Last Modification Date: 2024-08-30 @ 4:11 PM
PIN: 17162330050000
Property Address: 53 W JACKSON BLVD
City - Zip: CHICAGO - 60604
2023 Property Class: EX
2023 Township: 76 - South Chicago
2023 Neighborhood: 76010
2023 Tax District: 76098
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 127 Violations
Violation Inspector Comments Address Category Status View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE CABLE GUARDS ON MACHINE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA DEMARK DECK LEVEL IN MACHINE ROOM 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: FULLY ENCLOSE SECONDARY HOISTWAY ACCESS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: PROVIDE *1 TACTILE IDENTIFICATION ON BOTH JAMBS 53 W JACKSON BLVD PERMIT FAILED View
OPEN TYPE VIOLATION STOP ALL WORK UNTIL PROPER PLANS AND PERMITS HAVE BEEN OBTAINED (SEC. 13-12-050 & 13-12-080) 53 W JACKSON BLVD COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR FOR ALTERATIONS TO 1ST FLOOR RETAIL SPACE AND FOR ALTERATIONS TO 17TH FLOOR SPACES 1734, 1760 53 W JACKSON BLVD COMPLAINT FAILED View
FINES AND PENALTIES 53 W JACKSON BLVD COMPLAINT FAILED View
WORK NOT ALLOWED 53 W JACKSON BLVD COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: PROVIDE CANDY STRIPPING AROUND COUNTERWEIGHT AREA AND COMP CHAINS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: PROVIDE CABLE GUARDS IN SECONDARY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: PROVIDE ALTERNATE STOP SWITCH AND TEST IN THE SECONDARY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #1-#4: REPAIR GRATING & RAILING IN MACHINE ROOM. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE "HEAVY DUTY" 3 PHASE DISCONNECT SWITCH. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE CORRECT CAR ID ON HOISTWAY DOOR FRAMES. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: INSTALL CABLE GUARD ON MACHINE. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE 10FC OF LIGHTING AT EACH LANDING PER CODE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: CANT OVERHEAD LEDGES 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE SAFE ACCESS TO SERVICE MACHINE BREAK 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #1-#4: INSTALL RAILING ON SECONDARY DECK. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE MACHINE ROOM DOOR SIGNAGE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: REMOVE ALL UNUSED PIPES AND WIRING FROM MACHINE ROOM AND HOISTWAY OR SOFFIT. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #1-#4: PERMANENTLY SHUT ACCESS OPENINGS IN OVERHEAD. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE KICK GUARDS & COVER HOLES IN MACHINE ROOM. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA : PROVIDE ADDITIONAL LIGHTING IN LOBBY AT ALL LANDINGS. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE CODE COMPLIANT CAR TOP EMERGENCY EXIT. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: IDENTIFY PIT. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 19FC OF LIGHTING FROM ANY AREA OF CARTOP. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #1-#4: PROVIDE HVAC IN MACHINE ROOM. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE MACHINE ROOM DOOR SIGN. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE SWITCHED PIT DOOR WITH VISION PANEL. PROVIDE "WARNING: GAIN CONTROL" LABEL. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE PIT DOOR SIGN 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE "DANTER COUNTERWEIGHT" SIGNS IN PIT 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE ELEVATOR IDENTIFICATION ON: MACHINE EQUIPMENT; CARTOP; PIT EQUIPMENT; DISCONNECTS; AND TOE GUARD. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE FIRE RATED PIT DOOR WITH GROUP I SECURITY. MUST BE SELF-CLOSING AND SELF-LOCKING 53 W JACKSON BLVD PERMIT FAILED View
SEND EX. METAL LETTER 53 W JACKSON BLVD COMPLAINT PASSED View
PROVIDE 1) ONE AND TWO WAY VOICE COMMUNICATION SYSTEM NOT INSTALLED AT THE TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. ONE AND TWO WAY SYSTEM REQUIRED PER 13-196-204. 2) AUTOMATIC SPRINKLER SYSTEM INSTALLATION NOT COMPLETE AT TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. AUTOMATIC SPRINKLER SYSTEM REQUIRED PER 13-196-205. BUILDING IS ONLY PARTIALLY SPRINKLERED.3) FURNISH / INSTALL ACCESS STAIR TO FIRE ESCAPE WINDOWS THROUGHOUT BUILDING AS REQUIRED WHEN ESCAPE WINDOW SILL IS ABOVE 2'-0" FROM FINISHED FLOOR PER 10(13-160-640)(D)4) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. SHALL BE STORED IN FIREPROOF CABINET PER 15-28-970. PAINT WAS FOUND THROUGHOUT ELECTRICAL CLOSETS AND BASEMENT. 53 W JACKSON BLVD COMPLAINT FAILED View
1HR ENCL FLR TO FLR SHAFT/DUCT PIPE SHAFTS C & D HAVE AREAS OF WALL MISSING ABOVE ENTRY DOOR THROUGHOUT ALL FLOORS.ACCESS DOORS TO ALL SHAFTS ( A, B, C & D) ARE COMBUSTIBLE TYPE. REMEDIATION EFFORTS WERE OBSEREVED DURING INSPECTION AT SHAFT CLOSETS. FIRE RATED DOORS AND PARTITIONS ARE BEING ADDED AT SHAFTS C & D. PER BUILDING PRESIDENT THE SAME APPROACH WILL BE COMPLETED AT SHAFTS A & B. 53 W JACKSON BLVD COMPLAINT FAILED View
SELF-CLOSE CLASS B FIRE DOOR SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK:1) A, B, C & D SHAFT ACCESS DOORS THROUGHOUT BUILDING. C & D SHAFT ACCESS DOORS ARE ADJACENT TO THE LANDINGS OF STAIRS C & D. REMEDIATION EFFORTS WERE OBSEREVED DURING INSPECTION AT SHAFT CLOSETS. FIRE RATED DOORS AND WALLS ARE BEING ADDED AT SHAFTS C & D AND PER BUILDING PRESIDENT THE SAME APPROACH WILL BE COMPLETED AT SHAFTS A & B.2) PASSENGER ELEVATOR MACHINE ROOM AT BOTH NORTH AND SOUTH BUILDINGS, COMBUSTIBLE DOORS WITH NON RATED GLAZING & MISSING SELF CLOSING HARDWARE3) 17TH FLOOR NORTH BUILDING FREIGHT ELEVATOR MACHINE ROOM, COMBUSTIBLE DOOR WITH NON RATED GLAZING & MISSING SELF CLOSING HARDWARE3) 17TH FLOOR NORTH BUILDING PUMP ROOM DOORS, 1 COMBUSTIBLE DOOR WITH NON RATED GLAZING. 2ND DOOR IS MISSING FIRE RATED LABEL & SELF CLOSING HARDWARE4) 17TH FLOOR NORTH BUILDING FREIGHT GENERATOR ROOM, COMBUSTIBLE DOOR WITH VENTILATION GRILLE NOT EQUIPPED WITH FUSIBLE LINK5) THROUGHOUT BASEMENT PAINT STORAGE, ELECTRICAL EQUIPMENT ROOMS, GENERATOR ROOM, ELECTRICAL SWITCHGEAR ROOM, BOILER ROOM & MECHANICAL ROOMS. 53 W JACKSON BLVD COMPLAINT FAILED View
REPAIR EXTERIOR DOOR EXTERIOR DOORS AT 18TH FLOOR OF NORTH BUILDING DO NOT LATCH DUE TO MISSING SELF CLOSING HARDWARE. IN ADDITION, THE DOORS FIRE RATING LABEL IS MISSING. 53 W JACKSON BLVD COMPLAINT FAILED View
PROTECT BLDG WALL OPENINGS APPROVED FIRE RATED WINDOWS REQUIRED IN ALL OPENINGS WITHIN 15 FEET OF A FIRE ESCAPE, MULTIPLE LOCATIONS THROUGHOUT BUILDING AT BOTH FIRE ESCAPE WINDOWS AND ADJACENT WINDOWS. 53 W JACKSON BLVD COMPLAINT FAILED View
MAINTAIN WINDOW SASH MAINTAIN ALL FIRE ESCAPE WINDOWS IN GOOD CONDITION SO THAT EXCESSIVE FORCE IS NOT REQUIRED TO OPEN WINDOW. WINDOWS AT MULTIPLE LOCATIONS WERE NOT OPERABLE. 53 W JACKSON BLVD COMPLAINT FAILED View
EXPOSED WIRING PROPERLY SECURE EXPOSED WIRING AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING 53 W JACKSON BLVD COMPLAINT FAILED View
CLOSE BOX OPENINGS FURNISH / INSTALL COVERS ON OPEN ELECTRICAL EQUIPMENT AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING 53 W JACKSON BLVD COMPLAINT FAILED View
1HR PUB.CORIDR NON-RES/SPRNKLD PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS AND METER ROOMS THROUGHOUT ENTIRE BUILDING, SELF CLOSING DEVICES ARE REQUIRED. 2) THROUGHOUT BASEMENT RATED PUBLIC CORRIDOR. HORIZONTAL PENETRATIONS EXISTING AT MULTIPLE LOCATIONS, INFILL REQUIRED PER APPROVED UNDERWRITERS LABORATORIES ASSEMBLY. 53 W JACKSON BLVD COMPLAINT FAILED View
PLANS & PERMITS REQUIRED 1) SUBMIT PLANS AND OBTAIN PERMIT FOR REMEDIATION WORK AT MECHANICAL RISER SHAFTS A, B, C & D. DURING THE COURSE OF THE LIFE SAFTEY EVALUATION INSPECTION WORK IN PROGRESS WAS OBSERVED IN SHAFTS C & D. THE SCOPE OF WORK ENTAILS CREATING A FIRE RATED VESTIBULE WITH FIRE RATED DOORS TO ACCESS THE SHAFT. THE EXISTING SHAFT ACCESS DOOR WILL REMAIN IN PLACE. EXISTING SHAFT ACCESS DOOR IN C & D STAIR ARE ADJACENT TO STAIR LANDINGS. SHAFT A ACCESS DOOR IS THE PUBLIC CORRIDOR. SHAFT B ACCESS DOOR IS WITHIN THE B ELECTRICAL CLOSET. 2) SUBMIT PLANS AND OBTAIN PERMIT FOR TEMPORARY SHORING AND SCAFFOLDING OBSERVED IN SOUTHWEST AND WEST FOUNDATION WALLS IN THE BASEMENT UNDER THE VAULTED CEILING. PROVIDE STRUCTURAL ENGINEERS REPORT TO DETERMINE THE STABILITY OF THE VAULTED CEILING. 53 W JACKSON BLVD COMPLAINT FAILED View
WORKING ON STOP WORK ORDER 53 W JACKSON BLVD COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REOMVE GREENFIELD FROM PIT. CAR 3 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: LABEL POWER PANEL AT SECONDARY LEVEL WITH EACH ELEVATOR IDENTIFICATION FOR EACH DISCONNECT 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PATCH HOISTWAY WHERE REQ'D. CAR 3 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM 125% BRAKE TEST. CAR 3 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RE-LOCATE PIT STOP SWITCH. CAR 3 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM ALL EMPTY & FULL LOAD TESTS. CAR 3 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERMANENTLY SHUT ACCESS OPENINGS IN OVERHEAD. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REINFORCE ROPE GRIPPER SUPPORTS. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM ALL EMPTY & FULL LOAD TESTS. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM 125% BRAKE TEST. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA TEST F.A.I.D.'S 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CODE COMPLIANT PIT ACCESS DOOR WITH WARNING SIGN. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL SWITCH ON PIT ACCESS DOOR. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RE-LOCATE PIT STOP SWITCH. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE GREENFIELD FROM PIT. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PATCH HOISTWAY WHERE REQ'D. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM ALL EMERGENCY BRAKE (ROPE GRIPPER) NO LOAD & FULL LOAD TESTS. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM FULL LOAD OVERSPEED SAFETY TEST. CAR 4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE ADDITIONAL LIGHTING IN LOBBY AT ALL LANDINGS. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL CABLE GUARD ON MACHINE. ALL CARS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE ACCESS TO SERVICE MACHINE BREAK 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA IDENTIFY PIT. ALL CARS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CORRECT CAR ID ON HOISTWAY DOOR FRAMES. ALL CARS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL RAILING ON SECONDARY DECK. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CODE COMPLIANT CAR TOP EMERGENCY EXIT. ALL CARS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE "HEAVY DUTY" 3 PHASE DISCONNECT SWITCH. ALL CARS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE HVAC IN MACHINE ROOM. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR GRATING & RAILING IN MACHINE ROOM. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE KICK GUARDS & COVER HOLES IN MACHINE ROOM. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CODE COMPLIANT PIT ACCESS DOOR. CARS 1-4 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA DEMARK PIT FLOOR BY ENTRY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE FIRE RATED MACHINE ROOM DOOR THAT IS SELF-CLOSING AND SELF-LOCKING WITH GROUP 2 SECURITY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE MACHINE ROOM DOOR SIGNAGE 53 W JACKSON BLVD PERMIT FAILED View
PIPE OPENING W/NONCOMBUST MATL PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ELECTRICAL CLOSETS, ELECTRICAL METER ROOMS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT BUILDING. ELECTRICAL CLOSETS AND METER ROOMS ARE LABELLED AS A, B, C & D. EXTENSIVE PENETRATIONS EXISTS AT ALL WALLS, CEILING AND FLOORS.2) ELEVATOR MACHINE ROOM, NORTH AND SOUTH BUILDINGS3) 17TH FLOOR PUMP ROOM, NORTH BUILDING4) THROUGHOUT BASEMENT MECHANICAL ROOM, ELECTRICAL CLOSET, STEAM SHAFTS, ELECTRICAL EQUIPMENTROOMS, BOILER ROOM, PAINT ROOM, GENERATOR ROOM AND STORAGE ROOMS ALONG PUBLIC CORRIDOR. 53 W JACKSON BLVD COMPLAINT FAILED View
BLOCKED FIRE DOOR 1) REMOVE OBSTRUCTIONS TO ALLOW ACCESS TO FIRE ESCAPE WINDOWS. OFFICE FURNITURE AND STORAGE IMPEDES FIRE ESCAPE ACCESS AT MULTIPLE LOCATIONS THROUGHOUT. 53 W JACKSON BLVD COMPLAINT FAILED View
COVER OUTLETS AND JBS FURNISH / INSTALL JUNCTION BOX COVERS AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING 53 W JACKSON BLVD COMPLAINT FAILED View
REPAIR SKYLIGHT REPLACE CRACKED GLAZING AT SKYLIGHT. 53 W JACKSON BLVD COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: PROVIDE "DANGER COUNTERWEIGHT" SIGNS IN PIT BY TRAILING BUFFER POCKET 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: FINISH CAB FLOORS PRIOR TO RELEASING FOR TEMP USE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #1-#4: PROVIDE CODE COMPLIANT PIT ACCESS DOOR. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5: PROVIDE 19FC OF LIGHTING IN MACHINE ROOM OVER MACHINE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE ELEVATOR IDENTIFICATION ON: MACHINE EQUIPMENT; CARTOP; PIT EQUIPMENT; DISCONNECTS; AND TOE GUARD. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE "DANTER COUNTERWEIGHT" SIGNS IN PIT 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE FIRE RATED PIT DOOR WITH GROUP I SECURITY. MUST BE SELF-CLOSING AND SELF-LOCKING 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE PIT DOOR SIGN 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE SWITCHED PIT DOOR WITH VISION PANEL. PROVIDE "WARNING: GAIN CONTROL" LABEL. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE FIRE RATED MACHINE ROOM DOOR WITH GROUP II SECURITY THAT IS SELF-CLOSING AND SELF-LOCKING. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE MACHINE ROOM DOOR SIGN. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: CANT OVERHEAD LEDGES 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: CUT UNUSED PIPE SHUTES FLUSH AND COVER HOLES IN MACHINE ROOM AND SECONDARY FLOOR 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: CUT UNUSED PIPE SHUTES FLUSH AND COVER HOLES 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE DISCONNECT SOURCE FEED; WARNING; VOLTAGE LABELS ON ALL DISCONNECTS INCLUDING PANEL'S NAME. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 10FC OF LIGHTING FROM ANY AREA OF CARTOP. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE "AVAILABLE FOR FIRE SERVICE" INDICATOR(S) IN LOBBY STATUS PANEL PER CITY OF CHICAGO CODE FOR FINAL. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: CORRECT FLOORS SERVICED PLACARD 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL CARS: CAULK HOISTWAY PENETRATIONS AND HOLES FROM OLD ELECTRICAL 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #5-#8: PROVIDE FIRE RATED MACHINE ROOM DOOR THAT IS SELF-CLOSING AND SELF-LOCKING WITH GROUP 2 SECURITY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ELEVATOR 8: LABEL 1/2" PIPES RUNNING IN HOISTWAY. IDENTIFY PURPOSE AND VOLTAGE EVERY 6'. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #6: ADJUST 15TH FLOOR DOOR LOCK 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA DEMARK PIT FLOOR BY ENTRY FOR BOTH PIT ENTRANCES 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE CANDY STRIPPING AROUND COUNTERWEIGHT AREA AND COMP CHAINS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE CABLE GUARDS IN SECONDARY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: BEVEL EDGES TO ENTRANCE OF ELEVATORS THAT HAS MORE THAN .5" RISE. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE "IN CASE OF FIRE" SIGNS AT ALL LANDINGS. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RESEAL/TAG GOVERNOR AFTER FINAL ADJUSTMENT. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE ADDITIONAL MACHINE ROOM KEYS IN FIRE BOX. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ELEVATOR 6 & 8: REMOVE OLD UNUSED PIPES IN HOISTWAY 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE TOP OF CAR BARRICADES WHERE DISTANCE IS 12" OR GREATER 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE SAFE ACCESS/EGRESS TO SECONDAY WITH BARRICADES AND NON COMBUSTIBLE STAIRS OR LADDER 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE PERMANENT MEANS TO SERVICE MACHINE BRAKE IN MACHINE ROOM 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: PROVIDE ANTI-ROTATION ON CAR AND COUNTERWEIGHT SHACKLES 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: CORRECT CAPACITY ON CAR STATION 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: FULLY ENCLOSE MACHINE ROOM INCLUDING FLOOR. PROVIDE 2HR FIRE RATED MATERIAL AND MACHINE ROOM DOOR WITH SIGNAGE. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE DISCONNECT SOURCE FEED; WARNING; VOLTAGE LABELS ON ALL DISCONNECTS INCLUDING PANEL'S NAME. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 10FC OF LIGHTING FROM ANY AREA OF CARTOP. 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA BOTH MACHINE ROOMS: PROVIDE MACHINE ROOM DOOR SIGNAGE 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: PROVIDE FASCIA AT 1ST FLOOR REAR HEADER AND REAR WALL 4TH FLOOR 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: CAULK HOLES AT 14TH FL 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA TEST LOSS OF COMM. AND FAIDS 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: PROVIDE CORRECT ELEVATOR ID ON JAMB AT EACH LANDING 53 W JACKSON BLVD PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 ELEVATOR: PROVIDE FIRE KEYBOX ADJACENT TO PHASE I LOBBY KEY SWITCH AND LOBBY PANEL WITH CORRECT NUMBER OF KEYS 53 W JACKSON BLVD PERMIT FAILED View