The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FLOOR DESIGNATION AT EACH LANDING ON BOTH JAMBS | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE "NOT A PASSENGER ELEVATOR" SIGN INSIDE OF FREIGHT | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PERMANENT NON COMBUSTIBLE STAIRS FOR MACHINE ROOM | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PERMANENT POWER TO 110V DISCONNECT | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST BRAKE MONITORING SYSTEM | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST ALL FAIDS AND EMERGENCY POWER | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST LOSS OF COMMUNICATION | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST KEY CARD ONCE ACTIVATED WITH FIRE MAN'S SERVICE PHASE II | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ELEVATOR IDENTIFICATION ON ALL MACHINE ROOM, TOP-OF-CAR AND PIT EQUIPMENT, INCLUDING TOE GUARD | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVICE "DANGER COUNTERWEIGHT" SIGNAGE IN PIT | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADEQUATE PIT (MIN OF 10FC) AND CARTOP (MIN OF 19FC) LIGHTING | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SECOND PIT STOP SWITCH 47" ABOVE PIT FLOOR | 900 N KINGSBURY ST | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | WORK INCOMPLETE - MISSING FIRE DAMPERS - FIRE SAFING | 900 N KINGSBURY ST | PERMIT | PASSED | View |
ARRANGE FOR RE-INSPECTION | 900 N KINGSBURY ST | PERMIT | FAILED | View | |
INSTALL SMOKE DETECTORS | SOUTHEAST, SOUTHWEST, NORTHEAST AND NORTHWEST STAIRWAY AT TOP MISSING, SMOKE DETECTORS. | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
CARB MONOX DETECT IN RESID | 11 N.E. BOILER RM ON ROOF MISSING CARBON MONOXIDE DETECTOR. | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
BLANK-TEXT MUST CITE CODE SECT | WORK INCOMPLETE - | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 1 TO 5 TEST ON ALL ELEVATOR AND SUBMIT ALL TEST RESULTS TO ELEVATOR BUREAU | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM CATEGORY 5 TEST-TAG AND DOCUMENT AS REQUIRED -ALL ELEVATORS | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 900 N KINGSBURY ST | PERMIT | FAILED | View | |
ARRANGE COMPLETED PERMIT INSP. | 900 N KINGSBURY ST | PERMIT | FAILED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CONTRASTING PAINT COLOR STRIPPING AROUND COMP CHAINS IN PIT AND TAIL SHEAVE. | 900 N KINGSBURY ST | PERMIT | PASSED | View |
IDENTIFY ELEV POWER LINE DISC | PROVIDE 110V AND MAIN LINE DISCONNECT SOURCE FEED LABELS | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR FIREMAN'S SERVICE L.E. ELEVATOR #8 AND # 10 DO NOT ARRIVE AT MAIN RECALL LANDINGS ON PHASE1 | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL A CERTIFICATE FRAME IN FREIGHT #6 ELEVATOR CAB | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | O | 900 N KINGSBURY ST | PERMIT | PASSED | View |
OPEN | MAKE CORRECTIONS | 900 N KINGSBURY ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR FIREMANS SERVICE L.E. FREIGHT #6 CALL CANCEL CIRCUIT MALFUNCTIONGS | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #6 FREIGHT ELEVATOR: PULL REPAIR PERMIT TO CHANGE UNDERSIZED/ROUGED CABLES | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
INSTALL SMOKE DETECTORS | 12 WEST BOILER ROOM AND EAST BOILER ROOM AT ROOF - SMOKE DETECTORS - MISSING. 13TH FLOOR - MECHANICAL STAIRWAY AT TOP - SMOKE DETECTOR - MISSING. | 900 N KINGSBURY ST | PERIODIC | FAILED | View |
COVER OUTLETS AND JBS | EAST BOILER ROOM AT ROOF - OPEN ELECTRICAL JUNCTION BOXES THROUGHOUT. | 900 N KINGSBURY ST | PERIODIC | FAILED | View |
REPAIR/REBUILD GARAGE OR SHED | INTERIOR OF BUILDING - 600W - GARAGE /CEILING AND WALLS - SECTIONS CRUMBLING WITH EXPOSED REBAR; CORNER CRUMBLING NEAR VEHICLE ENTRANCE. | 900 N KINGSBURY ST | PERIODIC | PASSED | View |
REPAIR DOOR, INT. | INTERIOR OF BUILDING - 600W - 1ST FL - FIRE DOOR H /DOOR - BROKEN CLOSING DEVICE. | 900 N KINGSBURY ST | PERIODIC | PASSED | View |