Chicago Building Violations Data: 21 Violations
Violation Inspector Comments Address Category Status View
SEE INSPECTOR COMMENTS GENERATED ANNUAL TEST WITNESSED BY INSPECTOR. (18-27-701-35) 71 S WACKER DR COMPLAINT CLOSED View
IDENTIFICATION LISTING OF EQUIPMENT - (18-27-110-3). BODY & BELT X-RAY MACHINES ARE NOT LABELED BY A RECOGNIZED AGENCY. 71 S WACKER DR COMPLAINT CLOSED View
MAINTAIN OR REPAIR ELECT ELEVA RETEST THE REINSTALLATION OF SMOKE DEVICE ON 9TH FLOOR, ELEVATORS 6-12, TO NOT RECALL 71 S WACKER DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROPERLY LABEL THE REMOVAL OF 9TH FLOOR LANDING FOR ELEVATORS 6 THRU 12 ON ANNUNCIATOR FIRE PANEL 71 S WACKER DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ELIMINATE 9TH FLOOR CONTROL POINT FOR WEST BANK ELEVATORS IN LOBBY 71 S WACKER DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PROPER LABELING ON THE FIRE ANNUNCIATOR PANEL, FOR ALL RISERS 71 S WACKER DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RETEST THE REINTALLATION OF SMOKE DEVICE FOR THE 9TH FLOOR, LOW RISE BANK, DUE TO CONSTRUCTION 71 S WACKER DR PERMIT FAILED View
ARRANGE PERMIT INSP. 71 S WACKER DR PERMIT PASSED View
ARRANGE PERMIT INSP. 71 S WACKER DR PERMIT PASSED View
ARRANGE PERMIT INSP. 71 S WACKER DR PERMIT PASSED View
MAINTAIN EXIT SIGN ILLUMINATED 49TH FLOOR, STAIR #1RED - EXIT SIGN NOT ILLUMINATED AT TIME OF INSPECTION. 71 S WACKER DR PERIODIC PASSED View
SELF-CLOSE CLASS B FIRE DOOR 41ST FLOOR EAST STAIR #2 BLUE - DOOR NOT PROPERLY CLOSING AND LATCHING SHUT. 71 S WACKER DR PERIODIC PASSED View
1HR ENCL FLR TO FLR SHAFT/DUCT 1. 34TH FLOOR, TELEPHONE DATA ROOM, FLOOR PENETRATIONS MISSING FIRE SEAL MATERIALS.2. 2ND AND 22ND FLOOR, ELECTRICAL ROOM - CONDUIT PENETRATIONS IN FLOOR MISSING FIRE SEAL MATERIALS. 71 S WACKER DR PERIODIC PASSED View
CARB MONOX DETECT IN ASSEMBLY 2ND FLOOR, FITNESS CENTER LAUNDRY ROOM - MISSING CARBON MONOXIDE DETECTOR. 71 S WACKER DR PERIODIC PASSED View
ARRANGE COMPLETED PERMIT INSP. 71 S WACKER DR PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 71 S WACKER DR PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 71 S WACKER DR PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA NO WEIGHTS OR PERMIT ON SITE. RE-SCHEDULE. 71 S WACKER DR PERMIT PASSED View
SEE INSPECTOR COMMENTS INSTALL DISCONNECT SWITCH 71 S WACKER DR PERMIT PASSED View
2-HR STAIR ENCLOSURE, 4+ STORY 47TH, 8TH AND 6TH FLOORS, STAIR #1RED - CONDUIT PENETRATIONS IN WALLS MISSING FIRE SEAL MATERIALS. 71 S WACKER DR PERIODIC PASSED View
EXPOSED WIRING 2ND FLOOR, EAST STAIR #4 YELLOW - LOW VOLTAGE CABLES HANGING IN STAIRWELL WITH PANEL COVER MISSING. 71 S WACKER DR PERIODIC PASSED View