Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | 1. PROPERLY REPAIR AND MAINTAIN WEST ELEVATOR. ELEVATOR IS CURRENTLY OUT OF SERVICE. 2. REPAIR BOTH DOOR RESTRICTORS TO OPERATE PROPERLY. 18-30-010,13-20-120 EV006105 | 5800 N SHERIDAN RD | PERIODIC | PASSED | View |
DEFECTIVE FIXTURES | IN STORAGE AREA'S LAUNDRY ROOM,AND MAIN ELECTRICAL ROOM | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
INSTALL COVERS | METER BANK TAP BOX HAS COVER MISSING ON SUPPLY SIDE IN 6TH FLOOR ELECTRICAL CLOSET,DANGEROUS AND HAZARDOUS CONDITION LIVE PARTS EXPOSE | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
SYSTEM III | PROVIDE BATTERY BACK UP EMERGENCY LITES AND EXIT SIGNS FLOORS 1 THRU 9 AND ALL COMMON AREAS OF BUILDING | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | EMERGENCY MAINTENANCE FOR BATTERY BACK UP SYSTEM 3 18-27-700.66.7 | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING /APT.502 - NO RESPONSE. UNVERIFIED DETECTORS AND CONDITIONS. UNVERIFIED COMPLAINT OF MICE, AND MOLD. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL - BROKEN REINFORCED CONCRETE COLUMNS AND BEAMS- SOUTH AND WEST ELEVATION | 5800 N SHERIDAN RD | PERIODIC | FAILED | View |
REPAIR LINTELS | BROKEN REINFORCED CONCRETE LINTELS SOUTH AND WEST ELEVATION | 5800 N SHERIDAN RD | PERIODIC | FAILED | View |
ROACHES | ROACHES INFESTING - APT.501,HALLWAYS,BOILER ROOM | 5800 N SHERIDAN RD | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | SMOKE DETECTOR MISSING IN GARAGE AND BASEMENT FLOOR | 5800 N SHERIDAN RD | PERIODIC | FAILED | View |
CARB MONOX DETECT IN ASSEMBLY | C.O. MISSING IN ENCLOSED BASEMENT GARAGE | 5800 N SHERIDAN RD | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TEST AND TAG DOCUMENT AS REQUIRED BOTH ELEVATOR | 5800 N SHERIDAN RD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ADJUST DOOR RESTRICTORS BOTHE ELEVATORS | 5800 N SHERIDAN RD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVDIE 3 FIRE SERVICE KEYS IN LOBBY FIREARMS BOX | 5800 N SHERIDAN RD | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A MONTHLY FIRE SERVICE TEST LOG ON SITE | 5800 N SHERIDAN RD | PERIODIC | PASSED | View |
LIFE SAFETY EVALUATION PLAN | LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
FILE BLDG REGISTRATION | BUILDING - NOT REGISTERED ALL YEARS , 1990 THROUGH 2014 . | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | INTERIOR OF BUILDING - UNVERIFIED DETECTORS , CONDITIONS AND OCCUPANCY . 2014 ANNUAL INSPECTION REQUIRED . | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
INSTALL EXIT SIGN | 1ST FLOOR BOILER ROOM, LAUNDRY ROOM AND LOWER LEVEL GARAGE - MISSING EXIT SIGNS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE PER CODE SECTION 18-27-700.6 EMERGENCY LIGHTING - EMERGENCY LIGHTING MISSING IN BOILER ROOM, LAUNDRY ROOM, AND ENCLOSED GARAGE SPACES. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | 1ST FLOOR LAUNDRY ROOM - DOOR MISSING FIRE RATING TAG AND CLOSER. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | 1. 10TH FLOOR ELEVATOR MACHINE ROOM AND STAIRWELL - HOLE IN STAIRWELL THROUGH TO ELEVATOR MACHINE ROOM FOR HOIST. PROVIDE PROPER FIRE RATED ENCLOSURE FOR STAIRWELL.2. 9TH FLOOR - SCISSOR STAIR - CRACK IN STAIR AT WALL - STAIRWELL OPEN TO LOWER STAIRWELL. 3. LOWER LEVEL GARAGE - PIPE PENETRATIONS INTO STAIRWELL MISSING FIRE SEAL MATERIALS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE PER CODE SECTION 13-76-075 STAIRWELL IDENTIFICATION - PROPER PERMANENT STAIRWELL IDENTIFICATION MISSING AT EACH FLOOR ON INTERIOR STAIRWELL AND CORRIDOR SIDE OF STAIR. (NOTE: DIRECTIONAL SIGNS USING ¿N¿ FOR NORTH AND ¿S¿ FOR SOUTH IS NOT ALLOWED FOR SCISSOR STAIRS) MAY CAUSE CONFUSION FOR OCCUPANTS AND FIRE FIGHTERS IN EMERGENCY SITUATIONS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE PER CODE SECTION 18-27-700.5 EMERGENCY EGRESS LIGHTING AND EXIT SIGN ON-SITE AUXILIARY SOURCE OF CURRENT SUPPLY. - EXIT SIGNS MISSING BATTERY BACKUP WHERE NO EMERGENCY GENERATOR HAS BEEN INSTALLED. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
SELF-CLOSE DOOR >4 STORY RES. | UNIT DOORS DO NOT CLOSE AND LATCH SHUT: 903, 701, 703, 501, 503, 506, 505, 401, 201 AND 206 UNIT DOORS NO ENTRY, MISSING KEY: 402 AND 203. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | 1. ALL FLOORS - TRASH CHUTE DOORS DO NOT CLOSE AND LATCH SHUT. 2. 1ST FLOOR STORAGE ROOM ACCESSED FROM LAUNDRY ROOM - DOOR MISSING FIRE RATING TAG AND DOOR CLOSER. 3. LOWER LEVEL WEST STORAGE ROOM - STORAGE ROOM DOOR MISSING FIRE RATING TAG. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | ALL FLOORS MULTIPLE RUGS IN HALLWAYS - TRIPING HAZARD. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 2ND AND 9TH FLOORS AND LOWER LEVEL GARAGE FIRE EXTINGUISHERS - MISSING RECHARGE TAGS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
NO CLOSET/STORAGE UNDER STAIR | 1ST FLOOR STAIR B - CLOSET CREATED INSIDE STAIRWELL ENCLOSURE. REMOVE CLOSET AND STORAGE ITEMS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
H.P 2 HR ENCLOSURE | 1ST FLOOR BOILER ROOM - OPENINGS AROUND PIPE PENETRATIONS IN WALLS MISSING FIRE SEAL MATERIALS OR NON-COMBUSTIBLE MATERIALS. *SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
NO COMBUSTIBLES BLOCK EGRESS | 1ST FLOOR REAR CORRIDOR - TENANT WOOD STORAGE LOCKERS IN CORRIDOR PATH OF EGRESS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
I-A I-B I-C AND II FIRE RESIST | 1. 1ST FLOOR LAUNDRY ROOM - WOOD STORAGE LOCKERS. REMOVE COMBUSTIBLE WALL MATERIALS. 2. ARDMORE GARAGE - GARAGE ENCLOSURE CONSTUCTED WITH WOOD STUDS. WOOD NOT ALLOWED. REMOVE AND RETURN GARAGE TO ORIGINAL STATE OR SUBMIT PLANS TO OBTAIN A PERMIT FOR REPAIRS. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE CLASS A FIRE DOOR | LOWER LEVEL - STAIRWELL AND GARAGE VESTIBULE SEPARATION - GARAGE SIDE DOOR ONLY 1 1/2 HOUR RATED DOOR - PROVIDE 3 HOUR DOOR. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
DEMO DEBRIS | LOWER LEVEL GARAGE - TIRES BEING USED AS BUMERS ALONG THE WALLS - REMOVE TIRES AND FIRE HAZARD. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE PER CODE SECTION 13-108-100 GARAGE DOOR FOR 2ND MEANS OF EGRESS FROM GARAGE - GARAGE OVERHEAD DOOR BEING USED AS MEANS OF EGRESS ¿ MISSING FAIL-SAFE PULL STRING AND/OR MANUAL BUTTON AT DOOR TO OPERATE DOOR. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
EXPOSED WIRING | 6TH FLOOR ELECTRICAL ROOM - OPEN PANEL BOX - EXPOSED WIRES. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE | PER SECTION CODE 13-196-206 (D) FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | 2ND FLOOR STAIR B AND 1ST FLOOR STAIR B - STAIR DOORS DO NOT CLOSE AND LATCH SHUT. | 5800 N SHERIDAN RD | COMPLAINT | FAILED | View |