The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPLACE************** | MISSING LB COVER,FEEDING THE BUSINESS SIGN | 249 E 115TH ST | COMPLAINT | FAILED | View |
UNAPPROVED CORDS | UNPROVED CORD FEEDING THE BUSINESS SIGN | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR**************** | ALL ELECTRICAL WORK SHALL BE DONE IN AN NEAT AND WORKMAN LIKE MANNER | 249 E 115TH ST | COMPLAINT | FAILED | View |
PRV HIGH SIDE | FOR ONE TECUMSEH 2 HP. COMPRESSOR WITH 6" X 12" RECEIVER LOCATED IN BASEMENT. | 249 E 115TH ST | PERIODIC | FAILED | View |
PROVIDE | AISLE RESTRICTIONS AT PLATFORM AND OTHER PASSAGE WAYS UNDER 36" DANGEROUS AND HAZARDOUS 14B-10-1018.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PARAPET & COPING | PARAPET WALLS FRONT,EAST, AND WEST WASHED OUT MORTAR JOINTS PERMIT REQUIRED 14X-3-303.6 | 249 E 115TH ST | COMPLAINT | FAILED | View |
ALL ELECTRICAL CONDUIT, BOXES, WIRING,DEVICES AND ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE ,MANNER THROUGH OUT THE BASEMENT AND 1ST FLOOR STORE AREAS 14E-1-110.12 | 249 E 115TH ST | COMPLAINT | FAILED | View | |
SOIL/WASTE,VENT PIPE MATRL | REMOVE ALL PVC FITTINGS AND PIPING THROUGHOUT PREMISES | 249 E 115TH ST | COMPLAINT | FAILED | View |
DEFECTIVE OUTLETS | REPLACE DEFECTIVE RECEPTACLES THROUGH OUT THE STORE AND BASEMENT AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | REMOVE ALL PARTIONS AND FIXTURES (INCLUDING PLUMBING ELECTRIC, HVAC,) INSTALLED WITHOUT A PERMIT BRICKED IN WINDOWS AT REAR STORE 1ST FLOOR AND BASEMENT 14A-4-401.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROPER MATRL WATER SUPPLY PIPE | REMOVE FLEXIBLE WATER SUPPLY LINE AT THREE COMPARTMENT SINK AT REAR OF BUILDING | 249 E 115TH ST | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | RESTORE ALL EM LIGHTS AND EXIT SIGNS THROUGH OUT THE STORE AREAS; NON FUNCTIONING AND MISSING THROUGH OUT DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAYS | PROVIDE GROUND CONTINUITY FOR ARMORED CABLE THROUGH OUT THE BASEMENT AREAS AND HOT WATER HEATER TANKS CONDUIT RUNS APART AT FITTINGS THROUGH OUT THE BASEMENT AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
DETERIORATED CONDUCTORS | REPLACE ALL DETERIORATED CONDUCTORS THROUGH OUT THE BASEMENT, 1ST FLOOR AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR FLOOR | 1ST FLOOR DEFLECTS UNDER LOAD 14X-3-304.4 | 249 E 115TH ST | COMPLAINT | FAILED | View |
OBTN PERMIT FOR PLUMBING WORK | OBTAIN A PLUMBING PERMIT BEFORE ANY WORK | 249 E 115TH ST | COMPLAINT | FAILED | View |
DEFECTIVE SERVICE | SERVICE RISER NOT SUPPORTED ALTERED SERVICE EQUIPMENT DOUBLE LUGGING ON MAIN BREAKER IN PANEL DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
STOP ODORS RPR DFT SEWAGE SYS | OPEN WASTE LINES IN BASEMENT OF STORE DANGEROUS AND HAZARDOUS | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR STAIR | REAR EXTERIOR METAL STAIR SYSTEM GRADE TO 2ND-ALL COMPONENTS SEVERELY RUSTED PARAPET AS GUARDRAILS PLANS AND PERMIT REQUIRED DANGEROUS AND HAZARDOUS 14X-5-505.9.1.3 | 249 E 115TH ST | COMPLAINT | FAILED | View |
SOIL/WASTE,VENT PIPE MATRL | REMOVE 4" PVC USED AS A WASTE STACK AT EAST ELEVATION OF STORE REMOVE ALL PVC WASTE PIPING THROUGHOUT STORE | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL ALL ELEVATIONS BRICKS WASHED OUT MORTAR JOINTS AND SPALLED BROKEN AND MISSING SECTIONS OF SKIN COAT CONCRETE PERMIT REQUIRED FOR ALL MASONRY WORK 14X-3-303.1.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | REAR DOOR 32"UNDERSIZED INCLUDE IN PLANS AND PERMIT DANGEROUS AND HAZARDOUS 14X-3-303.13 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PANEL SCHEDULES | PROVIDE PROPER AND LEGIBLE PANEL DISCONNECT SCHEDULES | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE TRAP | REMOVE UNAPPROVED S-TRAP AT SINK BY KITCHEN AREA | 249 E 115TH ST | COMPLAINT | FAILED | View |
CEILING SUPPORT WIRES AND CEILING GRIDS SHALL NOT BE USED TO SUPPORT LIGHTS AND JUNCTION BOXES CONDUIT RUNS THROUGH OUT 1ST FLOOR STORE AREAS 14E-3-300.11 | 249 E 115TH ST | COMPLAINT | FAILED | View | |
INSTALL COVERS | PROVIDE PROPER TYPE COVERS FOR OPEN PANELS JUNCTION BOXES WITH EXPOSE WIRING THROUGH OUT BASEMENT AREAS AND ABOVE DROP CEILING AREAS STORE AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
CONTINUITY OF RACEWAYS | AT EXTERIOR SIGN DISCONNECT FITTING NOT ATTACHED BARE WIRES EXPOSE DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
1-HR HEATING PLANT ENCLOSURE | FURNACE INSTALLED IN CEILING INADEQUATE ENCLOSURE INCLUDE IN PLANS AND PERMIT DANGEROUS AND HAZARDOUS 14B-5-509 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROVIDE OPEN FRONT TOILET SEAT | PROVIDE OPEN FRONT SEAT AT TOILETS(S) | 249 E 115TH ST | COMPLAINT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY TO 2ND FLOOR UNABLE TO VERIFY OCCUPANCY AND DETECTORS 14A-1-104.7 | 249 E 115TH ST | COMPLAINT | FAILED | View |
VENT SYSTEM TO PRVNT BACK PRES | NO VENT ON DRAIN PIPING IN BASEMENT | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROVIDE | 4" WASTE STACK BACK PITCHED,PROVIDE PROPER PITCH FOR DRAIN PIPING 18-29-704.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
VENT SYSTEM TO PRVNT BACK PRES | NO VENT AT SINK BY KITCHEN AREA | 249 E 115TH ST | COMPLAINT | FAILED | View |
SUBMIT 2 COPY STRUCTURAL RPT | 1ST FLOOR-FLOOR/BASEMENT CEILING ROTTED JOIST REPLACED JOIST IMPROPER INSTALL NOT POCKET IN BRICK WALL PROVIDE STRUCTURAL ENGINEER REPORT DANGEROUS AND HAZARDOUS 14X-1-104.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROVIDE A WATER MAIN GROUND CONDUIT,CONDUCTOR TO WITHIN 5' OF WATER METER OR VALVE; MISSING WATER GROUND DANGEROUS AND HAZARDOUS CONDITION 14E-2-250.68 C1 | 249 E 115TH ST | COMPLAINT | FAILED | View | |
DEFECTIVE DISTRIBUTION | IN BASEMENT AREAS MULTIPLE PANELS DEFECTIVE VANDALIZED OPEN WITH EXPOSE LIVE PARTS INSTALLED WITHOUT PERMITS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
CORRODED CONDUIT & EQUIP | REPLACE ALL RUSTED, CORRODED CONDUIT,JUNCTION BOXES THROUGH OUT THE BASEMENT AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
SUPPLEMENTAL GROUND | PROVIDE SUPPLEMENTAL GROUND FOR METER BANK AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
MAINTAIN PROJECTIONS | CORNICE FRONT WASHED OUT MORTAR JOINT 14X-3-303.1.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
SECURE RACEWAY | PROPERLY SUPPORT ALL CONDUIT RUNS THROUGH OUT THE BASEMENT,1ST FLOOR AREAS AND CEILING AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
ARRANGE FOR REINSPECTION REGAR | PROVIDE ACCESS TO CEILING (DROPPED CEILING) FOR FULL INSPECTION EVIDENCE OF CODE VIOLATIONS DANGEROUS AND HAZARDOUS 14A-1-104.7 | 249 E 115TH ST | COMPLAINT | FAILED | View |
MIXED OCCUPANCY SEPARATION | FIRE SEPARATION COMPROMISED AT 1ST CEILING TO 2ND FLOOR UNIT, MISSING SECTIONS OF DRYWALL DANGEROUS AND HAZARDOUS PLANS AND PERMIT REQUIRED 14B-5-508 | 249 E 115TH ST | COMPLAINT | FAILED | View |
SUPPORT FIXTURES | PROPERLY SUPPORT ALL LIGHT FIXTURE HANGING BY BARE WIRES THROUGH OUT THE BASEMENT AREAS AND THROUGH OUT THE 1ST FLOOR AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO 1ST FLOOR REPAIRS TO BASEMENT STRUCTURE INTERIOR PLATFORM BRICKED IN WINDOW AT REAR AND FURNACE INSTALLATION 14A-4-401.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR DEFECTIVE FITTINGS | FLEXIBLE GAS LINES USES AT FRYER AND FLAT TOP GRILL, PROVIDE APPROVED GAS CONNECTIONS TO ALL GAS APPLIANCES DANGEROUS AND HAZARDOUS | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROVIDE | PROVIDE DIELECTRIC UNIONS AT ALL LOCATIONS WHERE THERE ARE DISSIMILAR METAL PIPING 18-29-605.21.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
OBTAIN ELECTRICAL PERMIT AND CONTRACTOR TO CORRECT VIOLATIONS 14A-4-404.6 | 249 E 115TH ST | COMPLAINT | FAILED | View | |
ABANDONED EQUIPMENT | REMOVE ALL ABANDONED RACEWAY, CONDUITS JUNCTION BOXES, PANELS DISCONNECTS THROUGH OUT THE BASEMENT AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
SERVICE WALK, PASSAGE, AREAWAY | REAR EXTERIOR WALK UNEVEN AND BROKEN CONCRETE CAUSING TRIP HAZARD DANGEROUS 14X-3-303.12 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PRV BALLCOCK,VB,OR AIR GAP | PROVIDE APPROVED BACKFLOW DEVICE FOR MOP SINK IN REAR OF BUILDING | 249 E 115TH ST | COMPLAINT | FAILED | View |
WORKING SPACE | REMOVE ALL DEBRIS FROM ALL PANEL,METER BANK AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
REMV SADDLE HUB CONNECTIONS | REMOVE SADDLE TEE AT 4" WASTE STACK IN BASEMENT | 249 E 115TH ST | COMPLAINT | FAILED | View |
DEFECTIVE FIXTURES | REPLACE ALL DEFECTIVE AND ALTERED LIGHT FIXTURES THROUGH OUT THE BASEMENT AND 1ST FLOOR STORE AREA | 249 E 115TH ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN RESID | MISSING CARBON MONOXIDE DETECTORS 1ST AND BASEMENT DANGEROUS AND HAZARDOUS 14X-5-504 | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR WINDOW SILLS | WINDOW SILLS FRONT WASHED OUT MORTAR JOINTS 14X-3-303.1.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
1HR FLR OVER BSMT, 1 OR 2 DU | FIRE SEPARATION COMPROMISED AT BASEMENT MISSING DRYWALL MUST INCLUDE ON PLANS AND PERMIT DANGEROUS AND HAZARDOUS 14B-6-605.4 | 249 E 115TH ST | COMPLAINT | FAILED | View |
ARMORED CABLE | REPLACE ALL DEFECTIVE AND EXCESSIVE USE OF ARMOURED CABLE THROUGH OUT THE BASEMENT AREAS AND THROUGH OUT THE STORE AREAS,CEILING AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
ADD RECEPTACLES | ADD RECEPTACLES TO EASE EXTENSION CORD USE THROUGH OUT THE STORE DROP CEILING AREAS AND STORE AREAS DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
LISTED FOR USE TEMP & LOCATION | PROVIDE WEATHER PROOF BOXES LIGHTS FITTINGS AND APPROVED RACEWAY FOR FRONT EXTERIOR AREAS AND REAR EXTERIOR AREAS | 249 E 115TH ST | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | BASEMENT DOOR TO BASEMENT NOT FIRE RATED DANGEROUS AND HAZARDOUS 14A-7-716.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
STOP ODORS RPR DFT SEWAGE SYS | OPEN VENT PIPE AT THREE COMPARTMENT SINK AT REAR OF BUILDING DANGEROUS AND HAZARDOUS | 249 E 115TH ST | COMPLAINT | FAILED | View |
PRV DISCHARGE PIPE FROM PRV | NO DISCHARGE PIPING AT WATER HEATER IN BASEMENT DANGEROUS AND HAZARDOUS | 249 E 115TH ST | COMPLAINT | FAILED | View |
REMOVE | REMOVE FERNCO COUPLINGS AT 4"STACK AT EAST ELEVATION OF STORE 18-29-705.12.1 | 249 E 115TH ST | COMPLAINT | FAILED | View |
MULTIPLE CONDUCTOR TERM | REMOVE DOUBLE LUGGING IN METERBANK AND PANEL DANGEROUS AND HAZARDOUS CONDITION | 249 E 115TH ST | COMPLAINT | FAILED | View |
REPAIR STOOP | REAR EXTERIOR CONCRETE STAIRS TO BASEMENT-COLLAPSED DANGEROUS AND HAZARDOUS 14X-5-505.9.1.3 | 249 E 115TH ST | COMPLAINT | FAILED | View |
RATS | INTERIOR EXCESSIVE RODENT DROPPINGS DANGEROUS AND HAZARDOUS 14X-3-308 | 249 E 115TH ST | COMPLAINT | FAILED | View |
LICENSED BONDED PLMBG CONTRCTR | OBTAIN LICENSE PLUMBING CONTRACTOR FOR ALL PLUMBING WORK TO BE DONE | 249 E 115TH ST | COMPLAINT | FAILED | View |
FIRE EXTNGSHR REQ, NONRESDNTL | MISSING FIRE EXTINGUISHERS THROUGHOUT DANGEROUS AND HAZARDOUS 14X-5-504.5 | 249 E 115TH ST | COMPLAINT | FAILED | View |
PROVIDE GUARD RAIL 42 IN HIGH | REAR EXTERIOR STAIRS TO BASEMENT MISSING HAND GUARDRAIL LARGE OPENING AT GRADE LEVEL DANGEROUS AND HAZARDOUS 14X-3-303.12 | 249 E 115TH ST | COMPLAINT | FAILED | View |
CONNECT VENT LINE | FOR ONE TECUMSEH 2 HP. COMPRESSOR LOCATED IN BASEMENT. | 249 E 115TH ST | PERIODIC | FAILED | View |