Chicago Building Violations Data: 36 Violations
Violation Inspector Comments Address Category Status View
CARB MONOX DETECT IN RESID PROVIDE CO2 DETECTOR IN MECHANICAL ROOM 211 E CHICAGO AVE PERIODIC FAILED View
REPAIR INTERIOR WALLS/CEILING REPAIR WALLS AROUND ALL PIPER GOING THROUGH WALLS IN BOILER 211 E CHICAGO AVE PERIODIC FAILED View
OPEN TYPE VIOLATION DOOR CLOSER ON MACHINE ROOM ENTRY DOOR 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION VENTILATION FOR MACHINE ROOM 211 E CHICAGO AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 211 E CHICAGO AVE COMPLAINT FAILED View
OUTSIDE AIR 15FT LOCATE OUTSIDE AIR INTAKE AT LEAST 15 FT FROM EXHAUST FAN DISCHARGE SO AIR UNCONTAMINATED AND OPENING UNOBSTRUCTED OUT OF DOORS 211 E CHICAGO AVE COMPLAINT FAILED View
POST APPROVED OCCUPANCY CARD POST OCCUPANCY DIAGRAMS FOR 2ND FLOOR AUDITORIUM MEETING ROOM A - F. 211 E CHICAGO AVE PERIODIC PASSED View
INSTITUTIONAL EXITDOOR RELEASE PROVIDE PANIC HARDWARE ON ALL DOORS THAT LEAD INTO SECOND FLOOE EXIT STAIRWELLS AND ALSO AT FIRST FLOOR DOORS EXITING FROM BOTH OF THESE STAIRWELLS. 211 E CHICAGO AVE PERIODIC PASSED View
POST APPROVED OCCUPANCY CARD OBTAIN NEW OCCUPANCY SIGNS FOR MEETING AND DINING ROOMS ON 22ND FLOOR. OBTAIN NEW OCCUPANCY CARDS FOR ROOM 2B-2E 211 E CHICAGO AVE PERIODIC FAILED View
INSTITUTIONAL EXITDOOR RELEASE PROVIDE PANIC HARDWARE ON ALL DOORS THAT LEAD INTO SECOND FLOOE EXIT STAIRWELLS AND ALSO AT FIRST FLOOR. DOORS EXITING FROM BOTH OF THESE STAIRWELLS. 2ND YR NO COMPLIANCE 211 E CHICAGO AVE PERIODIC FAILED View
POST APPROVED OCCUPANCY CARD OBTAIN NEW OCCUPANCY SIGNS FOR MEETING AND DINING ROOMS ON 22ND FLOOR. OBTAIN NEW OCCUPANCY CARDS FOR ROOM 2B-2E ,2ND YR NO COMPLIANCE 211 E CHICAGO AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CAR #3 NO RUNBY. 211 E CHICAGO AVE PERMIT PASSED View
PROVIDE TEST OF REFRIGERATION LEAK DETECTION SYSTEM -MONITOR,SENSOR,ALARMS AND VENTILATION SERVING 3RD FLOOR CHILLER ROOM. TO BE WITNESSED BY REFRIGERATION BUREAU. CALL 312-743-3562 ASK FOR INSPECTOR #653 ,RICH HASTINGS,WEDNESDAYS BETWEEN 8:00 AND 9:00 AM. 211 E CHICAGO AVE PERIODIC FAILED View
PROVIDE AUDIBLE AND VISUAL ALARM INSIDE 3RD FLOOR CHILLER ROOM-TO WARN OF REFRIGERATION LEAK. PROVIDE SECONDARY LEAK DETECTOR AT BASE OF NEW CARRIER CHILLER. PROVIDE SIGNAGE AT MAIN ENTRANCE TO CHILLER ROOM -3RD FLOOR- HIGH PRESSURE REFRIGERANT-IF LIGHT AND ALARM ON -DO NOT ENTER. 211 E CHICAGO AVE PERIODIC FAILED View
PROVIDE TEST OF REFRIGERATION LEAK DETECTION SYSTEM -MONITOR,SENSOR,ALARMS AND VENTILATION SERVING 3RD FLOOR CHILLER ROOM. TO BE WITNESSED BY REFRIGERATION BUREAU. CALL 312-743-3562 ASK FOR INSPECTOR #653 ,RICH HASTINGS,WEDNESDAYS BETWEEN 8:00 AND 9:00 AM. 211 E CHICAGO AVE PERIODIC PASSED View
PROVIDE AUDIBLE AND VISUAL ALARM INSIDE 3RD FLOOR CHILLER ROOM-TO WARN OF REFRIGERATION LEAK. PROVIDE SECONDARY LEAK DETECTOR AT BASE OF NEW CARRIER CHILLER. PROVIDE SIGNAGE AT MAIN ENTRANCE TO CHILLER ROOM -3RD FLOOR- HIGH PRESSURE REFRIGERANT-IF LIGHT AND ALARM ON -DO NOT ENTER. 211 E CHICAGO AVE PERIODIC PASSED View
LIFE SAFETY EVALUATION PLAN LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 211 E CHICAGO AVE COMPLAINT FAILED View
OPEN TYPE VIOLATION PROVIDE HOISTWAY ACCESS AT ALL FLOORS (SINGLE HOISTWAY) 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION MECHANICALLY PROTECT ELEVATOR CAB LIGHT. 18-30-010,13-20-120. 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION 110V DISCONNECT HEAVY DUTY LOCKABLE AND FUSED (ALL VIOLATIONS IN REGARDS FOR #8 CAR) 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION PERMANENTLY MOUNT FIRE EXTINGUISHER IN MACHINE ROOM 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION GFCI IN MACHINE ROOM 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION FIRE PROOF 2HOUR RATING FOR MACHINE ROOM AND HOISTWAY PATCH CAULK 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION GFCI OUTLET IN ELEVATOR PIT 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION 4" FOOT FLOURESCENT LIGHT IN ELEVATOR PIT WITH SWITCH 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION SUMP PUMP RECEPTICLE AND METAL SUMP HOLE COVER 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION REMOVE ALL UNRELATED PLUMBING IN MACHINE ROOM OVER HEAD 211 E CHICAGO AVE PERMIT FAILED View
OPEN TYPE VIOLATION PROVIDE GAS SENSOR WITH ALARM FOR NATURAL GAS LIVES IN MACHINE ROOM 211 E CHICAGO AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 211 E CHICAGO AVE PERMIT PASSED View
ARRANGE COMPLETED PERMIT INSP. 211 E CHICAGO AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 211 E CHICAGO AVE PERMIT PASSED View
ARRANGE COMPLETED PERMIT INSP. 211 E CHICAGO AVE COMPLAINT FAILED View
TEST G & S PASS ELE IN REGARDS TO "ALL". EV000936. 211 E CHICAGO AVE PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA 1 OF 6 ELEVATORS DOOR PACKAGE 211 E CHICAGO AVE PERMIT PASSED View
REMOVE SOFT SOLDER JOINTS FROM VENT LINE SERVING NEW CHILLER IN 3RD FLOOR CHILLER ROOM. BRAZE ALL JOINTS. 211 E CHICAGO AVE PERIODIC PASSED View
REMOVE SOFT SOLDER JOINTS FROM VENT LINE SERVING NEW CHILLER IN 3RD FLOOR CHILLER ROOM. BRAZE ALL JOINTS. 211 E CHICAGO AVE PERIODIC FAILED View