Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE CABLE GUARDS ON MACHINE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DEMARK DECK LEVEL IN MACHINE ROOM | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: FULLY ENCLOSE SECONDARY HOISTWAY ACCESS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: PROVIDE *1 TACTILE IDENTIFICATION ON BOTH JAMBS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | STOP ALL WORK UNTIL PROPER PLANS AND PERMITS HAVE BEEN OBTAINED (SEC. 13-12-050 & 13-12-080) | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | FOR ALTERATIONS TO 1ST FLOOR RETAIL SPACE AND FOR ALTERATIONS TO 17TH FLOOR SPACES 1734, 1760 | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
FINES AND PENALTIES | 53 W JACKSON BLVD | COMPLAINT | FAILED | View | |
WORK NOT ALLOWED | 53 W JACKSON BLVD | COMPLAINT | FAILED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: PROVIDE CANDY STRIPPING AROUND COUNTERWEIGHT AREA AND COMP CHAINS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: PROVIDE CABLE GUARDS IN SECONDARY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: PROVIDE ALTERNATE STOP SWITCH AND TEST IN THE SECONDARY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #1-#4: REPAIR GRATING & RAILING IN MACHINE ROOM. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE "HEAVY DUTY" 3 PHASE DISCONNECT SWITCH. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE CORRECT CAR ID ON HOISTWAY DOOR FRAMES. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: INSTALL CABLE GUARD ON MACHINE. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE 10FC OF LIGHTING AT EACH LANDING PER CODE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: CANT OVERHEAD LEDGES | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE SAFE ACCESS TO SERVICE MACHINE BREAK | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #1-#4: INSTALL RAILING ON SECONDARY DECK. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE MACHINE ROOM DOOR SIGNAGE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: REMOVE ALL UNUSED PIPES AND WIRING FROM MACHINE ROOM AND HOISTWAY OR SOFFIT. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #1-#4: PERMANENTLY SHUT ACCESS OPENINGS IN OVERHEAD. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE KICK GUARDS & COVER HOLES IN MACHINE ROOM. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | : PROVIDE ADDITIONAL LIGHTING IN LOBBY AT ALL LANDINGS. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE CODE COMPLIANT CAR TOP EMERGENCY EXIT. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: IDENTIFY PIT. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 19FC OF LIGHTING FROM ANY AREA OF CARTOP. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #1-#4: PROVIDE HVAC IN MACHINE ROOM. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE MACHINE ROOM DOOR SIGN. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE SWITCHED PIT DOOR WITH VISION PANEL. PROVIDE "WARNING: GAIN CONTROL" LABEL. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE PIT DOOR SIGN | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE "DANTER COUNTERWEIGHT" SIGNS IN PIT | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE ELEVATOR IDENTIFICATION ON: MACHINE EQUIPMENT; CARTOP; PIT EQUIPMENT; DISCONNECTS; AND TOE GUARD. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE FIRE RATED PIT DOOR WITH GROUP I SECURITY. MUST BE SELF-CLOSING AND SELF-LOCKING | 53 W JACKSON BLVD | PERMIT | FAILED | View |
SEND EX. METAL LETTER | 53 W JACKSON BLVD | COMPLAINT | PASSED | View | |
PROVIDE | 1) ONE AND TWO WAY VOICE COMMUNICATION SYSTEM NOT INSTALLED AT THE TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. ONE AND TWO WAY SYSTEM REQUIRED PER 13-196-204. 2) AUTOMATIC SPRINKLER SYSTEM INSTALLATION NOT COMPLETE AT TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. AUTOMATIC SPRINKLER SYSTEM REQUIRED PER 13-196-205. BUILDING IS ONLY PARTIALLY SPRINKLERED.3) FURNISH / INSTALL ACCESS STAIR TO FIRE ESCAPE WINDOWS THROUGHOUT BUILDING AS REQUIRED WHEN ESCAPE WINDOW SILL IS ABOVE 2'-0" FROM FINISHED FLOOR PER 10(13-160-640)(D)4) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. SHALL BE STORED IN FIREPROOF CABINET PER 15-28-970. PAINT WAS FOUND THROUGHOUT ELECTRICAL CLOSETS AND BASEMENT. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
1HR ENCL FLR TO FLR SHAFT/DUCT | PIPE SHAFTS C & D HAVE AREAS OF WALL MISSING ABOVE ENTRY DOOR THROUGHOUT ALL FLOORS.ACCESS DOORS TO ALL SHAFTS ( A, B, C & D) ARE COMBUSTIBLE TYPE. REMEDIATION EFFORTS WERE OBSEREVED DURING INSPECTION AT SHAFT CLOSETS. FIRE RATED DOORS AND PARTITIONS ARE BEING ADDED AT SHAFTS C & D. PER BUILDING PRESIDENT THE SAME APPROACH WILL BE COMPLETED AT SHAFTS A & B. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK:1) A, B, C & D SHAFT ACCESS DOORS THROUGHOUT BUILDING. C & D SHAFT ACCESS DOORS ARE ADJACENT TO THE LANDINGS OF STAIRS C & D. REMEDIATION EFFORTS WERE OBSEREVED DURING INSPECTION AT SHAFT CLOSETS. FIRE RATED DOORS AND WALLS ARE BEING ADDED AT SHAFTS C & D AND PER BUILDING PRESIDENT THE SAME APPROACH WILL BE COMPLETED AT SHAFTS A & B.2) PASSENGER ELEVATOR MACHINE ROOM AT BOTH NORTH AND SOUTH BUILDINGS, COMBUSTIBLE DOORS WITH NON RATED GLAZING & MISSING SELF CLOSING HARDWARE3) 17TH FLOOR NORTH BUILDING FREIGHT ELEVATOR MACHINE ROOM, COMBUSTIBLE DOOR WITH NON RATED GLAZING & MISSING SELF CLOSING HARDWARE3) 17TH FLOOR NORTH BUILDING PUMP ROOM DOORS, 1 COMBUSTIBLE DOOR WITH NON RATED GLAZING. 2ND DOOR IS MISSING FIRE RATED LABEL & SELF CLOSING HARDWARE4) 17TH FLOOR NORTH BUILDING FREIGHT GENERATOR ROOM, COMBUSTIBLE DOOR WITH VENTILATION GRILLE NOT EQUIPPED WITH FUSIBLE LINK5) THROUGHOUT BASEMENT PAINT STORAGE, ELECTRICAL EQUIPMENT ROOMS, GENERATOR ROOM, ELECTRICAL SWITCHGEAR ROOM, BOILER ROOM & MECHANICAL ROOMS. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
REPAIR EXTERIOR DOOR | EXTERIOR DOORS AT 18TH FLOOR OF NORTH BUILDING DO NOT LATCH DUE TO MISSING SELF CLOSING HARDWARE. IN ADDITION, THE DOORS FIRE RATING LABEL IS MISSING. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
PROTECT BLDG WALL OPENINGS | APPROVED FIRE RATED WINDOWS REQUIRED IN ALL OPENINGS WITHIN 15 FEET OF A FIRE ESCAPE, MULTIPLE LOCATIONS THROUGHOUT BUILDING AT BOTH FIRE ESCAPE WINDOWS AND ADJACENT WINDOWS. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
MAINTAIN WINDOW SASH | MAINTAIN ALL FIRE ESCAPE WINDOWS IN GOOD CONDITION SO THAT EXCESSIVE FORCE IS NOT REQUIRED TO OPEN WINDOW. WINDOWS AT MULTIPLE LOCATIONS WERE NOT OPERABLE. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
EXPOSED WIRING | PROPERLY SECURE EXPOSED WIRING AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
CLOSE BOX OPENINGS | FURNISH / INSTALL COVERS ON OPEN ELECTRICAL EQUIPMENT AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
1HR PUB.CORIDR NON-RES/SPRNKLD | PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS AND METER ROOMS THROUGHOUT ENTIRE BUILDING, SELF CLOSING DEVICES ARE REQUIRED. 2) THROUGHOUT BASEMENT RATED PUBLIC CORRIDOR. HORIZONTAL PENETRATIONS EXISTING AT MULTIPLE LOCATIONS, INFILL REQUIRED PER APPROVED UNDERWRITERS LABORATORIES ASSEMBLY. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
PLANS & PERMITS REQUIRED | 1) SUBMIT PLANS AND OBTAIN PERMIT FOR REMEDIATION WORK AT MECHANICAL RISER SHAFTS A, B, C & D. DURING THE COURSE OF THE LIFE SAFTEY EVALUATION INSPECTION WORK IN PROGRESS WAS OBSERVED IN SHAFTS C & D. THE SCOPE OF WORK ENTAILS CREATING A FIRE RATED VESTIBULE WITH FIRE RATED DOORS TO ACCESS THE SHAFT. THE EXISTING SHAFT ACCESS DOOR WILL REMAIN IN PLACE. EXISTING SHAFT ACCESS DOOR IN C & D STAIR ARE ADJACENT TO STAIR LANDINGS. SHAFT A ACCESS DOOR IS THE PUBLIC CORRIDOR. SHAFT B ACCESS DOOR IS WITHIN THE B ELECTRICAL CLOSET. 2) SUBMIT PLANS AND OBTAIN PERMIT FOR TEMPORARY SHORING AND SCAFFOLDING OBSERVED IN SOUTHWEST AND WEST FOUNDATION WALLS IN THE BASEMENT UNDER THE VAULTED CEILING. PROVIDE STRUCTURAL ENGINEERS REPORT TO DETERMINE THE STABILITY OF THE VAULTED CEILING. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
WORKING ON STOP WORK ORDER | 53 W JACKSON BLVD | COMPLAINT | FAILED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | REOMVE GREENFIELD FROM PIT. CAR 3 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: LABEL POWER PANEL AT SECONDARY LEVEL WITH EACH ELEVATOR IDENTIFICATION FOR EACH DISCONNECT | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH HOISTWAY WHERE REQ'D. CAR 3 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM 125% BRAKE TEST. CAR 3 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-LOCATE PIT STOP SWITCH. CAR 3 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM ALL EMPTY & FULL LOAD TESTS. CAR 3 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERMANENTLY SHUT ACCESS OPENINGS IN OVERHEAD. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REINFORCE ROPE GRIPPER SUPPORTS. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM ALL EMPTY & FULL LOAD TESTS. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM 125% BRAKE TEST. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST F.A.I.D.'S | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE COMPLIANT PIT ACCESS DOOR WITH WARNING SIGN. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL SWITCH ON PIT ACCESS DOOR. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-LOCATE PIT STOP SWITCH. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE GREENFIELD FROM PIT. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PATCH HOISTWAY WHERE REQ'D. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM ALL EMERGENCY BRAKE (ROPE GRIPPER) NO LOAD & FULL LOAD TESTS. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM FULL LOAD OVERSPEED SAFETY TEST. CAR 4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADDITIONAL LIGHTING IN LOBBY AT ALL LANDINGS. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL CABLE GUARD ON MACHINE. ALL CARS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SAFE ACCESS TO SERVICE MACHINE BREAK | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | IDENTIFY PIT. ALL CARS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CORRECT CAR ID ON HOISTWAY DOOR FRAMES. ALL CARS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL RAILING ON SECONDARY DECK. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE COMPLIANT CAR TOP EMERGENCY EXIT. ALL CARS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE "HEAVY DUTY" 3 PHASE DISCONNECT SWITCH. ALL CARS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE HVAC IN MACHINE ROOM. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR GRATING & RAILING IN MACHINE ROOM. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE KICK GUARDS & COVER HOLES IN MACHINE ROOM. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CODE COMPLIANT PIT ACCESS DOOR. CARS 1-4 | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DEMARK PIT FLOOR BY ENTRY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FIRE RATED MACHINE ROOM DOOR THAT IS SELF-CLOSING AND SELF-LOCKING WITH GROUP 2 SECURITY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MACHINE ROOM DOOR SIGNAGE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ELECTRICAL CLOSETS, ELECTRICAL METER ROOMS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT BUILDING. ELECTRICAL CLOSETS AND METER ROOMS ARE LABELLED AS A, B, C & D. EXTENSIVE PENETRATIONS EXISTS AT ALL WALLS, CEILING AND FLOORS.2) ELEVATOR MACHINE ROOM, NORTH AND SOUTH BUILDINGS3) 17TH FLOOR PUMP ROOM, NORTH BUILDING4) THROUGHOUT BASEMENT MECHANICAL ROOM, ELECTRICAL CLOSET, STEAM SHAFTS, ELECTRICAL EQUIPMENTROOMS, BOILER ROOM, PAINT ROOM, GENERATOR ROOM AND STORAGE ROOMS ALONG PUBLIC CORRIDOR. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
BLOCKED FIRE DOOR | 1) REMOVE OBSTRUCTIONS TO ALLOW ACCESS TO FIRE ESCAPE WINDOWS. OFFICE FURNITURE AND STORAGE IMPEDES FIRE ESCAPE ACCESS AT MULTIPLE LOCATIONS THROUGHOUT. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
COVER OUTLETS AND JBS | FURNISH / INSTALL JUNCTION BOX COVERS AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS, METER CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT ENTIRE BUILDING | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
REPAIR SKYLIGHT | REPLACE CRACKED GLAZING AT SKYLIGHT. | 53 W JACKSON BLVD | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: PROVIDE "DANGER COUNTERWEIGHT" SIGNS IN PIT BY TRAILING BUFFER POCKET | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: FINISH CAB FLOORS PRIOR TO RELEASING FOR TEMP USE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #1-#4: PROVIDE CODE COMPLIANT PIT ACCESS DOOR. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5: PROVIDE 19FC OF LIGHTING IN MACHINE ROOM OVER MACHINE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE ELEVATOR IDENTIFICATION ON: MACHINE EQUIPMENT; CARTOP; PIT EQUIPMENT; DISCONNECTS; AND TOE GUARD. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE "DANTER COUNTERWEIGHT" SIGNS IN PIT | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE FIRE RATED PIT DOOR WITH GROUP I SECURITY. MUST BE SELF-CLOSING AND SELF-LOCKING | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE PIT DOOR SIGN | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE SWITCHED PIT DOOR WITH VISION PANEL. PROVIDE "WARNING: GAIN CONTROL" LABEL. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE FIRE RATED MACHINE ROOM DOOR WITH GROUP II SECURITY THAT IS SELF-CLOSING AND SELF-LOCKING. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE MACHINE ROOM DOOR SIGN. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: CANT OVERHEAD LEDGES | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: CUT UNUSED PIPE SHUTES FLUSH AND COVER HOLES IN MACHINE ROOM AND SECONDARY FLOOR | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: CUT UNUSED PIPE SHUTES FLUSH AND COVER HOLES | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE DISCONNECT SOURCE FEED; WARNING; VOLTAGE LABELS ON ALL DISCONNECTS INCLUDING PANEL'S NAME. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 10FC OF LIGHTING FROM ANY AREA OF CARTOP. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE "AVAILABLE FOR FIRE SERVICE" INDICATOR(S) IN LOBBY STATUS PANEL PER CITY OF CHICAGO CODE FOR FINAL. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: CORRECT FLOORS SERVICED PLACARD | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL CARS: CAULK HOISTWAY PENETRATIONS AND HOLES FROM OLD ELECTRICAL | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #5-#8: PROVIDE FIRE RATED MACHINE ROOM DOOR THAT IS SELF-CLOSING AND SELF-LOCKING WITH GROUP 2 SECURITY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 8: LABEL 1/2" PIPES RUNNING IN HOISTWAY. IDENTIFY PURPOSE AND VOLTAGE EVERY 6'. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #6: ADJUST 15TH FLOOR DOOR LOCK | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DEMARK PIT FLOOR BY ENTRY FOR BOTH PIT ENTRANCES | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE CANDY STRIPPING AROUND COUNTERWEIGHT AREA AND COMP CHAINS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE CABLE GUARDS IN SECONDARY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: BEVEL EDGES TO ENTRANCE OF ELEVATORS THAT HAS MORE THAN .5" RISE. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE "IN CASE OF FIRE" SIGNS AT ALL LANDINGS. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RESEAL/TAG GOVERNOR AFTER FINAL ADJUSTMENT. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE ADDITIONAL MACHINE ROOM KEYS IN FIRE BOX. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 6 & 8: REMOVE OLD UNUSED PIPES IN HOISTWAY | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE TOP OF CAR BARRICADES WHERE DISTANCE IS 12" OR GREATER | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE SAFE ACCESS/EGRESS TO SECONDAY WITH BARRICADES AND NON COMBUSTIBLE STAIRS OR LADDER | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE PERMANENT MEANS TO SERVICE MACHINE BRAKE IN MACHINE ROOM | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: PROVIDE ANTI-ROTATION ON CAR AND COUNTERWEIGHT SHACKLES | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: CORRECT CAPACITY ON CAR STATION | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: FULLY ENCLOSE MACHINE ROOM INCLUDING FLOOR. PROVIDE 2HR FIRE RATED MATERIAL AND MACHINE ROOM DOOR WITH SIGNAGE. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE DISCONNECT SOURCE FEED; WARNING; VOLTAGE LABELS ON ALL DISCONNECTS INCLUDING PANEL'S NAME. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE ADDITIONAL CARTOP LIGHTING TO ACHIEVE 10FC OF LIGHTING FROM ANY AREA OF CARTOP. | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BOTH MACHINE ROOMS: PROVIDE MACHINE ROOM DOOR SIGNAGE | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: PROVIDE FASCIA AT 1ST FLOOR REAR HEADER AND REAR WALL 4TH FLOOR | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: CAULK HOLES AT 14TH FL | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST LOSS OF COMM. AND FAIDS | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: PROVIDE CORRECT ELEVATOR ID ON JAMB AT EACH LANDING | 53 W JACKSON BLVD | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #9 ELEVATOR: PROVIDE FIRE KEYBOX ADJACENT TO PHASE I LOBBY KEY SWITCH AND LOBBY PANEL WITH CORRECT NUMBER OF KEYS | 53 W JACKSON BLVD | PERMIT | FAILED | View |