The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR DOOR HARDWARE | INTERIOR STAIRWAY DOORS - ADJUST CLOSERS. | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
PROVIDE | 1) THE REQUIRED WARNING SIGN POSTED ON THE MACHINE ROOM DOOR.(18-28-1105.5)2) A TEST OF THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE PRESENCE OF A CITY OF CHICAGO REFRIGERATION INSPECTOR. (18-28-1105.6) | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312) 743-3562 MONDAYS BETWEEN 8:00-9:00 AM | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
REPAIR OR REPLACE | THE EMERGENCY FREON LEAK DETECTOR WHICH IS CURRENTLY NOT OPERATING (18-28-1105.5) | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
PROVIDE | 1) THE REQUIRED WARNING SIGN POSTED ON THE MACHINE ROOM DOOR.(18-28-1105.5)2) A TEST OF THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE PRESENCE OF A CITY OF CHICAGO REFRIGERATION INSPECTOR. (18-28-1105.6) | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312) 743-3562 MONDAYS BETWEEN 8:00-9:00 AM | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
2HR SEP FOR STORAGE >100SF | STORAGE ROOM PANEL NOT RATED | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
SELF-CLOSE DOOR >4 STORY RES. | DEFECTIVE CLOSERS AND/OR LATCHES AT:2601,2501,2502,2503,2504,2402,2302,2204,2202,2203,2102.1902,1903,1502,1504,1503,1302,1301,1202,1802,1803,1703,1601,1603,1102,1002,902,803,602,603,504,502,401,404;2401,2301,2103,501- NO LABELS. | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
1HR PUB.CORIDR NON-RES/SPRNKLD | 26TH FLOOR ELECTRIC ROOM AND WASHROOM-NO LABEL;FIRST FLOOR OFFICE AND MEN'S WASHROOM-HOLLOW CORE DOORS;LAUNDRY ROOM-DEFECTIVE CLOSER AND/OR LATCH. | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | 25B TO 26B,1B AND 25A- PANELS NOT RATED | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
INSUFFICIENT MEANS OF EGRESS | ROOF DECK ONE EXIT ONLY | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
2HR SEP FOR STORAGE >100SF | STORAGE ROOM-PANEL NOT RATED | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | FIRST FLOOR SATIRWELL-GLASS DOOR; LOCKER ROOM AND SHOP DOORS NOT 'B' LABEL | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 21A,17A,15A,12A,11A,9A,7A,5A,19A,25A - METAL BOXES IN STAIRWELLS | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
HEATING PLANT/BOILER ROOM DOOR | BOILER ROOM DOOR NO LABEL | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
PROVIDE CLASS A FIRE DOOR | GARAGE LOBBY DOORS NO LABELS | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
MIXED OCCUPANCY SEPARATION | FIRST FLOOR GARAGE AC IN WALL | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
PROVIDE | EMERGENCY LIGHTS NOT WORKING AT 21B,12B,3--SECTION 13-160-690. GARAGE,ELKEVATOR ROOM,2,22B,17CORRIDOR,17A,12B,9A,TRASH ROOM,CHILLER ROOM-FIRESTOP ALL PENETRATIONS SECTION 15-8-570. | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
REMOVE | CHILLER ROOM-USED FOAM FOR FIRE STOPPING SECTION 15-8-570. TRASH ROOM AC IN WALL SECTION 15-8-170. | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |
REPAIR OR REPLACE | SOUTH GARAGE DOOR FROM INTERIOR STAIRWAY - LOCKED - UNLOCK OR PROVIDE FAIL SAFE ELECTRONIC SYSTEM SECTION 13-196-084. | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
REPAIR DOOR, INT. | INTERIOR STAIRWAY DOOR STICKING AND RUB JAMS - RESET | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
PROVIDE | WORKING REFRIGERANT MONITOR IN FIRST FLOOR CHILLER ROOM. UNIT IS CURRENTLY POWERD OFF. TEST MONITOR. | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
PROVIDE | WORKING REFRIGERANT MONITOR IN FIRST FLOOR CHILLER ROOM. UNIT IS CURRENTLY POWERD OFF. TEST MONITOR. | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS & PERMIT FOR FAIL SAFE SYSTEM INSTALLED. | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | PLANS & PERMIT FOR FAIL SAFE SYSTEM INSTALLED. | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
ILLUMINATE PUBLIC STAIR/HALL | EMERGENCY BACKUP LIGHTING - BATTERIES ARE DEAD THRU-OUT. | 247 E CHESTNUT ST | PERIODIC | PASSED | View |
OBTAIN REFRIGERATION PERMIT | FOR TEMPORARY 200 TON TRANE CHILLER LOCATED AT SOUTH GRADE AND FOR CHANGE OUT OF EXISTING CHILLER COMPRESSOR. | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
REPAIR OR REPLACE | THE EMERGENCY FREON LEAK DETECTOR WHICH IS CURRENTLY NOT OPERATING (18-28-1105.5) | 247 E CHESTNUT ST | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | BOILER ROOM-STORAGE | 247 E CHESTNUT ST | COMPLAINT | FAILED | View |