Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PROV SAFE ACCESS TO CAR GOV | SAFE ACCESS TO GOVERNOR ELEVATOR #1-#2 ACCESS DOOR/LADDER WITH SAFETY SWITCH. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | SCHEDULE INSPECTIONS FOR ELEVATOR #3 & #4 CURRENTLY RUNNING TO NEW FLOORS WITHOUT INSPECTIONS AND PRESSURE TEST. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | MAKE NECESSARY REPAIRS ON ELEVATORS #1 & #2 TO PREVENT DRIFTING ONTO BUFFERS ON CAR TOP INSPECTIONS. 18-30-010,13-20-120. 100014982. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR #4 & #3 NEEDS TO HAVE RETESTOF FAID RECALL | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-SCHEDULE INSPECTION & HAVE FIRE ALARM COMPANY PRESENT TO TEST FAID'S. | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE-SCHEDULE INSPECTIONS OF ELEVATORS #1, #2, #3, #4,& MONROE/MICHINGAN KIOSK.PHASE I & PHASE II | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE HOIST ROPES ON ELEVATOR #1N-RAN | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 REMOVE OLD EQUIPMENT FROM MACHINE ROOM ALSO PIPE | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SIGN ON COUNTERWEIGHT GUARD. | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR #4 & #3 NEEDS TO HAVE RETEST OF FAID RECALL | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #3 ELEVATOR PHASE I LIGHT AT KEY SWITCH NOT ILLUMINATED | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE-SCHEDULE INSPECTIONS OF ELEVATORS #1, #2, #3, & #4.PHASE I & PHASE II | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CABLE GUARDS ON MACHINE FRONT AND BACK. | 201 E RANDOLPH ST | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | SCHEDULE FIRE SERVICE/SMOKES RECALL TEST. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | PROVIDE ANTI SPIN OUTS FOR COUNTER WEIGHT SHACKLES ELEVATOR #1 & #2. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
REP/REPL DEF C/S BUTTONS PASS | STREET LEVEL & TERRACE LEVEL CAB CAR BUTTONS ALWAYS LIT ELEVATOR 1-2. | 201 E RANDOLPH ST | PERMIT | PASSED | View |
STOP/REMOVE NUISANCE | LOWER LEVEL MEN'S AND WOMEN'S BATHROOM AND HALL AIR HANDLING VENTS - CLOGGED WITH DUST. | 201 E RANDOLPH ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | LABEL POWER SOURCE LOCATION | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE THE SMOKES FROM THE TOP OF THE HOISTWAY #3C | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE THE PROTRUDING SCREWS FROM THE TOP OF THE HOISTWAY #3C | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 FIRE TEST | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 REPAIR INCAR STOP SWITCHE'S | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 RELOCATE PIT SWITCH , GFI OUTLET , LIGHT SWITCH , ADD ADDITIONAL LIGHT'S IN PIT | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 INSTALL HOISTWAY FASCIA | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 PHONE MONITORING | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 FLOOR NUMBER WITH BRAILLE | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 CODE DATA TAG ON CONTROLLER | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SYNCHRONIZED JACK | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #4 INSTALL PROPER PIT LADDER | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MOVE PIT LADDER OUT AS MUCH AS POSSIBLE.CAR#2 | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CAR#2- LABEL TOE GUARD AND CAR TOP. | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST FAIDS | 201 E RANDOLPH ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR #3 ALTERNATE FLOOR FIRE SERVICE FLOOR HAS NO EGRESS DANGEROUS & HAZARDOUS | 201 E RANDOLPH ST | PERMIT | FAILED | View |