Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
POST OWNER/MANAGERS NAME/# | POSTED MGMT. SIGN NOT COMPLETE | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
FIRE EXTNGSHR RECHARGE & TAG | P3 OF PARKING GARAGE FIRE EXT. TAGGED 2005. | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
REPAIR DOOR, INT. | NORTH AT LOBBY LEVEL AT STAIRWELL DOOR RUSTED INT. | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
REPAIR DOOR FRAME, MULLION | NORTH AT LOBBY LEVEL STAIRWELL DOOR FRAME RUSTED INT. | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
STOP LEAKING WATER | NORTH AT LOBBY EVIDENCE OF RUST AND WATER DAMAGE. | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | NORTH AT LOBBY LEVEL AT STAIRWELL INT. STAIRWELL DOOR STUCK OPEN FIRE/SAFETY HAZARD WILL NOT CLOSE. | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
REPAIR DOOR, INT. | LOBBY LEVEL NORTH STAIRWELL DOOR RUSTED AND SHIFTING PROPERLY | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
REPAIR DOOR FRAME, MULLION | LOBBY LEVEL NORTH STAIRWELL DOOR FRAME RUSTED AND NOT SET PROPERLY IN ROUGH OPENING | 360 E RANDOLPH ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE GOVERNOR ROPES ON ELEVATOR #3 - BREAKS WITH CAR AT LOBBY FLOOR | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROPERLY PIPE ALL WIRING IN MACHINE ROOM - ELEVATORS # 1, 2,3,4 LOW VOLTAGE | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADDITIONAL MACHINE ROOM LIGHTING OVER ELEVATOR #1,2,3 MACHINES | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE GFCIS AT ALL MACHINE SPACES - ALL 110V RECEPTICLES MUST BE PROTECTED | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE COVERS ON ALL ELECTRICAL BOXES AND DUCTS IN MACHINE ROOM - ALL ELEVATORS | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MECHANICAL PROTECTION ON ALL LIGHT BULBS | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE COVERS ON TRANSFORMERS AT TOP OF CONTROLLER | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROPERLY PIPE ALL WIRING IN HYDRAULIC MACHINE ROOM | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PATCH MACHINE ROOM PIPE CHASES - HYDRAULIC #5 CAR | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SIGNAGE ON ALL MACHINE ROOM DOORS | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR #3 P2 - EMERGENCY ACCESS DOOR SAFETY SWITCH NEEDS TO BE REPAIRED; PROVIDE SWEEP ON DOOR BOTTOM; LOCATE KEY SPECIFIC TO DOOR, ONLY LOCK IN BUILDING; AND MINIMUM OF 4" SIGNAGE ON LOBBY SIDE OF DOOR MARKED "DANGER ELEVATOR SHAFT" | 360 E RANDOLPH ST | PERMIT | PASSED | View |
PROVIDE | EXISTING COMPARTMENTALIZATION DOORS ON FLOORS 3 -44 ARE NOT EQUIPPED WITH FIRE RATED LABEL INFORMATION. IN ADDITION THE DOORS ARE NOT CAPABLE OF POSITIVE LATCHING SINCE THEY ARE NOT EQUIPPED WITH ANY HARDWARE OTHER THAN A SELF CLOSING DEVICE. PROVIDE TWO HOUR RATED ASSEMBLY DIVIDING FLOOR INTO COMPARTMENTS PER 13-76-020. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
PROVIDE CLASS A FIRE DOOR | PROVIDE VESTIBULE WITH TWO 3 HOUR 'A' LABEL RATED DOORS ON EACH SIDE OF A 4 HOUR SEPARATION. ONLY ONE 3 HOUR DOOR PROVIDED AT EAST, WEST AND A FREIGHT ELEVATOR ENTRANCE IN PARKING LEVELS 1 - 5. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | THE FOLLOWING 'B' RATED DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED.1) 8TH FLOOR TRASH CHUTE2) 20TH FLOOR TRASH CHUTEFIRE RESISTANCE RATING OF THE FOLLOWING DOORS COULD NOT BE VERIFIED DUE TO MISSING DOOR RATING LABEL.1) ROOFTOP ACCESS DOOR AT NORTH AND SOUTH STAIR ENCLOSURE2) PARKING LEVEL 1 SHAFT ROOM (ACCESSED THROUGH STORAGE SPACE), IN ADDITION THE DOOR IS ALSO MISSING SELF CLOSING DEVICE. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQUIRED | SUBMIT PLANS AND OBTAIN PERMIT FOR INTERIOR REMODEL OF UNIT 2308. DURING THE COURSE OF THE LIFE SAFETY EVALUATION INSPECTION, INTERIOR REMODEL WORK WAS OBSERVED IN UNIT. SCOPE OF WORK INCLUDED ARCHITECTURAL, ELECTRICAL & PLUMBING ALTERATIONS. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED IN THE FOLLOWING LOCATIONS.1) 'B' RATED DOOR AT SOUTH EAST AIR HANDLING UNIT ROOM IS EQUIPPED WITH VENTILATION GRILLE NOT HAVING A FUSIBLE LINKFIRE RESISTANCE RATING OF THE FOLLOWING PUBLIC CORRIDOR DOORS COULD NOT BE VERIFIED DUE TO MISSING DOOR RATING LABEL.1) 44TH FLOOR MECHANICAL ROOM & POOL CHEMICAL EQUIPMENT ROOM, IN ADDITION THE DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT HAVING A FUSIBLE LINK. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY AT MULTIPLE LOCATIONS THROUGHOUT NORTH AND SOUTH STAIR ENCLOSURE. 1) EXISTING PENETRATIONS HAVE BEEN COVERED WITH 1/8" THICK METAL PLATE CAULKED AT PERIMETER WITH FIRE SEALANT BUT THE METAL PLATE HAS NO LABELED FIRE RATING VISIBLE. REMOVE PLATES AND INFILL WALL TO MATCH EXISTING RATED CONSTRUCTION. 2) ABANDONED FIRE COMMUNICATION EQUIPMENT ENCLOSURES REMAIN AT MULTIPLE LOCATIONS THROUGHOUT NORTH AND SOUTH STAIR. REMOVE AND INFILL WALL TO MATCH EXISTING RATED CONSTRUCTION. 3) EAST STAIR AT LOBBY LEVEL HAS CONDUIT PENETRATION ABOVE DOOR AND PERIMETER PENETRATION AROUND JUNCTION BOX. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | THE FOLLOWING DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED:1) EAST STAIR DOOR | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) 44TH FLOOR MECHANICAL ROOM, PERIMETER OF DUCT ABOVE DOOR AND SOUTH WALL2)ELECTRICAL METER ROOMS (MULTIPLE LOCATIONS) ON EVEN NUMBERED FLOOR, MINOR BREACHES/FRACTURES AT CEILING CONDUIT PENETRATIONS. IN ADDITION, STEEL PLATES HAVE BEEN ADDED AT BASE LEVEL TO ALLOW FOR ACCESS TO EQUIPMENT. PLATES REQUIRE ADDITIONAL FIRE CAULKING AROUND PERIMETER (MULTIPLE LOCATIONS).3) FREIGHT/TRASH CUTE VESTIBULE ON ALL FLOORS FROM 44 TO PARKING LEVEL 5. EXISTING PENETRATIONS FOR LOW VOLTAGE EQUIPMENT HAVE BEEN INFILLED AT FLOOR LEVEL BUT REQUIRE ANNULAR INFILL AT CEILING LEVEL.4) 10TH FLOOR NORTH STAIR SMOKE TOWER SHAFT. INTERIOR WALL OF RATED CONSTRUCTION CONTAINS 1 S.F. BREACH.5) PARKING LEVEL 1 MECHANICAL ROOM (ACCESS THROUGH STORAGE ROOM)6) PARKING LEVEL 1 ELECTRICAL ROOM, PENETRATIONS INFILEDL WITH FIRE BLOCK FOAM WHICH IS NOT PERMITTED FOR THIS CONSTRUCTION TYPE.7) PARKING LEVEL 1 MECHANICAL ROOM (ADJACENT TO AIR HANDLING UNIT ROOM)8) PARKING LEVEL 1 PUMP ROOM, ABOVE ENTRY DOOR AND SUPPLY DUCTS9) PARKING LEVEL 1 BICYCLE STORAGE ROOM, ABOVE ENTRY DOOR AND AT ADJACENT WALL10) PARKING LEVEL 4 SWITCHGEAR ROOM11) PARKLING LEVEL 4 DATA ROOM, FOAM FIRE BLOCK USED12) PARKING LEVEL 5 ELEVAOR MECHANICAL ROOM, PENETRATIONS AT WALLS & FOAM FIRE BLOCK USED | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
SUBMIT STRUCT. ENG. RPT (INT.) | PROVIDE STRUCTURAL ENGINEER REPORT VERIFYING THAT THE EXISTING TEMPORARY LOLLY COLUMN IS ADEQUATE SUPPORT FOR CATCH BASIN IN PARKING GARAGE LEVEL P3, NO PLANS OR PERMITS ALLOWING TEMPORARY COLUMN FOUND. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
OPEN | 360 E RANDOLPH ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | NO USE. CAR PULLED INTO THE OVER HEAD. CUT DRIVE SHEAVE IF CAPABLE OR REPLACE. | 360 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | (AUDIT) REPLACE GOVERNOR ROPE. #2 CAR | 360 E RANDOLPH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | (AUDIT) LABEL ALL PIT EQUIPMENT. | 360 E RANDOLPH ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | (AUDIT) REMOVE BX CABLE HANGING UNDER CAR. #2 CAR | 360 E RANDOLPH ST | COMPLAINT | PASSED | View |
MAINTAIN MECH. VENT SYSTEM | 360 E RANDOLPH ST | COMPLAINT | CLOSED | View | |
CLASS A FIRE DOOR, NO GLASS | VISION PANEL NOT PERMITTED IN A CLASS 'A' FIRE DOOR. | 360 E RANDOLPH ST | PERIODIC | FAILED | View |
STOP/REMOVE NUISANCE | POOL LOUNGE CHAIRS STORED IN AIR HANDLING ROOM | 360 E RANDOLPH ST | PERIODIC | FAILED | View |