Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OWNER OR LICENSED CONTRACTOR | 624 S MICHIGAN AVE | PERIODIC | CLOSED | View | |
INTERNAL | #1 #2 FREEMAN BOILERS. | 624 S MICHIGAN AVE | PERIODIC | CLOSED | View |
SEND EX. METAL LETTER | SUBMIT FOR ENGINEERS REPORT. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
TWISTED COUNTERBALANCE | REPAIR OR REPLACE TWISTED OR BENT FIRE ESCAPE HAND RAILING. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR - EAST ELEVATION AT 13TH AND 14TH FLOORS TERRA COTTA SURROUND, CRACKING, SPALLING WASHED OUT MORTAR AND AT ORNATE COLUMNS (2) EAST ELEVATION TERRA COTTA HEADS CRACKING, SPALLING, WASHED OUT MORTAR (3) SOUTH EAST AND NORTH EAST CORNER AT 12TH FLOOR TERRA COTTA SEVERE SHIFTING, WIDE JOINTS,TERRA COTTA CRACKING, WASHED OUT MORTAR (4) SOUTHEAST AND NORTHEAST CORNERS TERRA COTTA CRACKING MINOR FROM 3RD FLOOR TO 12TH FLOOR (5) PLANS AND PERMITS FOR REPAIRS | 624 S MICHIGAN AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | OBSTRUCTION LOCKED STAIRWELL DOORS FROM 5TH TO 6TH ALL DOORS UNLOCK OR PROVIDE FAIL SAFE UNLOCKING SYSTEM | 624 S MICHIGAN AVE | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | EXTERIOR WALL REPAIR - EAST ELEVATION AT 13TH AND 14TH FLOORS TERRA COTTA SURROUND, CRACKING, SPALLING WASHED OUT MORTAR AND AT ORNATE COLUMNS (2) EAST ELEVATION TERRA COTTA HEADS CRACKING, SPALLING, WASHED OUT MORTAR (3) SOUTH EAST AND NORTH EAST CORNER AT 12TH FLOOR TERRA COTTA SEVERE SHIFTING, WIDE JOINTS,TERRA COTTA CRACKING, WASHED OUT MORTAR (4) SOUTHEAST AND NORTHEAST CORNERS TERRA COTTA CRACKING MINOR FROM 3RD FLOOR TO 12TH FLOOR (5) PLANS AND PERMITS FOR REPAIRS | 624 S MICHIGAN AVE | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | OBSTRUCTION LOCKED STAIRWELL DOORS FROM 5TH TO 6TH ALL DOORS UNLOCK OR PROVIDE FAIL SAFE UNLOCKING SYSTEM | 624 S MICHIGAN AVE | PERIODIC | FAILED | View |
SUBMIT 2 COPIES CRITICAL EXAM | FILE REPORTS AS REQUIRED BY EXTERIOR WALL ORDINANCE. LAST CRITICAL WAS FILED IN 2001, SHORT FORMS WERE FILED IN 2002 AND 2004. DID NOT FILE CRITICAL EXAM DUE BY DECEMBER 1, 2005 AS OF MARCH 10, 2006. MUST FILE CRITICAL EXAM TO BRING BUILDING UP TO DATE. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
COVER OUTLETS AND JBS | BASEMENT - OPEN JUNCTION BOXES WITH EXPOSED WIRES. | 624 S MICHIGAN AVE | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | THE FOLLOWING DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED:1) 11TH FLOOR WEST STAIR2) 10TH FLOOR WEST & EAST STAIR3) LIBRARY STAIR AT BASEMENT.FIRE RESISTANCE RATING OF THE FOLLOWING DOOR COULD NOT BE VERIFIED DUE TO EXISTING DOOR LABEL HAVING BEEN PAINTED OVER. CLEAN/RESTORE LABEL AS REQUIRED TO ALLOW FOR VISIBLE CONFIRMATION OF FIRE RATING:1) ROOFTOP ACCESS DOOR AT WEST STAIR | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
SELF-CLOSE CLASS B FIRE DOOR | SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK:1) ALL ELECTRICAL ROOMS/CLOSETS ON ALL FLOORS. 2) LIBRARY ELEVATOR PENTHOUSE ACCESS DOOR, NOT LATCHING PROPERLY.3) BASEMENT GAS RISER ROOM, DOOR PROPPED OPEN4) BASEMENT SUMP PUMP ROOM, DOOR NOT LATCHING | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN ASSEMBLY | FURNISH/INSTALL CARBON MONOXIDE DETECTOR ADJACENT TO FUEL FIRED BACK UP GENERATOR. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
REPAIR/REPLACE SMOKE DETECTORS | INSTALL SMOKE DETECTORS IN THE FOLLOWING AREAS. SMOKE DETECTORS SHALL BE INSTALLED IN CONJUNCTION WITH EXISTING FIRE ALARM SYSTEM.1) CEILING OF EAST AND WEST STAIR AT 14TH FLOOR. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
RESTORE EXIT AND EM | FIRE ESCAPE INDICATOR SIGNAGE NOT ILLUMINATED AT 5TH FLOOR ROOFTOP ABOVE EXIT DOOR LEADING TO WEST FIRE ESCAPE. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
NO KEY TO USE EXIT DOOR | LABELED EXIT DOOR FROM BOOKSTORE INTO LIBRARY REQUIRES KEY TO OPERATE, REVISE HARDWARE AS REQUIRED. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
PROVIDE | 1) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. IN BASEMENT SHALL BE STORED IN FIREPROOF CABINET PER 15-28-9702) FURNISH / INSTALL ACCESS STAIR TO FIRE ESCAPE WINDOWS THROUGHOUT BUILDING AS REQUIRED WHEN ESCAPE WINDOW IS ABOVE 2'-0" FROM FINISHED FLOOR PER 13-160-640 (D) | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
UNINTERRUPTED EXIT AT GRADE | 1) TRAVEL PATH FROM 2ND FLOOR TO 1ST FLOOR AT WEST STAIR IS IMPAIRED BY KEY LOCKED METAL HINGED GATE. AT TIME OF INSPECTION THE DOOR WAS UNLOCKED BUT WAS TOLD BY BUILDING ENGINEER THAT DOOR IS MAINTAINED IN LOCKED POSITION DURING EVENING HOURS. REMOVE METAL GATE ENTIRELY, COORDINATE WITH ARCHITECT TO PROVIDE PROPER ENCLOSURE IF SECURITY IS A CONCERN.2) EMERGENCY EXIT TRAVEL PATH FROM LIBRARY ROOFTOP LEADS TO STAIR ENCLOSURE WHICH LEADS TO WEST FIRE ESCAPE. STAIR ENCLOSURE CONTAINS COMBUSTIBLE WOOD DOOR AT INTERMEDIATE LANDING. DOOR DOES NOT ACT AS ENCLOSURE AND MUST BE REMOVED. IN ADDITION DOOR THRESHOLD RISES 2-1/2" ABOVE LANDING CREATING A TRIPPING HAZARD. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
I-A I-B I-C AND II FIRE RESIST | INSTALL MISSING LAYER OF GYPSUM BOARD FINISH TO COMPLETE 1 HOUR FIRE RATED CONSTRUCTION IN RISER ROOM IN EAST SECTION OF FLOOR PLAN. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
INSTALL COVERS | FURNISH / INSTALL JUNCTION BOX COVERS WHERE MISSING AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSETS THROUGHOUT BUILDING2) MECHANICAL ROOMS THROUGHOUT BUILDING 3) FREIGHT ELEVATOR VESTIBULES THROUGHOUT BUILDING. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
BLOCKED FIRE DOOR | REMOVE OBSTRUCTIONS PROHIBITING ACCESS TO FIRE ESCAPE ACCESS AT THE FOLLOWING LOCATIONS:1) 13TH FLOOR EAST FIRE ESCAPE WINDOW, USED AS STORAGE AREA BY THE OFFICE TENANT.2) 13TH FLOOR WEST FIRE ESCAPE DOOR, PODIUM AND CHAIR IN FRONT OF DOOR.3) WEST FIRE ESCAPE DOES NOT OPERATE PROPERLY AT GRADE LEVEL DUE TO ENCUMBRANCE CAUSED BY DUMPSTER. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
1HR PUB.CORIDR NON-RES/SPRNKLD | THE FIRE RATING OF THE PUBLIC CORRIDOR IS COMPROMISED AT THE FOLLOWING LOCATIONS:1) ELECTRICAL CLOSET, FREIGHT ELEVATOR LOBBY AND MECHANICAL ROOMS. THESE ROOMS CONTAIN PIPE PENETRATIONS INTO THE PUBLIC CORRIDOR WALL. THE PENETRATIONS WERE NOT VISIBLE FROM THE CORRIDOR SIDE DUE TO CEILING TILES IN THE CORRIDOR BUT WERE OBSERVED IN THE AFOREMENTIONED ROOMS.2) 11TH FLOOR COMMUNITY ROOM. COMPARTMENTATION DOUBLE DOORS ARE MAINTAINED OPEN WITH HOLD OPEN DEVICES, 1 DOOR HAS EXISTING CLOSER DISABLED, THE OTHER IS MISSING CLOSER ALLTOGETHER. 3) MECHANICAL ROOMS DOORS THROUGHOUT THE BUILDING. THE MAJORITY OF DOORS HAVE THEIR SELF CLOSING DEVICES DISABLE OR MISSING ALLTOGETHER.4) 1ST FLOOR COMPARTMENTATION DOORS AT THE NORTHWEST SECTION OF THE FLOOR PLAN. EXISTING SET OF DOORS ARE NOT LATCHING PROPERLY. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
MAINTAIN WINDOW SASH | MAINTAIN FIRE ESCAPE WINDOW IN GOOD WORKING ORDER SO THAT EXCESSIVE FORCE IS NOT REQUIRED TO OPEN WINDOW. EXISTING WINDOW HAS BEEN PAINTED SHUT. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | REPAIR AS REQUIRED AT THE FOLLOWING LOCATIONS:1) FREIGHT ELEVATOR LOBBY CEILING AND CORRIDOR WALL, SECTIONS OF WALL/CEILING MISSING THROUGHOUT BUILDING.2) MECHANICAL ROOMS THROUGHOUT BUILDING. SECTIONS OF WALL MISSING, TYPICALLY AT PLUMBING WALL ADJACENT TO RESTROOMS AND AT CORRIDOR WALL. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ALL ELECTRICAL CLOSETS AND MECHANICAL ROOMS ON ALL FLOORS. THE PENTRATIONS ARE MOST SUBSTANTIAL IN THE ELECTRICAL CLOSETS. 1ST FLOOR MECHANICAL ROOM HOUSES PENETRATIONS ON ALL WALLS AND AT CEILING.2) PUMP PENTHOUSE AT 14TH FLOOR MEZZANINE3) PASSENGER ELEVATOR PENTHOUSE, MINOR PENETRATION AT FLOOR4) FREIGHT ELEVATOR VESTIBULE5) THROUGHOUT BASEMENT CORRIDOR, MECHANICAL AND ELECTRICAL ROOMS | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | FURNISH / INSTALL 'B' LABEL ACCESS PANEL AT MUTIPLE FLOORS IN EAST STAIR ENCLOSURE. EXISTING CHASE ACCESS PANEL AND FRAME ARE OF COMBUSTIBLE MATERIALSINTERIOR STAIRWAYS SHALL BE ENCLOSED WITH WALLS AND PARTITIONS PROVIDING FIRE RESISTANCE OF TWO HOURS AT THE FOLLOWING LOCATIONS:1) LIBRARY STAIR FROM 2ND FLOOR TO 1ST FLOOR, EXISTING STAIR OPEN DIRECTLY TO CHECK OUT STATION.2) EAST & WEST STAIR FROM 2ND FLOOR TO 1ST FLOOR. STAIRS ENCLOSURES RUN THE ENTIRE HEIGHT OF THE BUILDING. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |
STAIRWELL ENCLOSURE - BASEMENT | INTERIOR STAIRWAY SHALL BE ENCLOSED WITH WALLS AND PARTITIONS PROVIDING FIRE RESISTANCE OF TWO HOURS AT THE FOLLOWING LOCATIONS:1) BASEMENT EAST STAIR TO LOBBY. | 624 S MICHIGAN AVE | COMPLAINT | FAILED | View |