Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-24 @ 6:41 PM
PIN: 17091240090000
Property Address: 409 W HURON ST
City - Zip: CHICAGO - 60654
2023 Property Class: 591
2023 Township: 74 - North Chicago
2023 Neighborhood: 74030
2023 Tax District: 74015
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 34 Violations
Violation Inspector Comments Address Category Status View
SEND EX. METAL LETTER SUBMIT ENGINEER'S REPORT ON 2 FIRE ESCAPE'S 2 A/C PLATFORMS AND 1 WATER TANK 409 W HURON ST COMPLAINT CLOSED View
F.E. MIDRAIL REPAIR OR REPLACE BROKEN MIDRAILS ON FIRE ESCAPE 409 W HURON ST COMPLAINT CLOSED View
CARB MONOX DETECT IN RESID THE 4TH FLOOR UNLICENSED NIGHT CLUB HAS NO CARBON MONOXIDE DETECTORS. 409 W HURON ST COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR THE 4TH FLOOR SPACE HAS BEEN COMPLETELY REHABBED WITH PARTITION WALLS FORMING ROOMS, PLUMBING/ELECTRICAL - WIRING/PIPING AND ASSOCIATED FIXTURES. THIS PROPERTY, ORIGINALLY A HEAVY TIMBER CONSTRUCTION MANUFACTURING SPACE, WAS REHABBED INTO AN OFFICE COMPLEX IN 1995 (PERMIT# B802330). SINCE THAT TIME, ANOTHER MORE RECENT REHAB HAS OCCURRED ON THE 4TH FLOOR, WITHOUT PLANS OR PERMITS. AS MENTIONED ABOVE, THE REHAB THAT NOW EXISTS IS A FULLY OPERATIONAL NIGHT CLUB. THE ABOVE MENTIONED PARTITIONS INCLUDE 12 PRIVATE BOTTLE SERVICE ROOMS, A FULL SERVICE BAR AND A DANCE FLOOR WITH D.J. EQUIPMENT. THE 4TH FLOOR SPACE HAS NO LICENSES ON FILE. AT THE TIME OF THIS INSPECTION, LIQUOR (BOTH BAR AND BOTTLE SERVICE) AND FOOD WERE BEING SOLD WITHOUT LICENSES. THIS UNLICENSED PARTY VENUE/NIGHT CLUB HAS NO PPA LICENSE FOR SMALL ASSEMBLIES EITHER. BOTH THE DEPARTMENT OF BUILDINGS AND THE DEPARTMENT OF BUSINESS AFFAIRS/CONSUMER SERVICES HAVE POSTED/ISSUED CLOSURE NOTICES. 409 W HURON ST COMPLAINT FAILED View
MAINTAIN EXIT SIGN ILLUMINATED THE 4TH FLOOR UNLICENSED NIGHT CLUB DIRECTIONAL EXIT SIGNS ARE ALL INOPERABLE. (DANGEROUS AND HAZARDOUS) 409 W HURON ST COMPLAINT FAILED View
INSTALL SMOKE DETECTORS THE FRONT INTERIOR STAIRS AND THE 4TH FLOOR UNLICENSED NIGHT CLUB HAS NO SMOKE DETECTORS. (DANGEROUS AND HAZARDOUS) 409 W HURON ST COMPLAINT FAILED View
OBSTRUCTIONS IN EXIT WAY THE 4TH FLOOR UNLICENSED NIGHT CLUB HAS ONLY 1 EXIT. THE REAR EXIT ACCESS TO THE EAST ELEVATION FIRE ESCAPE HAS BEEN BOARDED WITH PLYWOOD. THE PLYWOOD IS COVERING A DOOR TO A ROOM THAT CONTAINS WINDOW ACCESS TO THE FIRE ESCAPE. (DANGEROUS AND HAZARDOUS) 409 W HURON ST COMPLAINT FAILED View
WORK NOT ALLOWED REMOVE EVERYTHING FROM THE 4TH FLOOR SPACE THAT WAS INSTALLED WITHOUT PLANS/PERMITS. REMOVE ALL PARTITION WALLS FORMING ROOMS AND THE BAR. REMOVE ALL ELECTRICAL AND PLUMBING FIXTURES INSTALLED WITHOUT PLANS/PERMITS. RESTORE THE 4TH FLOOR SPACE TO IT'S PREVIOUS CONDITION PRIOR TO THIS UN-PERMITTED REHAB. A PERMIT TO DECONVERT MUST BE OBTAINED. 409 W HURON ST COMPLAINT FAILED View
OPEN TYPE VIOLATION 1. PERFORM PRESSURE RELIEF TEST FRONT PASSENGER. 18-30-010, 13-20-120. EV002796 409 W HURON ST PERIODIC FAILED View
SEND EX. METAL LETTER EXPOSED METAL LETTER 409 W HURON ST COMPLAINT FAILED View
REPAIR EX. MET. ENGINEER REPORT (F.E.) 409 W HURON ST COMPLAINT FAILED View
EX. MET. FOR WATER TANKS ENGINEER REPORT WATER TANK 409 W HURON ST COMPLAINT FAILED View
REPAIR UNSAFE WATER TANK REPAIR WATER TANK BOLTS, CATWALK, RAILS, PAINT 409 W HURON ST COMPLAINT FAILED View
MAINTAIN EXIT SIGN ILLUMINATED 4TH FLOOR EAST REAR EXIT LIGHT OUT 409 W HURON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED SOUTH AT HALLWAY 6TH AND 3RD EMERGENCY LIGHT NOT WORKING 409 W HURON ST PERIODIC FAILED View
POST OWNER/MANAGERS NAME/# NO OWNER ID SIGN POSTED 409 W HURON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED 4TH FLOOR EAST REAR EXIT LIGHT OUT 409 W HURON ST PERIODIC FAILED View
POST OWNER/MANAGERS NAME/# NO OWNER ID SIGN POSTED 409 W HURON ST PERIODIC FAILED View
ARRANGE FOR REINSPECTION REGAR ENTRY TO 5TH FLOOR UNIT, FIRST FLOOR COMMERCIAL SPACE AND GROUND TO 5TH FLOOR INTERIOR STAIRWAY. ARRANGE FOR INTERIOR INSPECTION TO VERIFY OCCUPANCY AND DETECTORS. 409 W HURON ST PERIODIC FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY NORTH ELEVATION, GROUND TO 5TH FLOOR, INTERIOR STAIRWAY, 5TH FLOOR, STAIRWAY DOOR, NOT LATCHING, MISSING SELF-CLOSER. 409 W HURON ST PERIODIC FAILED View
ILLUMINATE EXIT AREAS NORTH ELEVATION, GROUND TO 5TH FLOOR, INTERIOR STAIRWAY, 4TH FLOOR LANDING, EMERGENCY LIGHTS, NOT WORKING. 409 W HURON ST PERIODIC FAILED View
REPAIR INTERIOR STAIR SYSTEM 1) NORTH ELEVATION, GROUND TO 5TH FLOOR, INTERIOR STAIRWAY: A) GROUND TO 1ST FLOOR LANDING, STAIR TREADS, LOOSE, DEFLECTING UNDER LOAD; B) 3RD FLOOR LANDING, GUARDRAIL, LOOSE, DEFLECTING UNDER LOAD; C) 4TH TO 5TH FLOOR, STAIRS, 1ST STAIR TREAD AT 4TH FLOOR, LOOSE, DEFLECTING UNDER LOAD; 2) NORTH ELEVATION, 1ST FLOOR, COMMERCIAL SPACE, PERSONAL TRAINING CENTER, 1ST FLOOR, AT FRONT, SECTION OF GUARDRAIL, MISSING. OBTAIN PERMIT FOR REPAIRS. 409 W HURON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED NORTH ELEVATION, FIRST FLOOR COMMERCIAL SPACE, PERSONAL TRAINING CENTER, FRONT DOOR, EXIT SIGN, MISSING. 409 W HURON ST PERIODIC FAILED View
REPAIR EXTERIOR STAIR DANGEROUS AND HAZARDOUS. SOUTH-EAST ELEVATION, GROUND TO FIRST FLOOR, METAL STAIR SYSTEM, OUT OF PLUMB, SEVERELY LEANING, PULLING AWAY FROM THE BUILDING, LARGE GAP BETWEEN BUILDING AND STAIRS LANDING. OBTAIN PLANS AND PERMIT FOR REPAIRS. 409 W HURON ST PERIODIC FAILED View
REPAIR EXTERIOR WALL 1) DANGEROUS AND HAZARDOUS. SOUTH-EAST CORNER, WATER TOWER, 5TH FLOOR TO TOP OF THE WATER TOWER, BULGING, SHIFTING, SPALLING MASONRY, OVER PUBLIC WAY; 2) DANGEROUS AND HAZARDOUS. NORTH ELEVATION, 5TH FLOOR, ENTIRE WIDTH OF THE BUILDING, ALL WINDOWS, LIMESTONE ABOVE WINDOWS, BULGING, SHIFTING, PULLING AWAY FROM STRUCTURE, OVER PUBLIC WAY. OBTAIN PLANS AND PERMIT FOR REPAIRS. 409 W HURON ST PERIODIC FAILED View
PARAPET 1) EAST AND SOUTH ELEVATIONS, ENTIRE SPAN OF ELEVATIONS, PARAPET WALL, BULGING, SHIFTING, SPALLING MASONRY, OVER PUBLIC WAY. OBTAIN PERMIT FOR REPAIRS. 409 W HURON ST PERIODIC FAILED View
REPAIR LINTELS 1) NORTH ELEVATION, 2ND TO 5TH FLOOR, ALL WINDOWS, METAL LINTELS, RUSTED, BENT, SAGGING IN THE MIDDLE, LARGE GAPS ABOVE THEM, FILLED WITH MORTAR, BULGING, SHIFTING MASONRY ABOVE LINTELS; 2) EAST ELEVATION, 1ST TO 5TH FLOOR, ALL WINDOWS AND ALL DOORS TO FIRE ESCAPE STAIRS, METAL LINTELS, RUSTED, BENT, GAPS ABOVE THEM, FILLED WITH MORTAR. OBTAIN PLANS AND PERMIT FOR REPAIRS. 409 W HURON ST PERIODIC FAILED View
OBSTRUCTIONS IN EXIT WAY EAST ELEVATION, 1ST FLOOR COMMERCIAL SPACE, PERSONAL TRAINING CENTER: 1) BACK EXIT DOOR, ACCUMULATION OF BUILDING MATERIALS, LARGE SECTIONS OF HVAC DUCTS, PLASTIC BUCKETS, ETC., OBSTRUCTING PATH OF EGRESS; 2) BACK EXIT DOOR, METAL SHUTTERS, OBSTRUCTING PATH OF EGRESS. 409 W HURON ST PERIODIC FAILED View
PROVIDE SIDEWALK SHED F/PROTCT IMMEDIATELY PROVIDE SIDEWALK SHED FOR PROTECTION OF PROPERTY AND PASSERSBY FROM UNSAFE CONDITIONS, AS FOLLOWS: NORTH ELEVATION, 5TH FLOOR, ENTIRE WIDTH OF THE BUILDING, ALL WINDOWS, LIMESTONE ABOVE WINDOWS, BULGING, SHIFTING, PULLING AWAY FROM STRUCTURE, OVER PUBLIC WAY. 409 W HURON ST PERIODIC FAILED View
SUBMIT 2 COPY STRUCTURAL RPT SOUTH-EAST CORNER, WATER TOWER, ALL ELEVATIONS, 5TH FLOOR TO TOP OF THE WATER TOWER, BULGING, SHIFTING, SPALLING MASONRY, OVER PUBLIC WAY. 409 W HURON ST PERIODIC FAILED View
ARRANGE PREMISE INSPECTION INTERIOR OF BUILDING - UNVERIFIED DETECTORS, OCCUPANCY AND CONDITIONS. 409 W HURON ST PERIODIC FAILED View
PROVIDE PROVIDE PER SECTION 13-96-820, 13-96-830, 13-96-840, 13-96-850, 13-96-870, 100% HANDS-ON CRITICAL EXAM OF FIRE ESCAPE. SUBMIT TO: DEPARTMENT OF BUILDINGS, ATTN: CODE-COMPLIANCE GROUP, 2045 W. WASHINGTON 60612. 409 W HURON ST PERIODIC FAILED View
TEST G & S FRT ELE BACK FREIGHT 5YEAR TEST. 409 W HURON ST PERIODIC FAILED View
PARAPET SOUTH PARAPET WALL SPALLING 409 W HURON ST PERIODIC FAILED View