Chicago Building Violations Data: 86 Violations
Violation Inspector Comments Address Category Status View
OPEN TYPE VIOLATION REPAIR DOOR RESTRICTOR CURRENTLY INOPERABLE AND UNSAFE CONDITION RULE 111.12. 10022 S HALSTED ST PERIODIC CLOSED View
REP/REPL CAR PLATFORM PASS SECURE CAR SILL AND TRANSITION STRIP. 10022 S HALSTED ST PERIODIC CLOSED View
ELIMINATE TRIPPING HAZARD PASS ADJUST VALUE FOR LEVELING. 10022 S HALSTED ST PERIODIC CLOSED View
OPEN TYPE VIOLATION PERFORM ANNUAL FULL LOAD PRESSURE TEST RULE 1005.2A (CHAPTER 18-30 OF THE CITY OF CHICAGO BUILDING AND ASME 17.1 1996) (13-20-120, 18-30-010). EV002559 10022 S HALSTED ST PERIODIC CLOSED View
PROTECT METAL MEMBERS 10022 S HALSTED ST COMPLAINT FAILED View
SEND EX. METAL LETTER 10022 S HALSTED ST COMPLAINT FAILED View
REPAIR EXTERIOR DOOR 3RD FLOOR EAST HALL DOOR RUBS 10022 S HALSTED ST PERIODIC FAILED View
REPAIR EXTERIOR DOOR 3RD FLOOR EAST HALL DOOR RUBS 10022 S HALSTED ST PERIODIC FAILED View
OPEN TYPE VIOLATION INSTALL EMERGENCY TELEPHONE ON ELEVATOR AND PROGRAM TO 24HR SOURCE 10022 S HALSTED ST PERIODIC FAILED View
SERVICE WALK, PASSAGE, AREAWAY FRONT SIDEWALK AND SOUTH END OF BUILDING CRACKED AND BROKEN. 10022 S HALSTED ST PERIODIC FAILED View
PERMIT REQUIRED - CONTRACTOR SOUTH,WEST AND NORTH SIDE OF BUILDING CORROGATED STEEL FENCE,ALSO INSTALLING WROUGHT IRON GATE NO PERMIT. 10022 S HALSTED ST PERIODIC FAILED View
PERMIT REQUIRED - CONTRACTOR SOUTH, WEST AND NORTH ELEVATIONS - 7 FEET HIGH CORROGATED STEEL FENCE AND WROUGHT IRON GATE INSTALLED WITHOUT A PERMIT. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR FLOOR UNIT 223 / BATHROOM ENTRY WAY - LOOSE AND MISSING FLOOR TILES. 10022 S HALSTED ST PERIODIC FAILED View
ARRANGE PREMISE INSPECTION BSMT. BOILER ROOM AND MOST UNITS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS UNIT 122: SMOKE DETECTOR - OUT OF SERVICE, WITH MISSING BATTERY. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR FLOOR UNIT 223 / BATHROOM ENTRY WAY - LOOSE AND MISSING FLOOR TILES. 10022 S HALSTED ST PERIODIC FAILED View
ARRANGE PREMISE INSPECTION BSMT. BOILER ROOM AND MOST UNITS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. 10022 S HALSTED ST PERIODIC FAILED View
WORK NOT ALLOWED OBTAIN PERMIT FOR IRON FENCE OVER 5' AT SOUTH WEST AND NORTH ELEVATION AT PROPERTY, OR REDUCE HEIGHT 10022 S HALSTED ST COMPLAINT PASSED View
REPAIR FENCE IRON FENCE LEANING AT NORTH ELEVATION REPAIRS REQUIRED 10022 S HALSTED ST COMPLAINT PASSED View
FIRE EXTNGSHR RECHARGE & TAG FIRE EXTINGUISHERS THROUGHOUT PROPERTY REQUIRED RECHARGED AND RETAGED 10022 S HALSTED ST COMPLAINT PASSED View
REPAIR LINTELS SOUTH/WEST ELEVATION ADDITION TO PROPERTY STORAGE ROOM ENTRY DOOR MISSING LINTEL OVER DOOR 10022 S HALSTED ST COMPLAINT PASSED View
DRYER EXHAUST NUISANCE REMOVE ACCESS OF LINT BUILD UP WITHIN LAUNDRY ROOM FROM DRYERS (DANGEROUS AND HAZARDOUS) 10022 S HALSTED ST COMPLAINT PASSED View
CARPETING ALL HALLWAY STAIR CARPETING SHALL BE REMOVED CURRENTLY CAUSING TRIP HAZARDS THROUGHOUT 10022 S HALSTED ST COMPLAINT PASSED View
REMOVE REMOVE ALL FLAMMABLE LIQUIDS FROM STORAGE/WORK SHOP LOCATED AT 1ST FLOOR NEXT TO OFFICE AREAS (DANGEROUS AND HAZARDOUS) 15-4-090 10022 S HALSTED ST COMPLAINT PASSED View
HEATING PLANT/BOILER ROOM DOOR CLASS B FIRE DOORS AND FRAMES REQUIRED FOR HEATING PLANT ROOMS AND HOT WATER TANK LOCATED WITHIN THE BASEMENT AREAS (DANGEROUS AND HAZARDOUS) 10022 S HALSTED ST COMPLAINT PASSED View
STRUCTURAL MEMBER, PIER BLOCK IMMEDIATE REPAIRS REQUIRED FOR CALIFORNIA STYLE PORCH SYSTEMS CURRENTLY STEEL WITH CONCRETE STYLED PORCH SYSTEM FAILING AND SEPARATING AT THE CONNECTIONS PREVIOUS REPAIRS DOES NOT SATISFY RUST DAMAGES 2 SOUTH TIER MISSING UPRIGHT STEEL POST FOR 2ND AND 3RD FLOOR FOR OVERSPANNED STEEL AND CONCRETE SYSTEM 3 PORCH SYSTEM RAILS UNSTABLE AND REQUIRE ADDITIONAL REINFORCE (DANGEROUS AND HAZARDOUS) 10022 S HALSTED ST COMPLAINT PASSED View
SUBMIT STRUCT. ENG. RPT (INT.) OBTAIN STRUCTURAL ENGINEERS REPORT TO DETERMINE REMEDIES FOR PORCH REPAIRS AND WHERE STRUCTURAL MEMBERS ARE REQUIRED THROUGHOUT PROPERTY 10022 S HALSTED ST COMPLAINT PASSED View
PROVIDE SIDEWALK SHED F/PROTCT CANOPY REQUIRED FOR FAILING PORCH SYSTEM OVER OFFICE AREAS (DANGEROUS AND HAZARDOUS) 10022 S HALSTED ST COMPLAINT PASSED View
PLANS & PERMITS REQ - CONTRCTR PLANS AND PERMITS IS REQUIRED FOR ADDITION ADDED TO PROPERTY AND BUT NOT LIMITED TO ALL CORRECTIONS OF BUILDING CODE VIOLATIONS THROUGHOUT PROPRTY 10022 S HALSTED ST COMPLAINT PASSED View
PROVIDE OPEN FRONT TOILET SEAT UNAPPROVED ROUND BOWL WITH CLOSED FRONT TOILET SEAT AT BATHROOM IN LAUNDRY ROOM AND UNITS 114 AND 113 ALL TOILETS TO BE ELONGATED TYPE WITH OPEN FRONT SEATS 10022 S HALSTED ST COMPLAINT PASSED View
PROPER MATRL WATER SUPPLY PIPE UNAPPROVED FLEXIBLE WATER SUPPLIES TO BATHROOM TOILETS AND LAVATORIES THROUGHOUT ENTIRE PREMISES 10022 S HALSTED ST COMPLAINT PASSED View
STOP LEAKING WATER LEAK AT SUSPENDED GALVANIZED PIPING AT BASEMENT MECHANICAL ROOM CEILING 10022 S HALSTED ST COMPLAINT PASSED View
KEEP FIXTUR CLEAN AND SANITARY BATHROOM TOILETS, AND LAVATORIES IN A DIRTY UNSANITARY CONDITION THROUGHOUT PREMISES 10022 S HALSTED ST COMPLAINT PASSED View
REPLACE DEFECTIVE PLBG FIXTURE LAVATORY CABINET FALLING APART IN ROOM 113 10022 S HALSTED ST COMPLAINT PASSED View
REPLACE DEFECTIVE SOIL PIPING SUSPENDED CAST IRON PIPING AT WEST WALL OF MECHANICAL ROOM IS DETERIORATED AND EXPOSED AT TOP OF PIPE IS EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS SEWER GAS AND DANGEROUS AND HAZARDOUS COLLAPSE CONDITION 10022 S HALSTED ST COMPLAINT PASSED View
INDIRECT CONN.FOR WATER SUPPLY SOAP DISPENSER WATER CONNECTION IN LAUNDRY ROOM NEXT TO LAUNDRY SINK IS DIRECTLY CONNECTED TO WATER SUPPLY WITHOUT ANY MEANS OF BACKFLOW PROTECTION CROSS CONNECTION IS EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS CROSS CONTAMINATION OF POTABLE WATER 10022 S HALSTED ST COMPLAINT PASSED View
OPEN BATHROOM LOCATED IN LAUNDRY ROOM IS MISSING FLOOR DRAIN (18-29-412.3) 10022 S HALSTED ST COMPLAINT PASSED View
OBTAIN PERMIT FOR PLUMBING OBTAIN PERMIT BEFORE CONSTRUCTING ALTERING OR USING PLUMBING SYSTEM 10022 S HALSTED ST COMPLAINT PASSED View
ENGAG LIC & BOND PLMBNG CNTRC ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING 10022 S HALSTED ST COMPLAINT PASSED View
DEFECTIVE SERVICE MAIN ELECTRICAL SERVICE HEAD IS NOT SECURED TO BUILDING ENSURE ALL ELECTRICAL SERVICE IN APPROVED CONDITION 10022 S HALSTED ST COMPLAINT PASSED View
PROPER SIZE GRD ELECTRODE COND NO VISIBLE WATER GROUND ENSURE ALL ELECTRICAL SERVICES GROUNDED IN APPROVED MANNER DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
DEFECTIVE DISTRIBUTION MISSING PANEL COVERS, OPEN PANELS, LOOSE PANEL COVES AT ELECTRICAL CLOSETS PANEL COVER AT GUEST ROOM 114 NOT SECURE CIRCUIT BREAKERS AT ROOM 114 PANEL APPEAR DETERIORATED TRANSFER SWITCH LOCATED AT BASEMENT ELECTRICAL ROOM IS OPEN AND APPEARS TO BE IN STATE OF DISREPAIR ENSURE ALL DISTRIBUTION EQUIPMENT THROUGHOUT PREMISES IN APPROVED CONDITION DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
SEE INSPECTOR COMMENTS ELEVATOR CONTROLLER AT BASEMENT IS MISSING VARIOUS EQUIPMENT COVERS LAUNDRY DRYER IS MISSING EQUIPMENT COVERS REAR FURNACE COVER MISSING AT SOUTH 1ST FLOOR STORAGE ENSURE EQUIPMENT COVERS INSTALLED THROUGHOUT (14E-1-110.3) DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
INSTALL COVERS OPEN BOXES VARIOUS AREAS BASEMENT OPEN BOX BEHIND SINK AT GUEST ROOM 113 OPEN BOXES 1ST FLOOR MAINTENANCE ROOM CLOSE OPEN BOXES WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
EXPOSED WIRING OPEN WIRING AT MAIN OFFICE OPEN WIRING AT ELECTRICAL CLOSETS REMOVE OPEN WRING WHERE REQUIRED THROUGHOUT DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
PANEL SCHEDULES INSUFFICIENT ILLEGIBLE PANEL SCHEDULES THROUGHOUT PREMISES 10022 S HALSTED ST COMPLAINT PASSED View
SUPPORT FIXTURES VARIOUS EXTERIOR LIGHT FIXTURES NOT SECURELY SUPPORTED LIGHT FIXTURE AT LAUNDRY CEILING NOT SUPPORTED IN APPROVED MANNER SECURE LIGHT FIXTURES IN APPROVED MANNER THROUGHOUT PREMISES 10022 S HALSTED ST COMPLAINT PASSED View
WORKING SPACE INSUFFICIENT WORKING SPACE AT LAUNDRY ROOM PANEL ENSURE WORKING SPACE WHERE REQUIRED THROUGHOUT 10022 S HALSTED ST COMPLAINT PASSED View
INSTALL GFCI'S INSTALL GFCI PROTECTION OFFICE BATH, BASEMENT, EXTERIOR AND WHERE REQUIRED 10022 S HALSTED ST COMPLAINT PASSED View
ADD RECEPTACLES ADD RECEPTACLES AT BASEMENT FRONT COUNTER AREA AND WHERE REQUIRED TO PREVENT EXTENSION CORD USAGE 10022 S HALSTED ST COMPLAINT PASSED View
DEFECTIVE FIXTURES DAMAGED LIGHT FIXTURES AT 1ST FLOOR MAINTENANCE ROOM AND BASEMENT REPLACE LIGHT FIXTURES WHERE REQUIRED THROUGHOUT 10022 S HALSTED ST COMPLAINT PASSED View
DEFECTIVE OUTLETS EXCESSIVELY PAINTED RECEPTACLES AT VARIOUS GUEST ROOMS REPLACE DEFECTIVE SWITCHES/RECEPTACLES WHERE REQUIRED THROUGHOUT 10022 S HALSTED ST COMPLAINT PASSED View
PROVIDE PERMIT TO CORRECT VIOLATIONS (14A-4-404.6) 10022 S HALSTED ST COMPLAINT PASSED View
STOP SMOKE, NOXIOUS ODORS FOUL ODORS FROM ROOMS AT TIME OF INSPECTION 10022 S HALSTED ST COMPLAINT PASSED View
OWNER OR LICENSED CONTRACTOR 10022 S HALSTED ST PERIODIC CLOSED View
MAINTAIN OR REPAIR HYDRO ELEVA PERFORM CAT 1 TEST AND PROVIDE DOCUMENTATION 10022 S HALSTED ST PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR EMERGENCY PHONE FOR 24HR-2WAY COMMUNICATION INSIDE ELEVATOR 10022 S HALSTED ST PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR CAR DOOR RESTRICTOR. 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR EMERGENCY PHONE INSIDE ELEVATOR. 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPLACE MISSING 1ST FLOOR BRAILLE PLATE INSIDE CAB. 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPLACE MISSING DOOR LOCK COVERS. 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE DOCUMENTATION OF HYDROLIC CYLINDER HAVING DOUBLE BOTTOM. REPLACE IF NECESSARY. 10022 S HALSTED ST PERIODIC PASSED View
RESTORE EXIT AND EM EMERGENCY LIGHTING SYSTEM NOT OPERABLE AT OFFICE AND BASEMENT AREA EXTERIOR EXIT SIGNS NOT SUITABLE FOR WET LOCATION ENSURE EMERGENCY SYSTEM IN APPROVED OPERABLE CONDITION DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
EXTERIOR LIGHT FIXTURES BOXES FITTINGS RACEWAYS MUST BE SUITABLE FOR WET LOCATIONS (14E-1-110.3) 10022 S HALSTED ST COMPLAINT PASSED View
REPLACE DEFECTIVE FAUCET LAUNDRY SINK IN LAUNDRY ROOM FAUCET LEAKING 10022 S HALSTED ST COMPLAINT PASSED View
ROACHES ROACH INFESTATION THROUGHOUT BASEMENT AREAS EXTERMIATOR REQUIRED 10022 S HALSTED ST COMPLAINT PASSED View
1HR PUB.CORRIDOR IN MULT. D.U. ALL AREAS WHERE PIPE PENETRATIONS ARE PRESENT SHALL REQUIRE FIRE RESISTANT MATERIAL SUCH AS FIRE CAULK/OR CEMENT WHERE NECESSARY CURRENTLY PIPE PENETRATION WITHIN ELECTRICAL ROOM BASEMENT AREAS AND LAUNDRY ROOMS REQUIRE IMMEDIATE ATTENTION (DANGEROUS AND HAZARDOUS) 10022 S HALSTED ST COMPLAINT PASSED View
ARRANGE PREMISE INSPECTION FULL ENTRY TO ENTIRE PROPERTY REQUIRED PARTIAL ENTRY TO ROOMS WITH FULL ENTRY TO COMMON AREAS AND EXTERIOR OF PROPERTY ENTRY TO ROOMS 114, 113, 318, 319 10022 S HALSTED ST COMPLAINT PASSED View
REPAIR INTERIOR WALLS/CEILING DRYWALL SOFFIT WITHIN LAUNDRY ROOM DETERIORATING REPAIRS REQUIRED 10022 S HALSTED ST COMPLAINT PASSED View
DWELLING CLEAN AND SANITARY UNSANITARY CONDITIONS AT PROPERTY CURRENTLY ROOMS CARPET SOILED TO EXTENT THAT REMOVAL IS REQUIRED 10022 S HALSTED ST COMPLAINT PASSED View
CLOSE BOX OPENINGS EXCESSIVE MISSING PANEL FILLERS AT ELECTRICAL CLOSET PANELS AND BASEMENT INSTALL PANEL AND BOX FILLERS WHERE REQUIRED DANGEROUS AND HAZARDOUS 10022 S HALSTED ST COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA CLEAN PIT OF EXCESSIVE DEBRIS 10022 S HALSTED ST PERIODIC PASSED View
PERMIT REQUIRED - CONTRACTOR SOUTH, WEST AND NORTH ELEVATIONS - 7 FEET HIGH CORROGATED STEEL FENCE AND WROUGHT IRON GATE INSTALLED WITHOUT A PERMIT. 10022 S HALSTED ST PERIODIC FAILED View
ARRANGE PREMISE INSPECTION MOST ROOMS: ENTRY REFUSED BY MANAGEMENT - UNVERIFIED DETECTORS AND CONDITIONS. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS UNIT 122: SMOKE DETECTOR - OUT OF SERVICE, WITH MISSING BATTERY. 10022 S HALSTED ST PERIODIC FAILED View
FILE BLDG REGISTRATION BLDG. - NOT REGISTERED FROM 1990 THRU 2017. 10022 S HALSTED ST PERIODIC FAILED View
SUPPLY HOT WTR MIN TEMP 120DEG MOST ROOMS, INCLUDING 211 AND 123 - LOW HOT WATER PRESSURE. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR/REPLACE SMOKE DETECTORS MOST ROOMS, INCLUDING 211, 324, HALLS AND EAST STAIRWELL - SMOKE DETECTORS - OUT OF SERVICE. 10022 S HALSTED ST PERIODIC FAILED View
REPAIR INTERIOR WALLS/CEILING MANAGEMENT BATHROOM - WALLS AND CEILING - WATER DAMAGE, WITH PEELING PAINT. 10022 S HALSTED ST PERIODIC FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR EMERGENCY BELL INSIDE ELEVATOR 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR LEVELING 1ST FLOOR LANDING 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR OIL LEAKIMG & CORROSION ON CYLINDER, POSSIBLY NEED REPACKING. 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE A PIT LADDER AND PIT LIGHT FOR ELEVATOR 10022 S HALSTED ST PERIODIC PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA PERFORM CAT1 TEST AND PROVIDE DOCUMENTATION 10022 S HALSTED ST PERIODIC PASSED View
OPEN TYPE VIOLATION REPAIR OR REPLACE EMERGENCY ALARM BELL. 10022 S HALSTED ST PERIODIC FAILED View
INSTALL CARBON MONOXIDE DETECTOR IN BOILER ROOM. 10022 S HALSTED ST PERIODIC CLOSED View