Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
CARB MONOX DETECT IN RESID | PROVIDE CO2 DETECTOR IN MECHANICAL ROOM | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR WALLS AROUND ALL PIPER GOING THROUGH WALLS IN BOILER | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | DOOR CLOSER ON MACHINE ROOM ENTRY DOOR | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | VENTILATION FOR MACHINE ROOM | 211 E CHICAGO AVE | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 211 E CHICAGO AVE | COMPLAINT | FAILED | View | |
OUTSIDE AIR 15FT | LOCATE OUTSIDE AIR INTAKE AT LEAST 15 FT FROM EXHAUST FAN DISCHARGE SO AIR UNCONTAMINATED AND OPENING UNOBSTRUCTED OUT OF DOORS | 211 E CHICAGO AVE | COMPLAINT | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY DIAGRAMS FOR 2ND FLOOR AUDITORIUM MEETING ROOM A - F. | 211 E CHICAGO AVE | PERIODIC | PASSED | View |
INSTITUTIONAL EXITDOOR RELEASE | PROVIDE PANIC HARDWARE ON ALL DOORS THAT LEAD INTO SECOND FLOOE EXIT STAIRWELLS AND ALSO AT FIRST FLOOR DOORS EXITING FROM BOTH OF THESE STAIRWELLS. | 211 E CHICAGO AVE | PERIODIC | PASSED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN NEW OCCUPANCY SIGNS FOR MEETING AND DINING ROOMS ON 22ND FLOOR. OBTAIN NEW OCCUPANCY CARDS FOR ROOM 2B-2E | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
INSTITUTIONAL EXITDOOR RELEASE | PROVIDE PANIC HARDWARE ON ALL DOORS THAT LEAD INTO SECOND FLOOE EXIT STAIRWELLS AND ALSO AT FIRST FLOOR. DOORS EXITING FROM BOTH OF THESE STAIRWELLS. 2ND YR NO COMPLIANCE | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN NEW OCCUPANCY SIGNS FOR MEETING AND DINING ROOMS ON 22ND FLOOR. OBTAIN NEW OCCUPANCY CARDS FOR ROOM 2B-2E ,2ND YR NO COMPLIANCE | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAR #3 NO RUNBY. | 211 E CHICAGO AVE | PERMIT | PASSED | View |
PROVIDE | TEST OF REFRIGERATION LEAK DETECTION SYSTEM -MONITOR,SENSOR,ALARMS AND VENTILATION SERVING 3RD FLOOR CHILLER ROOM. TO BE WITNESSED BY REFRIGERATION BUREAU. CALL 312-743-3562 ASK FOR INSPECTOR #653 ,RICH HASTINGS,WEDNESDAYS BETWEEN 8:00 AND 9:00 AM. | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
PROVIDE AUDIBLE AND VISUAL ALARM INSIDE 3RD FLOOR CHILLER ROOM-TO WARN OF REFRIGERATION LEAK. PROVIDE SECONDARY LEAK DETECTOR AT BASE OF NEW CARRIER CHILLER. PROVIDE SIGNAGE AT MAIN ENTRANCE TO CHILLER ROOM -3RD FLOOR- HIGH PRESSURE REFRIGERANT-IF LIGHT AND ALARM ON -DO NOT ENTER. | 211 E CHICAGO AVE | PERIODIC | FAILED | View | |
PROVIDE | TEST OF REFRIGERATION LEAK DETECTION SYSTEM -MONITOR,SENSOR,ALARMS AND VENTILATION SERVING 3RD FLOOR CHILLER ROOM. TO BE WITNESSED BY REFRIGERATION BUREAU. CALL 312-743-3562 ASK FOR INSPECTOR #653 ,RICH HASTINGS,WEDNESDAYS BETWEEN 8:00 AND 9:00 AM. | 211 E CHICAGO AVE | PERIODIC | PASSED | View |
PROVIDE AUDIBLE AND VISUAL ALARM INSIDE 3RD FLOOR CHILLER ROOM-TO WARN OF REFRIGERATION LEAK. PROVIDE SECONDARY LEAK DETECTOR AT BASE OF NEW CARRIER CHILLER. PROVIDE SIGNAGE AT MAIN ENTRANCE TO CHILLER ROOM -3RD FLOOR- HIGH PRESSURE REFRIGERANT-IF LIGHT AND ALARM ON -DO NOT ENTER. | 211 E CHICAGO AVE | PERIODIC | PASSED | View | |
LIFE SAFETY EVALUATION PLAN | LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 | 211 E CHICAGO AVE | COMPLAINT | FAILED | View |
OPEN TYPE VIOLATION | PROVIDE HOISTWAY ACCESS AT ALL FLOORS (SINGLE HOISTWAY) | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | MECHANICALLY PROTECT ELEVATOR CAB LIGHT. 18-30-010,13-20-120. | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | 110V DISCONNECT HEAVY DUTY LOCKABLE AND FUSED (ALL VIOLATIONS IN REGARDS FOR #8 CAR) | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PERMANENTLY MOUNT FIRE EXTINGUISHER IN MACHINE ROOM | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | GFCI IN MACHINE ROOM | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | FIRE PROOF 2HOUR RATING FOR MACHINE ROOM AND HOISTWAY PATCH CAULK | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | GFCI OUTLET IN ELEVATOR PIT | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | 4" FOOT FLOURESCENT LIGHT IN ELEVATOR PIT WITH SWITCH | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | SUMP PUMP RECEPTICLE AND METAL SUMP HOLE COVER | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | REMOVE ALL UNRELATED PLUMBING IN MACHINE ROOM OVER HEAD | 211 E CHICAGO AVE | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PROVIDE GAS SENSOR WITH ALARM FOR NATURAL GAS LIVES IN MACHINE ROOM | 211 E CHICAGO AVE | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 211 E CHICAGO AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 211 E CHICAGO AVE | PERMIT | FAILED | View | |
ARRANGE COMPLETED PERMIT INSP. | 211 E CHICAGO AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 211 E CHICAGO AVE | COMPLAINT | FAILED | View | |
TEST G & S PASS ELE | IN REGARDS TO "ALL". EV000936. | 211 E CHICAGO AVE | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | 1 OF 6 ELEVATORS DOOR PACKAGE | 211 E CHICAGO AVE | PERMIT | PASSED | View |
REMOVE | SOFT SOLDER JOINTS FROM VENT LINE SERVING NEW CHILLER IN 3RD FLOOR CHILLER ROOM. BRAZE ALL JOINTS. | 211 E CHICAGO AVE | PERIODIC | PASSED | View |
REMOVE | SOFT SOLDER JOINTS FROM VENT LINE SERVING NEW CHILLER IN 3RD FLOOR CHILLER ROOM. BRAZE ALL JOINTS. | 211 E CHICAGO AVE | PERIODIC | FAILED | View |