The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
HEATING PLANT/BOILER ROOM DOOR | BASEMENT LOWER LEVEL BOILER ROOM - SOUTH DOOR MISSING DOOR CLOSER. | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | NORTH INTERIOR STAIR #2, 1ST FLOOR - PIPE PENETRATIONS FROM NEW RESTAURANT PLUMBING MISSING FIRE SEAL MATERIALS AND COMPLETE FIRE SEPARATION. | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
H.P 2 HR ENCLOSURE | BASEMENT LOWER LEVEL BOILER ROOM - MULTIPLE AREAS ON SOUTH AND WEST INTERIOR WALLS - PIPE PENETRATIONS MISSING FIRE SEAL MATERIALS AND PROPER FIRE RATED ENCLOSURE. | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY DIAGRAMS FOR 1, 2, 3 & 4 FLOORS | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY DIAGRAMS FOR 1, 2, 3 & 4 FLOORS | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
OBTAIN PERMIT BEFORE SIGN WORK | ONE BUILDING MOUNTED VINYL 24 X 16' SIGN READS "BUCKMINSTER FULLER STARTING WITH THE UN,LEASE", 13-20-520 AND 13-20-550 | 220 E CHICAGO AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT BEFORE SIGN WORK | ONE BUILDING MOUNTED VINYL 24 X 16 SIGN READS "TAKE YOUR TIME OLAFUR ELIASSON", 13-20-520 AND 13-20-550 | 220 E CHICAGO AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT BEFORE SIGN WORK | ONE BUILDING MOUNTED VINYL 24 X 16' SIGN READS "BUCKMINSTER FULLER STARTING WITH THE UN,LEASE", 13-20-520 AND 13-20-550 | 220 E CHICAGO AVE | COMPLAINT | FAILED | View |
OBTAIN PERMIT BEFORE SIGN WORK | ONE BUILDING MOUNTED VINYL 24 X 16 SIGN READS "TAKE YOUR TIME OLAFUR ELIASSON", 13-20-520 AND 13-20-550 | 220 E CHICAGO AVE | COMPLAINT | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN OCCUPANCY PLACARDS FOR GARDEN AND PATIO AREAS. | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
PROVIDE | 1) THE REQUIRED WARNING SIGN POSTED ON THE MACHINE ROOM DOOR. (18-28-1105.5)2) A TEST OF THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE PRESENCE OF A CITY OF CHICAGO REFRIGERATION INSPECTOR.(18-28-1105.6) | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312)743-3562 MONDAYS BETWEEN 8:00-9:00 AM | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN DUPLICATE OCCUPANCY PLACARDS FOR THEATER 1ST FLR ROOM 1.50 AND 3RD FLR GALLERY 3.00 | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
OWNER OR LICENSED CONTRACTOR | 220 E CHICAGO AVE | PERIODIC | CLOSED | View | |
INTERNAL | #1 JOHNSTON SM #8922. | 220 E CHICAGO AVE | PERIODIC | CLOSED | View |
INTERNAL | #2 JOHNSTON SM #8923. | 220 E CHICAGO AVE | PERIODIC | CLOSED | View |
ARRANGE COMPLETED PERMIT INSP. | 220 E CHICAGO AVE | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL REQUIRED SPRINKLER IN ELEVATOR PIT. (18-30-340 PART 2) | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | LABEL DISCONNECT SWITCHES. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | IDENTIFY ELEVATOR AT ALL LANDINGS (#3). | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL "IN CASE OF FIRE" PICTOGRAPHS AT ALL LANDINGS. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE-PROGRAM ELEVATORS #4 & #5 TO COMPLY WITH THE 2017 FIRE SERVICE UP-GRADE MANDATE AND RE-SCHEDULE ACCEPTANCE TEST | 220 E CHICAGO AVE | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | (FINAL APPL) NUMEROUS ITEMS TO COMPLETE / CORRECT | 220 E CHICAGO AVE | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 220 E CHICAGO AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | INSPECTION REQUIRED 18-28-106.1 | 220 E CHICAGO AVE | COMPLAINT | PASSED | View |
DUST SEPARATOR OUTSIDE OF BLDG | COLLECTORS AND SEPARATORS 18-28-511.1.1 | 220 E CHICAGO AVE | COMPLAINT | PASSED | View |
PROVIDE DUST COLLECTOR | HAZARDOUS EXHAUST SYSTEMS 18-28-510 | 220 E CHICAGO AVE | COMPLAINT | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN OCCUPANCY FOR MARISOL DINING /BAR AREA | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
REPAIR OR REPLACE | THE EMERGENCY FREON LEAK DETECTION SYSTEM IN THE MACHINE ROOM. (18-28-1105.5) | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
ADDITIONAL EXIT | PROVIDE ADDITIONAL EGRESS FOR PATIO/GARDERN (EVENT EXCESS 300 OCCUPANCY -3 EXITS REQUIRED | 220 E CHICAGO AVE | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL 110V CAB DISCONNECT. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PRE TEST AUTO FIRE RECALL AND REINSPECT SYSTEM PRIOR TO FINAL. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECOND PIT SWITCH REQUIRED 47" ABOVE PIT FLOOR. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE SHUNT TRIP FROM MAINLINE CIRCUIT. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSCRIBED CODE DATA TAG REQUIRED ON CONTROLLER. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE HEAT AND SMOKE DETECTORS IN ELEVATOR PIT. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL MACHINE ROOM, PIT, AND CARTOP EQUIPMENT WITH CAR NUMBER, ALSO LABEL INSIDE OF LANDING DOORS WITH FLOOR NUMBERS. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
POST APPROVED OCCUPANCY CARD | POST MISSING OCCUPANCY PLACARDS AT OUTDOOR PATIO AND THE COMMONS. IF DUPLICATE PLACARDS ARE REQUIRED, CONTACT DOBCAPSIGN@CITYOFCHICAGO.ORG | 220 E CHICAGO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CODE COMPLIANT PHASE 1 HALO REQUIRED. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | HANDRAIL REQUIRED ON BACK OF CARTOP. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CONVENIENCE OUTLET IN PIT MUST BE GFI RATED. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | 48" TOE GUARDS REQUIRED FOR BOTH ELEVATORS. | 220 E CHICAGO AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST ALL LOBBY PANEL FEATURES PRIOR TO FINAL. | 220 E CHICAGO AVE | PERMIT | PASSED | View |