SWITCH. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: TIGHTEN OR REPACK HEAD TO ELIMINATE EXCESSIVE OIL LEAKING WHEN ON STOP RING. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: SHOW PROOF OF COMPLIANCE WITH BULKHEAD REQUIREMENTS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | A-CAR - INSTALL CARTOP LOW OVERHEAD & FALL HAZARD DANGER SIGNAGE. SAFETY STRIPE WARNING CARTOP EDGES | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR: IDENTIFY ELEVATOR AT ALL LANDINGS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR:CROSSHEAD DATA TAG REQUIRED. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR:48" TOE GUARD REQUIRED OR OBTAIN ADMINISTRATIVE RELIEF. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR: SPRINKLER AT TOP OF HOISTWAY REQUIRES SMOKE AND HEAT DETECTORS AND A SHUNT TRIP. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR: INSTALL AND PRETEST SMOKE DETECTORS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: LABEL ALL DISCONNECT SWITCHES WITH VOLTAGE AND USE. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR:FIRE TABS REQUIRED ON ALL LANDING DOORS. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: SHOW PROOF OF COMPLIANCE WITH SECTION 8.6.5.8 OF A17.1-2007 (BULKHEAD REQUIREMENTS) | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: INSCRIBED CODE DATA TAG REQUIRED ON CONTROLLER. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | D CAR: RETEST GOVERNOR AND SAFETIES AND ASCENDING CAR OVERSPEED WHEN MACHINE BEAMS ARE PROPERLY SECURED. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | B CAR: REPAIR CYLINDER HEAD TO PREVENT EXCESSIVE OIL LOSS WHEN ON STOP RING. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CHANGE CAPACITY ON CAR OPERATING PANEL FROM 3000# TO 2500# (PER CROSSHEAD DATA TAG) | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REGARDING MODERNIZATION PERMIT 100699070:SCHEDULE INSPECTION WITH SUBURBAN ELEVATOR TO CLOSE OPEN VIOLATIONS FROM 2018. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CARS C AND D: CLEAN ELEVATOR PITS. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS: CHECK 2 WAY COMMUNICATION (PHONES) FOR CORRECT OPERATION. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAR C: 1)CERTIFICATE FRAME REQUIRED IN ELEVATOR CAB. 2)WORKING DOOR RESTRICTOR REQUIRED 3)WORKING PIT LIGHT REQUIRED | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CARS B AND C: WORKING ALARM BELLS REQUIRED. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REGARDING REPAIR PERMIT 100789781: SCHEDULE INSPECTION WITH SUBURBAN ELEVATOR TO CLOSE OPEN VIOLATIONS FROM 2018. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CARS A AND B: INSTALL CARTOP SAFETY HANDRAILS. | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
PROV FIRE KEY BOX & KEYS PASS | A-B LOBBY. EV006130 | 6130 N SHERIDAN RD | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | IDENTIFY ELEVATOR AT ALL LANDINGS. | 6130 N SHERIDAN RD | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | LABEL ALL DISCONNECTS WITH VOLTAGE AND USE. | 6130 N SHERIDAN RD | PERMIT | FAILED | View |