Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | REPAIR DOOR RESTRICTOR CURRENTLY INOPERABLE AND UNSAFE CONDITION RULE 111.12. | 10022 S HALSTED ST | PERIODIC | CLOSED | View |
REP/REPL CAR PLATFORM PASS | SECURE CAR SILL AND TRANSITION STRIP. | 10022 S HALSTED ST | PERIODIC | CLOSED | View |
ELIMINATE TRIPPING HAZARD PASS | ADJUST VALUE FOR LEVELING. | 10022 S HALSTED ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | PERFORM ANNUAL FULL LOAD PRESSURE TEST RULE 1005.2A (CHAPTER 18-30 OF THE CITY OF CHICAGO BUILDING AND ASME 17.1 1996) (13-20-120, 18-30-010). EV002559 | 10022 S HALSTED ST | PERIODIC | CLOSED | View |
PROTECT METAL MEMBERS | 10022 S HALSTED ST | COMPLAINT | FAILED | View | |
SEND EX. METAL LETTER | 10022 S HALSTED ST | COMPLAINT | FAILED | View | |
REPAIR EXTERIOR DOOR | 3RD FLOOR EAST HALL DOOR RUBS | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR | 3RD FLOOR EAST HALL DOOR RUBS | 10022 S HALSTED ST | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | INSTALL EMERGENCY TELEPHONE ON ELEVATOR AND PROGRAM TO 24HR SOURCE | 10022 S HALSTED ST | PERIODIC | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | FRONT SIDEWALK AND SOUTH END OF BUILDING CRACKED AND BROKEN. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | SOUTH,WEST AND NORTH SIDE OF BUILDING CORROGATED STEEL FENCE,ALSO INSTALLING WROUGHT IRON GATE NO PERMIT. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
PERMIT REQUIRED - CONTRACTOR | SOUTH, WEST AND NORTH ELEVATIONS - 7 FEET HIGH CORROGATED STEEL FENCE AND WROUGHT IRON GATE INSTALLED WITHOUT A PERMIT. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR FLOOR | UNIT 223 / BATHROOM ENTRY WAY - LOOSE AND MISSING FLOOR TILES. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | BSMT. BOILER ROOM AND MOST UNITS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | UNIT 122: SMOKE DETECTOR - OUT OF SERVICE, WITH MISSING BATTERY. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR FLOOR | UNIT 223 / BATHROOM ENTRY WAY - LOOSE AND MISSING FLOOR TILES. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | BSMT. BOILER ROOM AND MOST UNITS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
WORK NOT ALLOWED | OBTAIN PERMIT FOR IRON FENCE OVER 5' AT SOUTH WEST AND NORTH ELEVATION AT PROPERTY, OR REDUCE HEIGHT | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REPAIR FENCE | IRON FENCE LEANING AT NORTH ELEVATION REPAIRS REQUIRED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
FIRE EXTNGSHR RECHARGE & TAG | FIRE EXTINGUISHERS THROUGHOUT PROPERTY REQUIRED RECHARGED AND RETAGED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REPAIR LINTELS | SOUTH/WEST ELEVATION ADDITION TO PROPERTY STORAGE ROOM ENTRY DOOR MISSING LINTEL OVER DOOR | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DRYER EXHAUST NUISANCE | REMOVE ACCESS OF LINT BUILD UP WITHIN LAUNDRY ROOM FROM DRYERS (DANGEROUS AND HAZARDOUS) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
CARPETING | ALL HALLWAY STAIR CARPETING SHALL BE REMOVED CURRENTLY CAUSING TRIP HAZARDS THROUGHOUT | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REMOVE | REMOVE ALL FLAMMABLE LIQUIDS FROM STORAGE/WORK SHOP LOCATED AT 1ST FLOOR NEXT TO OFFICE AREAS (DANGEROUS AND HAZARDOUS) 15-4-090 | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
HEATING PLANT/BOILER ROOM DOOR | CLASS B FIRE DOORS AND FRAMES REQUIRED FOR HEATING PLANT ROOMS AND HOT WATER TANK LOCATED WITHIN THE BASEMENT AREAS (DANGEROUS AND HAZARDOUS) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
STRUCTURAL MEMBER, PIER BLOCK | IMMEDIATE REPAIRS REQUIRED FOR CALIFORNIA STYLE PORCH SYSTEMS CURRENTLY STEEL WITH CONCRETE STYLED PORCH SYSTEM FAILING AND SEPARATING AT THE CONNECTIONS PREVIOUS REPAIRS DOES NOT SATISFY RUST DAMAGES 2 SOUTH TIER MISSING UPRIGHT STEEL POST FOR 2ND AND 3RD FLOOR FOR OVERSPANNED STEEL AND CONCRETE SYSTEM 3 PORCH SYSTEM RAILS UNSTABLE AND REQUIRE ADDITIONAL REINFORCE (DANGEROUS AND HAZARDOUS) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
SUBMIT STRUCT. ENG. RPT (INT.) | OBTAIN STRUCTURAL ENGINEERS REPORT TO DETERMINE REMEDIES FOR PORCH REPAIRS AND WHERE STRUCTURAL MEMBERS ARE REQUIRED THROUGHOUT PROPERTY | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PROVIDE SIDEWALK SHED F/PROTCT | CANOPY REQUIRED FOR FAILING PORCH SYSTEM OVER OFFICE AREAS (DANGEROUS AND HAZARDOUS) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS AND PERMITS IS REQUIRED FOR ADDITION ADDED TO PROPERTY AND BUT NOT LIMITED TO ALL CORRECTIONS OF BUILDING CODE VIOLATIONS THROUGHOUT PROPRTY | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PROVIDE OPEN FRONT TOILET SEAT | UNAPPROVED ROUND BOWL WITH CLOSED FRONT TOILET SEAT AT BATHROOM IN LAUNDRY ROOM AND UNITS 114 AND 113 ALL TOILETS TO BE ELONGATED TYPE WITH OPEN FRONT SEATS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PROPER MATRL WATER SUPPLY PIPE | UNAPPROVED FLEXIBLE WATER SUPPLIES TO BATHROOM TOILETS AND LAVATORIES THROUGHOUT ENTIRE PREMISES | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
STOP LEAKING WATER | LEAK AT SUSPENDED GALVANIZED PIPING AT BASEMENT MECHANICAL ROOM CEILING | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
KEEP FIXTUR CLEAN AND SANITARY | BATHROOM TOILETS, AND LAVATORIES IN A DIRTY UNSANITARY CONDITION THROUGHOUT PREMISES | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REPLACE DEFECTIVE PLBG FIXTURE | LAVATORY CABINET FALLING APART IN ROOM 113 | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REPLACE DEFECTIVE SOIL PIPING | SUSPENDED CAST IRON PIPING AT WEST WALL OF MECHANICAL ROOM IS DETERIORATED AND EXPOSED AT TOP OF PIPE IS EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS SEWER GAS AND DANGEROUS AND HAZARDOUS COLLAPSE CONDITION | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
INDIRECT CONN.FOR WATER SUPPLY | SOAP DISPENSER WATER CONNECTION IN LAUNDRY ROOM NEXT TO LAUNDRY SINK IS DIRECTLY CONNECTED TO WATER SUPPLY WITHOUT ANY MEANS OF BACKFLOW PROTECTION CROSS CONNECTION IS EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS CROSS CONTAMINATION OF POTABLE WATER | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
OPEN | BATHROOM LOCATED IN LAUNDRY ROOM IS MISSING FLOOR DRAIN (18-29-412.3) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
OBTAIN PERMIT FOR PLUMBING | OBTAIN PERMIT BEFORE CONSTRUCTING ALTERING OR USING PLUMBING SYSTEM | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
ENGAG LIC & BOND PLMBNG CNTRC | ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DEFECTIVE SERVICE | MAIN ELECTRICAL SERVICE HEAD IS NOT SECURED TO BUILDING ENSURE ALL ELECTRICAL SERVICE IN APPROVED CONDITION | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PROPER SIZE GRD ELECTRODE COND | NO VISIBLE WATER GROUND ENSURE ALL ELECTRICAL SERVICES GROUNDED IN APPROVED MANNER DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DEFECTIVE DISTRIBUTION | MISSING PANEL COVERS, OPEN PANELS, LOOSE PANEL COVES AT ELECTRICAL CLOSETS PANEL COVER AT GUEST ROOM 114 NOT SECURE CIRCUIT BREAKERS AT ROOM 114 PANEL APPEAR DETERIORATED TRANSFER SWITCH LOCATED AT BASEMENT ELECTRICAL ROOM IS OPEN AND APPEARS TO BE IN STATE OF DISREPAIR ENSURE ALL DISTRIBUTION EQUIPMENT THROUGHOUT PREMISES IN APPROVED CONDITION DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
SEE INSPECTOR COMMENTS | ELEVATOR CONTROLLER AT BASEMENT IS MISSING VARIOUS EQUIPMENT COVERS LAUNDRY DRYER IS MISSING EQUIPMENT COVERS REAR FURNACE COVER MISSING AT SOUTH 1ST FLOOR STORAGE ENSURE EQUIPMENT COVERS INSTALLED THROUGHOUT (14E-1-110.3) DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
INSTALL COVERS | OPEN BOXES VARIOUS AREAS BASEMENT OPEN BOX BEHIND SINK AT GUEST ROOM 113 OPEN BOXES 1ST FLOOR MAINTENANCE ROOM CLOSE OPEN BOXES WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
EXPOSED WIRING | OPEN WIRING AT MAIN OFFICE OPEN WIRING AT ELECTRICAL CLOSETS REMOVE OPEN WRING WHERE REQUIRED THROUGHOUT DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PANEL SCHEDULES | INSUFFICIENT ILLEGIBLE PANEL SCHEDULES THROUGHOUT PREMISES | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
SUPPORT FIXTURES | VARIOUS EXTERIOR LIGHT FIXTURES NOT SECURELY SUPPORTED LIGHT FIXTURE AT LAUNDRY CEILING NOT SUPPORTED IN APPROVED MANNER SECURE LIGHT FIXTURES IN APPROVED MANNER THROUGHOUT PREMISES | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
WORKING SPACE | INSUFFICIENT WORKING SPACE AT LAUNDRY ROOM PANEL ENSURE WORKING SPACE WHERE REQUIRED THROUGHOUT | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
INSTALL GFCI'S | INSTALL GFCI PROTECTION OFFICE BATH, BASEMENT, EXTERIOR AND WHERE REQUIRED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
ADD RECEPTACLES | ADD RECEPTACLES AT BASEMENT FRONT COUNTER AREA AND WHERE REQUIRED TO PREVENT EXTENSION CORD USAGE | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DEFECTIVE FIXTURES | DAMAGED LIGHT FIXTURES AT 1ST FLOOR MAINTENANCE ROOM AND BASEMENT REPLACE LIGHT FIXTURES WHERE REQUIRED THROUGHOUT | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DEFECTIVE OUTLETS | EXCESSIVELY PAINTED RECEPTACLES AT VARIOUS GUEST ROOMS REPLACE DEFECTIVE SWITCHES/RECEPTACLES WHERE REQUIRED THROUGHOUT | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
PROVIDE PERMIT TO CORRECT VIOLATIONS (14A-4-404.6) | 10022 S HALSTED ST | COMPLAINT | PASSED | View | |
STOP SMOKE, NOXIOUS ODORS | FOUL ODORS FROM ROOMS AT TIME OF INSPECTION | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 10022 S HALSTED ST | PERIODIC | CLOSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CAT 1 TEST AND PROVIDE DOCUMENTATION | 10022 S HALSTED ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR EMERGENCY PHONE FOR 24HR-2WAY COMMUNICATION INSIDE ELEVATOR | 10022 S HALSTED ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR CAR DOOR RESTRICTOR. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR EMERGENCY PHONE INSIDE ELEVATOR. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE MISSING 1ST FLOOR BRAILLE PLATE INSIDE CAB. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE MISSING DOOR LOCK COVERS. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE DOCUMENTATION OF HYDROLIC CYLINDER HAVING DOUBLE BOTTOM. REPLACE IF NECESSARY. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
RESTORE EXIT AND EM | EMERGENCY LIGHTING SYSTEM NOT OPERABLE AT OFFICE AND BASEMENT AREA EXTERIOR EXIT SIGNS NOT SUITABLE FOR WET LOCATION ENSURE EMERGENCY SYSTEM IN APPROVED OPERABLE CONDITION DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
EXTERIOR LIGHT FIXTURES BOXES FITTINGS RACEWAYS MUST BE SUITABLE FOR WET LOCATIONS (14E-1-110.3) | 10022 S HALSTED ST | COMPLAINT | PASSED | View | |
REPLACE DEFECTIVE FAUCET | LAUNDRY SINK IN LAUNDRY ROOM FAUCET LEAKING | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
ROACHES | ROACH INFESTATION THROUGHOUT BASEMENT AREAS EXTERMIATOR REQUIRED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | ALL AREAS WHERE PIPE PENETRATIONS ARE PRESENT SHALL REQUIRE FIRE RESISTANT MATERIAL SUCH AS FIRE CAULK/OR CEMENT WHERE NECESSARY CURRENTLY PIPE PENETRATION WITHIN ELECTRICAL ROOM BASEMENT AREAS AND LAUNDRY ROOMS REQUIRE IMMEDIATE ATTENTION (DANGEROUS AND HAZARDOUS) | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | FULL ENTRY TO ENTIRE PROPERTY REQUIRED PARTIAL ENTRY TO ROOMS WITH FULL ENTRY TO COMMON AREAS AND EXTERIOR OF PROPERTY ENTRY TO ROOMS 114, 113, 318, 319 | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
REPAIR INTERIOR WALLS/CEILING | DRYWALL SOFFIT WITHIN LAUNDRY ROOM DETERIORATING REPAIRS REQUIRED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
DWELLING CLEAN AND SANITARY | UNSANITARY CONDITIONS AT PROPERTY CURRENTLY ROOMS CARPET SOILED TO EXTENT THAT REMOVAL IS REQUIRED | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
CLOSE BOX OPENINGS | EXCESSIVE MISSING PANEL FILLERS AT ELECTRICAL CLOSET PANELS AND BASEMENT INSTALL PANEL AND BOX FILLERS WHERE REQUIRED DANGEROUS AND HAZARDOUS | 10022 S HALSTED ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CLEAN PIT OF EXCESSIVE DEBRIS | 10022 S HALSTED ST | PERIODIC | PASSED | View |
PERMIT REQUIRED - CONTRACTOR | SOUTH, WEST AND NORTH ELEVATIONS - 7 FEET HIGH CORROGATED STEEL FENCE AND WROUGHT IRON GATE INSTALLED WITHOUT A PERMIT. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | MOST ROOMS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | UNIT 122: SMOKE DETECTOR - OUT OF SERVICE, WITH MISSING BATTERY. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
FILE BLDG REGISTRATION | BLDG. - NOT REGISTERED FROM 1990 THRU 2017. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
SUPPLY HOT WTR MIN TEMP 120DEG | MOST ROOMS, INCLUDING 211 AND 123 - LOW HOT WATER PRESSURE. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | MOST ROOMS, INCLUDING 211, 324, HALLS AND EAST STAIRWELL - SMOKE DETECTORS - OUT OF SERVICE. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | MANAGEMENT BATHROOM - WALLS AND CEILING - WATER DAMAGE, WITH PEELING PAINT. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR EMERGENCY BELL INSIDE ELEVATOR | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR LEVELING 1ST FLOOR LANDING | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR OIL LEAKIMG & CORROSION ON CYLINDER, POSSIBLY NEED REPACKING. | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A PIT LADDER AND PIT LIGHT FOR ELEVATOR | 10022 S HALSTED ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CAT1 TEST AND PROVIDE DOCUMENTATION | 10022 S HALSTED ST | PERIODIC | PASSED | View |
OPEN TYPE VIOLATION | REPAIR OR REPLACE EMERGENCY ALARM BELL. | 10022 S HALSTED ST | PERIODIC | FAILED | View |
INSTALL | CARBON MONOXIDE DETECTOR IN BOILER ROOM. | 10022 S HALSTED ST | PERIODIC | CLOSED | View |