Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ACCESS TO ROOF | 211 E OHIO ST | PERIODIC | FAILED | View | |
ARRANGE FOR INSPECTION | CALL INSPECTOR #657 OSBORNE @ 312-446-5315. | 211 E OHIO ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | 6TH FLOOR HEALTH CLUBL ROOM AND HALLWAY CEILING MISSING TILES | 211 E OHIO ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 INSTALL DOOR RESTRICTOR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 INSTALL PRESSURE SWITCH AND TEST | 211 E OHIO ST | PERMIT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | WALLS AND CEILINGS - UNIT# 1503 (1) BATHROOM TUB DAMAGED TILE LOOSE, FALLING OFF WALL NEAR WATER SPOUT (2) PROPER VENT COVER MISSING FROM EXHAUST FAN IN BATHROOM | 211 E OHIO ST | PERIODIC | FAILED | View |
REPAIR DOOR FRAME, MULLION | UPS STORE LOOSE DOOR | 211 E OHIO ST | COMPLAINT | PASSED | View |
1HR SEP-D.U. AND REST OF BLDG | 5TH FLOOR INSIDE ACCESS PANEL BEHIND UNIT 521-USED FOAM TO SEAL HOLES | 211 E OHIO ST | COMPLAINT | PASSED | View |
2HR SEP FOR STORAGE >100SF | STORAGE ROOMS IN BASEMENT-VENTS IN WALLS FIRST FLOOR RECEIVING ROOM-OPEN CEILING MISSING FIRE RATED DOORS,GLASS PANEL AND WOOD ON LOBBY SIDE | 211 E OHIO ST | COMPLAINT | PASSED | View |
CLASS B DOOR IN STAIRWELL | STAIRWELL AT BG RUSTED FRAME | 211 E OHIO ST | COMPLAINT | PASSED | View |
ARRANGE PREMISE INSPECTION | ALL APARTMENTS AND STORAGE ROOM IN 29TH FLOOR-NO ENTRY-UNABLE TO CHECK DOORS | 211 E OHIO ST | COMPLAINT | PASSED | View |
NO KEY TO USE EXIT DOOR | UPS STORE-USE OF KEY TO EXIT SOUTH STAIRWELL AT TOP-USE OF KEY TO EXIT AT TOP BY POOL | 211 E OHIO ST | COMPLAINT | FAILED | View |
PROVIDE CLASS A FIRE DOOR | FIRST FLOOR GARAGE SEPARATION-DOORS ON A FUSIBLE LINK DO NOT CLOSE. BASEMENT GARAGE SEPARATION DOORS-MISSING LABELS. FIRST FLOOR SEPARATION BETWEEN COMMERCIAL SPACE AND GARAGE DEFECTIVE LINKS | 211 E OHIO ST | COMPLAINT | FAILED | View |
REPAIR DOOR HARDWARE | DEFECTIVE CLOSERS AND/OR LATCHES AT: 26TH,23RD,21ST,18TH 16TH,9TH,8TH,7TH,6TH,FLOORS 9TH FLOOR TRASH ROOM DOOR FIRST FLOOR RESTAURANTS BACK DOORS TRASH ROOM BY 27W 25W 22ND FLOOR TRASH ROOM 9E TRASH ROOM 5 FLOOR EAST END CORRIDOR DOOR LAUNDRY ROOM DOOR BASEMENT GARBAGE ROOMS,BASEMENT ELECTRICAL ROOM BASEMENT STORAGE ROOMS---SECTION 13-196-170,15-8-150.15-8-160,15-8-170,15-8-240 | 211 E OHIO ST | COMPLAINT | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | GARAGE SOUTH STAIRWELL VERTICAL AND HORIZONTAL GAPS FROM 1 INCH TO ON E AND A HALF INCHES; STAIRWELL AT LOCK TO NS 24E,19E,19W,14E,8E,8W,3RD FLOOR NORTHWEST STAIRS VENT 6TH FLOOR NORTH STAIRWELL-EXPOSED DUCTS GARAGE SOUTH STAIRWELL AT TOP-GLASS ENCLOSURE | 211 E OHIO ST | COMPLAINT | FAILED | View |
REMOVE | COMBUSTIBLE MATERIALS IN 18 W TRASH ROOM 16W TRASH ROOM SECTION 15-8-170 | 211 E OHIO ST | COMPLAINT | FAILED | View |
REPAIR DOOR FRAME, MULLION | UPS STORE LOOSE DOOR IN FRAME | 211 E OHIO ST | COMPLAINT | FAILED | View |
PROVIDE | EMERGENCY LIGHTS MISSING-ENTIRE BUILDING SECTION 18-27-700.6 FIRESTOP ALL PENETRATIONS GAPS AND HOLES IN FIRE RATED ENCLOSURES AND SEPARATIONS ALL STAIRWELLS ELECTRICAL CLOSETS ELECTRICAL ROOM MECHANICAL ROOMS CORRIDORS STORAGE ROOMS TRASH ROOMS LAUNDRY ROOM PUMP ROOM BOILER ROOM SECTION 15-8-570 | 211 E OHIO ST | COMPLAINT | PASSED | View |
REMOVE | ENTIRE BUILDING-ORANGE FOAM USED FOR FIRESTOPPING SECTION 15-8-570 GAS TANKS POWER WASHER AND SNOW BLOWERS STORED IN MAINTENANCE SHOP SECTION 7-28-060, 15-4-090 | 211 E OHIO ST | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | UPS STORE-USE OF KEY TO EXIT SOUTH STAIRWELL AT TOP-USE OF KEY TO EXIT AT TOP BY POOL | 211 E OHIO ST | COMPLAINT | PASSED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | FIRST FLOOR GARAGE SEPARATION-DOORS ON A FUSIBLE LINK DO NOT CLOSE BASEMENT GARAGE SEPARATION DOORS-MISSING LABELS FIRST FLOOR SEPARATION BETWEEN COMMERCIAL SPACE AND GARAGE | 211 E OHIO ST | COMPLAINT | PASSED | View |
REPAIR DOOR HARDWARE | 26TH,23RD,21ST,18TH 16TH,9TH,8TH,7TH,6TH,FLOORS 9TH FLOOR TRASH ROOM DOOR FIRST FLOOR RESTAURANTS BACK DOORS TRASH ROOM BY 27W 25W 22ND FLOOR TRASH ROOM 9E TRASH ROOM 5 FLOOR EAST END CORRIDOR DOOR LAUNDRY ROOM DOOR BASEMENT GARBAGE ROOMS,BASEMENT ELECTRICAL ROOM BASEMENT STORAGE ROOMS | 211 E OHIO ST | COMPLAINT | PASSED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | GARAGE SOUTH STAIRWELL VERTICAL AND HORIZONTAL GAPS FROM 1 INCH TO 1/2 INCH STAIRWELL AT LOCK TO NS 24E,19E,19W,14E,8E,8W,3RD FLOOR NORTHWEST STAIRS VENT 6TH FLOOR NORTH STAIRWELL-EXPOSED DUCTS GARAGE SOUTH STAIRWELL AT TOP-GLASS ENCLOSURE | 211 E OHIO ST | COMPLAINT | PASSED | View |
REMOVE | COMBUSTIBLE MATERIALS IN 18 W TRASH ROOM 16W TRASH ROOM SECTION 15-8-170 STORAGE IN MECHANICAL ROOMS | 211 E OHIO ST | COMPLAINT | PASSED | View |
STOP/REMOVE NUISANCE | STORAGE IN MECHANICAL ROOMS | 211 E OHIO ST | COMPLAINT | FAILED | View |
REMOVE | BASEMENT BY ELEVATOR 4-STORAGE ROOM BUILT OF COMBUSTIBLE MATERIALS FIRST FLOOR BEHIND LOBBY-PARTITIONS BUILT OF COMBUSTIBLE MATERIALS BY ELEVATOR 4 AND 5---SECTION 15-8-260 | 211 E OHIO ST | COMPLAINT | FAILED | View |
WORK NOT ALLOWED | BASEMENT BY ELEVATOR 4-STORAGE ROOM BUILT OF COMBUSTIBLE MATERIALS FIRST FLOOR BEHIND LOBBY-PARTITIONS BUILT OF COMBUSTIBLE MATERIALS BY ELEVATOR 4 AND 5 | 211 E OHIO ST | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 211 E OHIO ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR PHASE 2 ON CARS 1 & 2 | 211 E OHIO ST | PERMIT | FAILED | View |
PROVIDE | FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) | 211 E OHIO ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 REPAIR DAMAGE DOOR JAMBS AS NEEDED | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE FLOOR NUMBERS ON THE HOISTWAY SIDE OF HOISTWAY DOORS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | EVAC SIGNAGE ON ALL LANDINGS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A METAL SUMP HOLE COVER IN THE PIT | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 EMERGENCY POWER TEST | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RETEST ALL SMOKES | 211 E OHIO ST | PERMIT | PASSED | View |
ARRANGE FOR REINSPECTION REGAR | INTERIOR OF BUILDING - NO RESPONSE TO DWELLING UNITS - UNVERIFIED DETECTORS AND CONDITIONS. | 211 E OHIO ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SEAL UP/PATCH OVER DUCT IN OVERHEAD OF THE HOISTWAY REMOVE CONSUITS PROTRUDING INTO HOISTWAYS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE AN EXTENTION TO THE PIT LADDER, IT MUST EXTEND 48 INCHES ABOVE THR FLOOR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A DRIP PAN UNDER PLUMBING ROUTED THROUGH THE MACHINE ROOM | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CONDUIT TO MECHANICALLY PROTECT ALL WIRING IN THE MACHINE ROOM AND HOISTWAYS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CAR NUMBER ON ALL CROSS HEADS, PITS, AND TOE GUARD | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE SIGNAGE ON THE MACHINE ROOM DOOR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE COMMUNICATION FAILURE SYSTEM AND LIGHT | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 SELF CLOSER ON MACHINE ROOM DOOR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 SIGNAGE ON MACHINE ROOM DOOR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 PATCH AROUND HOISTWAY | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 PROVIDE PROPER LOBBY PANEL | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 INSTALL SUMP PUMP COVER IN PIT | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 PROVIDE PROPER CAPACITY PLATE INSIDE CAR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #7 FIRE RECALL TEST AND EMERGENCY POWER | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 PROVIDE HANDRAIL TOP OF CAR | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 REMOVE FORM NAILS TOP OF HOISTWAY ALSO WALLS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 PATCH AROUND HALL BUTTONS IN HOISTWAY | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 PROVIDE LOW CLEARANCE SIGNAGE ON CAR ALSO TOP OF HOISTWAY | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 REPAIR PHONE MONITORING | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | #8 FIRE TEST | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SMOKE TEST AND EMERGENCY POWER TEST | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | EVAC SIGNAGE ON ALL LANDINGS | 211 E OHIO ST | PERMIT | FAILED | View |
MAINTAIN MECH. VENT SYSTEM | PREVENT LEAKING/DRIPPING OF GREASE FROM HOOD EXHAUST EQUIP. | 211 E OHIO ST | COMPLAINT | FAILED | View |
ARRANGE ANNUAL INSP. | ARRANGE INSPECTION TO VERIFY COMPLIANCE | 211 E OHIO ST | COMPLAINT | FAILED | View |
REPAIR OR REPLACE | 1. CLEAN ALL GREASE FROM KITCHEN HOOD EXHAUST FAN/EQUIP SERVING MINGHIN RESTAURANT 2. CLEAN ROOF OF ALL GREASE DROPPINGS 3. REPLACE FAN CANVASS CONNECTION WITH APPROVED U.L. LISTED TYPE CANVASS 4. REMOVE SCREWS FROM GREASE DUCT ACCESS DOORS AND REPLACE WITH BOLTS/NUTS FASTENER AND U.L. APPROVED GASKET 18-28-506.3.9 18-28-506.3.3.4 18-28-506.3.8 | 211 E OHIO ST | COMPLAINT | FAILED | View |
REPLACE DEFECTIVE FAUCET | UNIT# 1503 - FAUCET VERY LOOSE | 211 E OHIO ST | PERIODIC | FAILED | View |
REMOVE | ENTIRE BUILDING-ORANGE FOAM USED FOR FIRESTOPPING SECTION 15-8-570 GAS TANKS POWER WASHER AND SNOW BLOWERS STORED IN MAIN TENANCE SHOP SECTION 7-28-060, 15-4-090 | 211 E OHIO ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | COMPLETE MODERNIZATION OF ELEVATORS #6, #7, & #8 | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | COMPLETE MODERNIZATION OF ELEVATORS #6, #7, & #8 | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR DAMAGED ELEVATOR ENTRANCE DOOR JAMBS AS NEEDED | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | SMOKE TEST AND EMERGENCY POWER TEST FOR HYDRALIC ELEVATORS #6, #7, & #8 | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | FIRE RECALL TEST AND EMERGENCY POWER #6, #7, & #8 | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE LOW CLEARANCE SIGN ON CROSSHEAD AND IN OVERHEAD OF THE HOISTWAYS OF #6, #7,& #8 ELEVATORS | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE ELEVATOR PHONE MONITORING (COMMUNICATION FAILURE ALARM) ELEVATORS #6, #7, & #8 | 211 E OHIO ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | UPON COMPLETION OF ALL (5) ELEVATORS DOOR PACKAGE UPGRADE SCHEDULE FIREMANS RECALL TESTING WITH THE CITY OF CHICAGO, DEPARTMENT OF BUILDINGS, ELEVATOR BUREAU | 211 E OHIO ST | PERMIT | PASSED | View |
ARRANGE ANNUAL INSP. | 211 E OHIO ST | PERIODIC | PASSED | View |