Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
SEND EX. METAL LETTER | SUBMIT FOR ENGINEERS REPORT | 412 S WELLS ST | COMPLAINT | PASSED | View |
TWISTED COUNTERBALANCE | REPAIR REPLACE TWISTED OR BENT FIRE ESCAPE COUNTER BALANCE. | 412 S WELLS ST | COMPLAINT | PASSED | View |
SEND EX. METAL LETTER | SUBMIT ENGINEER REPORT | 412 S WELLS ST | COMPLAINT | PASSED | View |
TUCK POINT RAILINGS | TUCK POINT | 412 S WELLS ST | COMPLAINT | PASSED | View |
PROTECT METAL MEMBERS | SCRAPE AND PAINT | 412 S WELLS ST | COMPLAINT | PASSED | View |
ANCHOR COUNTERWEIGHT | ANCHOR COUNTER WEIGHT BLOCK - REMOVE RUST | 412 S WELLS ST | COMPLAINT | PASSED | View |
STIFFENER PIPE F.E. | REPLACE STIFFENER PIPE - UNDERSIDE OF COUNTER BALANCE | 412 S WELLS ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE SPRINKLER LINES FROM MACHINE ROOM | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BALANCE CARS AND PERFORM ALL SAFETY AND MECHANICAL TESTING WITNESSED BY CITY OF CHICAGO ELEVATOR INSPECTOR | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PRE-TEST AND SCHEDULE SMOKE AND FIRE RECALL TESTING | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-LOCATE PHASE I KEY SWITCH AS PER CHICAGO CODE | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL LOBBY CONTROL PANEL WITH FIRE KEY BOX AND PLAN SHOWING ELEVATOR LOCATIONS AND NUMBERS INCLUDING FREIGHT ELEVATOR. | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH, DRYWALL, AND FIRE CAULK HOISTWAYS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE OLD PIPES AND SPRINKLERS FROM OVERHEAD | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE OLD HOISTWAY WIRING CAR#1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PUT ALL ELEVATOR HOISTWAY WIRING IN TROUGH OR PIPE | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ADD PIT LIGHTING | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELIMINATE PIT WATER, PREVENT FURTHER ACCUMULATION | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPLACE CAR BUFFER SUPPORT CAR #1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL SPINOUTS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CROSSHEAD DATA PLATE CAR #1, ALL ROPE DATA TAGS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR DOOR RESTRICTORS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SELF CLOSING, SELF LOCKING FIRE RATED PIT AND MACHINE ROOM DOORS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CARTOP HANDRAILS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL ALL EQUIPMENT | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL EMERGENCY EXIT CONTACT | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL CATWALK TO SERVICE BUFFER | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PIT LADDERS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR CAR 1 ACCESS KEY SWITCHES TOP AND BOTTOM | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL HANDRAILS IN ELEVATOR CABS AS PER CODE | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE PICTOGRAPHS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL H.D. 110V. DISCONNECTS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ADDITIONAL MACHINE ROOM LIGHTING W/SWITCH AT DOOR ENTRY AND GFI FOR CAR # 1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ADDITIONAL PIT SWITCH CAR #1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SEAL SKYLIGHT LEAKS IN MACHINE ROOM | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | KICK ANGLES CAR #1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MACHINE ROOM FIRE EXTINGUISHER | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL LOBBY CONTROL PANEL | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | KICK ANGLES CAR #1 - AROUND MACHINE | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADDITIONAL FIRE SERVICE KEY IN FIRE KEY BOX. | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FLLOR PLAN ON STATUS PANEL TO SHOW CORRECT BUILDING FLOOR PLAN WITH ELEVATORS SHOWN & IDENTIFIED. | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL HOISTWAY & CAR WIRING NEEDS TO BE MECAHANICALLY PROTECTED. BOTH CARS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PHASE 1 OPERATION DOESN'T WORK. | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PHASE 1 KEY SWITCH OPERATION ISN'T WORKING. | 412 S WELLS ST | COMPLAINT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FINALIZE MODERNIZATION PERMIT #100516436. | 412 S WELLS ST | PERMIT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE INSTALLATION OF PASSENGER ELEVATOR UNDER PERMIT #100516436. | 412 S WELLS ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR RESTRICTOR. CAR 1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REINFORCE CAR TOP RAILING. CAR 2 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADEQUATE RUNNING CLEARANCE FOR GOVERNOR ROPE. CAR 1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL HOISTWAY & CAR WIRING NEEDS TO BE MECHANICALLY PROTECTED. BOTH CARS | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FLOOR PLAN ON STATUS PANEL TO SHOW CORRECT BUILDING FLOOR PLAN WITH ELEVATORS SHOWN & IDENTIFIED. | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | F.A.I.D.'S NOT IN COMPLINACE WITH A.S.M.E. A17.1-1996/CHICAGO 2001 CODE. REPAIR & RESCHEDULE INSPECTION WITH CITY OF CHICAGO ELEVATOR BUREAU. | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE INSTALLATION OF PASSENGER ELEVATOR UNDER PERMIT #100516436 & #100914159 | 412 S WELLS ST | COMPLAINT | FAILED | View |
REMOVE RUST | REMOVE TREADS, RUST AND CORROSION BETWEEN TREADS AND RISERS. | 412 S WELLS ST | COMPLAINT | PASSED | View |
REMOVE RUST | RUST AND CORROSION BETWEEN TREADS AND RISERS | 412 S WELLS ST | COMPLAINT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COUNTER WEIGHT TIE DOWNS CAR#1 | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL PIT BELL | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BEVEL LEDGES IN HOISTWAY | 412 S WELLS ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FINALIZE OPEN MODERNIZATION PERMIT #100516436. | 412 S WELLS ST | COMPLAINT | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE UNI-SRUTS FROM CAR TOP. CAR 1 | 412 S WELLS ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST F.A.I.D.'S | 412 S WELLS ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | F.A.I.D.'S NOT IN COMPLINACE WITH A.S.M.E. A17.1-1996/CHICAGO 2001 CODE. REPAIR BASEMENT AND MACHINE ROOM SMOKES. PRETEST ALL DEVICES AND THEN RESCHEDULE INSPECTION WITH CITY OF CHICAGO ELEVATOR BUREAU. | 412 S WELLS ST | PERMIT | PASSED | View |