Chicago Building Violations Data: 141 Violations
Violation Inspector Comments Address Category Status View
PRV HIGH SIDE FOR ONE UNITED COOLAIR 4 TON A/C UNIT LOCATED IN 14TH FLOOR ELEVATOR MACHINE ROOM. RECEIVER 6" X 20". 333 N MICHIGAN AVE PERMIT PASSED View
CONNECT VENT LINE UNITED COOL AIR UNIT SERVING 14TH FLOOR ELEVATOR MACHINE ROOM. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #6 CANT ALL LEDGE'S AS NEEDED 333 N MICHIGAN AVE PERMIT FAILED View
ARRANGE PERMIT INSP. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL STENSIL ALL EQUIPMENT 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL PIT FENCING #5 CAR 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL BUFFER CATWALK 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ADD PIT LIGHTING 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA SELF LOCKING / CLOSING PIT DOOR 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ESCUTCHEONS IN HOISTWAY DOORS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA FIRE ANGLES ON HOISTWAY DOORS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPLACE HOIST & COMP ROPES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CROSS HEAD & ROPE DATA TAGS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA GROUND WIRE DISCONNECTS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CODE DATA PLATES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM DROP TEST 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL ALL EQUIPMENT 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA BEVEL LEDGES IN HOISTWAY 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA FIRE ANGLES GIBS ON DOORS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REPLACE COMP ROPE AND HOIST ROPES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CROSSHEAD DATA AND ROPE DATA TAGS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA GROUND DISCONNECTS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL 48" TOE GUARD 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL CODE DATA PLATE 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA DOOR OPERATOR NOT WORKING 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA FENCE OFF ELEVATOR PIT #5 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA CATWALK TO SERVICE BUFFERS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA ROPE GUARDS IN SECONDARY 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ESCUTCHEON ON HOISTWAY DOORS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPLACE HOIST AND COMP ROPES 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA GROUND WIRE DISCONNECTS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CITY FIRE RECALL TEST AFTER MOD COM PHETION 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA SEE PUNCH LIST 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA INSTALL FIRE RATED MACHINE ROOM DOOR OR REQUEST ADMINISTRATIVE RELIEF (VARIENCE) 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA REMOVE TEMP WIRING FROM MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA INSCLUDE ELEVATOR IN LOBBY PANEL AND TIE IN FAID'S 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA COMPLETE LANDING LOBBIES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA COMPLETE MACHINE ROOM WALL ENCLOSURES. VIOLATIONS #35-#54 IN REGARDS TO ELEVATOR # 3 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PATCH ALL HOLES IN MACHINE ROOM WALLS, FLOORS, HOISTWAY , AND SECONDARY DECKS. 2HR FIRE FATING 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE AUXILARY DISCONNECT FOR ELEVATOR # 3, MAINTAIN LINE OF SIGHT FROM MACHINE 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA INSALL ALL ELECTRICAL COVERS, DUCT COVERS IN MACHINE ROOM AND HOISTWAYS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ALL DEBRIES, EXCESS WIRES, PIPING, AND STUBS IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE 4' FLOURESCENT LIGHT FIXTURES IN MACHINE ROOM, SECONDARY DECKS, AND PITS WITH GFCI OUTLETS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE LADDER FOR SAFE ACCESS TO SECONDARY DECK AND DELF CLOSSING/LOCKING DOOR 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE METAL CODE DATA PLATES ON ALL CONTROLLERS WITH PROPER CODE REFERENCES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROPERLY PIPE(CONDUIT) ALL DISCONNECTS MAXIMUM 36" OF GREENFIELD (FLEX) ALLOWED FOR ELEVATOR INSTALLATIONS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL GUARDS AND MACHINE NUMBERS ON ALL ELVATOR MACHINES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PROPER VENTILATION WITH FIRE DAMPERS IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE DRIP PANS WITH DRAINS UNDER ALL OVERHEAD PLUMBING IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE GROUNDS FOR 110V DISCONNECTS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR ISSUE WITH HOIST CABLES RUBBING AGAINST MACHINE BEAM IN OVER HEAD 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ALL RADIATORS OUT OF HOISTWAYS AND CANTOR LEDGES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE COVERS FOR ALL HALL LANTERNS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL FLOORING AND HAND RAILS IN CABS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA COMPLETE THE INSTALLATION OF ELEVATOR CONTROL PANEL (LOBBY PANEL) 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CHECK FIRE SERVICE PHASE I & II AND FAIDS ON FINAL 333 N MICHIGAN AVE PERMIT FAILED View
PROVIDE 1) ONE AND TWO WAY VOICE COMMUNICATION SYSTEM INSTALLATION NOT COMPLETE AT THE TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. ONE AND TWO WAY SYSTEM REQUIRED PER 13-196-204.2) AUTOMATIC SPRINKLER SYSTEM INSTALLATION NOT COMPLETE AT TIME OF LIFE SAFETY INSPECTION PER RECOMMENDED UPGRADES OUTLINED IN LIFE SAFETY REPORT. AUTOMATIC SPRINKLER SYSTEM REQUIRED PER 13-196-2053) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. SHALL BE STORED IN FIREPROOF CABINET PER 15-28-970. PAINT WAS FOUND THROUGHOUT BUILDING.4) FURNISH/INSTALL STAIRWELL IDENTIFICATION AT EACH FLOOR IN CORRIDOR SIDE OF STAIRWELL PER 13-76-075 333 N MICHIGAN AVE COMPLAINT PASSED View
PIPE OPENING W/NONCOMBUST MATL PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ELECTRICAL CLOSETS AND ELECTRICAL EQUIPMENT ROOMS THROUGHOUT BUILDING - PENETRATIONS EXISTS AT ALL WALLS, CEILING AND FLOORS.2) MECHANICAL CLOSETS AND EQUIPMENT ROOMS THROUGHOUT BUILDING3) DATA CLOSETS THROUGHOUT BUILDING 333 N MICHIGAN AVE COMPLAINT PASSED View
1HR PUB.CORIDR NON-RES/SPRNKLD PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED AT THE FOLLOWING LOCATIONS:1) MAJOR HORIZONTAL BREACHES INTO PUBLIC CORRIDOR WALL AT ALL FLOORS. PENETRATIONS WERE NOT VISIBLE FROM THE CORRIDOR SIDE DUE TO CEILING TILES IN CORRIDOR BUT WERE OBSERVED IN ELECTRICAL CLOSET, DATA CLOSETS SLOP SINK ROOMS AND MECHANICAL CLOSETS DIRECTLY ADJACENT TO THE PUBLIC CORRIDOR. PENETRATIONS OF FIRE RATED WALL WERE VISIBLE IN CORRIDORS ON FLOORS WHERE WORK IS IN PROGRESS.2) THROUGHOUT SUB GRADE LEVELS SB, BB, MB & BR. MAJOR HORIZONTAL PENETRATIONS EXISTING AT ALL FLOORS AT EVERY ROOM ADJACENT TO THE PUBLIC CORRIDOR. 3) SELF CLOSING DEVICES ARE REQUIRED AT ALL ROOMS DIRECTLY ADJACENT TO FIRE RATED PUBLIC CORRIDOR THROUGHOUT ENTIRE BUILDING. 333 N MICHIGAN AVE COMPLAINT PASSED View
SELF-CLOSE CLASS B FIRE DOOR SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK:1) ELECTRICAL CLOSETS, MECHANICAL CLOSETS AND RESTROOMS IN STAIR ENCLOSURES THROUGHOUT ENTIRE BUILDING2) ELECTRICAL EQUIPMENT ROOMS THROUGHOUT BUILDING3) MECHANICAL CLOSETS AND MECHANICAL EQUIPMENT ROOMS THROUGHOUT BUILDING4) SB SUMP PUMP ROOM5) BOILER ROOM 333 N MICHIGAN AVE COMPLAINT PASSED View
2-HR STAIR ENCLOSURE, 4+ STORY EXISTING ACCESS PANELS IN THROUGHOUT NORTH AND SOUTH STAIRS HAVE NO VISIBLE FIRE RATING LABEL. REMOVE PANEL AND PROVIDE FIRE RATED PANEL ASSEMBLY. 333 N MICHIGAN AVE COMPLAINT PASSED View
I-A I-B I-C AND II FIRE RESIST 1)COMBUSTIBLE FRAMING FOUND THROUGHOUT SUB GRADE LEVELS MB, BB, SB & BR IS NOT ALLOWED FOR THIS CONSTRUCTION TYPE. EXCESSIVE AMOUNTS OF COMBUSTIBLE FRAMING, SHELVING AND DOORS FOUND THROUGHOUT STORAGE AREAS. 2) COMBUSTIBLE EXTERIOR STAIRS AT LOWER WACKER AT NOT ALLOWED FOR THIS CONSTRUCTION TYPE. 333 N MICHIGAN AVE COMPLAINT PASSED View
CLASS B DOOR IN STAIRWELL THE FOLLOWING STAIR DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED:1)34TH, 29TH & 2ND FLOOR SOUTH STAIR2) 29TH, 27TH, SB FLOOR NORTH STAIR 333 N MICHIGAN AVE COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROPERLY RECALIBRATE GOVERNOR AND ADJUST WIND UP SAFETIES ON COUNTERWEIGHS TO REDUCE EXCESSIVE SLIDE CALL FOR REINSPECTION 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM A FULL FIRE SERVICE TEST & FULL SMOKE DETECTOR TEST WHEN MODERNIZATION IS COMPLETE. ALL ELEVATOR WILL BE OUT OF SERVICE DURING TAIS TEST 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL BUFFER CATWALK IN PIT WITH LIGHT, GFCI OUTLET, AND STOP SWITCH 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA ADD PIT LIGHTING 4' FLOURESCENT FIXTURES 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA SELF-LOCKING PIT DOOR 333 N MICHIGAN AVE PERMIT FAILED View
PRV HIGH SIDE FOR ONE UNITED COOLAIR 4 TON A/C UNIT LOCATED IN 14TH FLOOR ELEVATOR MACHINE ROOM. RECEIVER 6" X 20". 333 N MICHIGAN AVE PERMIT FAILED View
CONNECT VENT LINE UNITED COOL AIR UNIT SERVING 14TH FLOOR ELEVATOR MACHINE ROOM. 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ADD ADDITIONAL LOBBY SMOKE DETECTORS IN FRONT OF ELEVATOR #2 ON FLOORS 1-11 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE ADDITIONAL SMOKE DETECTORS IN MID RISE MACHINE ROOM AT CAR #3 HOIST MACHINE 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LOBBY SMOKE DETECTORS FOR MID RISE AND HIGH RISE ELEVATORS NOT WORKING 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CAR #11 WILL NOT RE-SET AFTER SMOKES HAVE BEEN ACTIVATED 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA TIE IN CARS #1,2,7,8,9,10,11 TO MEET CITY OF CHICAGO 2010 BUILDING CODE FOR FIRE ALARM RECALL ( P#100618622) 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CHANGE BEZELS INSIDE OF CARS #1,2 TO FIRE SERVICE BEZELS. 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA DISPLAY CAR #12 ON LOBBY PANEL 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PICTOGRAPH IN LOBBY PANEL TO SHOW ELEVATOR LOCATIONS 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE MASTER FIRE KEY SWITCH IN LOBBY PANEL TO BRING ALL ELEVATORS DOWN TO 1ST FLOOR. 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CROSS HEAD & ROPE DATA TAGS WITH AS MUCH INFORMATION AS POSSIBLE 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LOBBY SMOKE DETECTORS FOR MID RISE AND HIGH RISE ELEVATORS NEED TO BE RETESTED AND CHECK MASTER KEY SWITCH & PHASE 1 KEY SWITCH MUST BE TRUNED TO ON AT THE SAME TIME TO PULL ELEVATOR DOWN FROM ALTERNATE FLOOR. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR INSTALL GFI'S IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR REMOVE SPRINKLER FROM MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR SEAL/CAULK HOLES IN HOISTWAY AND MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR PROVIDE MACHINE ROOM DOOR LABEL AND DOOR CLOSER 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR PROVIDE ABC TYPE FIRE EXTINGUISHER 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR PERFORM ALL PERFORMANCE TESTS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR DUMBWTR PROVIDE PAN WITH DRAIN UNDER MACHINE ROOM PIPES 333 N MICHIGAN AVE PERMIT PASSED View
ARRANGE ANNUAL INSP. ARRANGE FOR ANNUAL INSPECTION REFUSED ACCESS FOR ANNUAL INSPECTION BY 2 BUILDING ENGINEERS NO NAMES)(JUST SHIRTS W/333 MICHIGAN BLDG ENGINEER) MB REAL ESTATE 333 N MICHIGAN SUITES 1219 OFFICE THE BLDG CHICAGO IL 60601 333 N MICHIGAN AVE COMPLAINT PASSED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #6 FIRE TEST AND EMERGENCY POWER 333 N MICHIGAN AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #6 PROVIDE WINDOW IN PIT DOOR WITH SWITCH 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #6 PATCH HOISTWAY AS NEEDED 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #6 SEAL PIT FROM WATER 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #6 LABEL DISCONNECTS / SOURCE LOCATION 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE(POSSIBLY AIR LINE) PIPE FROM HOISTWAY AND MACHINE ROOM ELEVATOR #10 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE EMERGENCY LIGHTING MACHINE IN THE MACHINE ROOM 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 NEED COUNTERWEIGHT DROP TEST 333 N MICHIGAN AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 CANT HOISTWAY AS NEEDED 333 N MICHIGAN AVE PERMIT PASSED View
SEE INSPECTOR COMMENTS FAILURE TO HAVE WORK INSPECTED PRIOR WALLS OR CEILINGS BEING COVERED.13-12-170 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL STENCIL ALL EQUIPMENT 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ROPE GUARDS IN SECONDARY 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ADD PIT LIGHTING AND GFI'S 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR/REPLACE CAR DOOR RESTRICTORS 333 N MICHIGAN AVE PERMIT FAILED View
REPLCE WINDOW PANES, PLEXGLAS REPLACE CRACKED GLAZING 333 N MICHIGAN AVE COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA CODE DATA PLATES 333 N MICHIGAN AVE PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT PASSED View
ARRANGE COMPLETED PERMIT INSP. 333 N MICHIGAN AVE PERMIT FAILED View
NO ENTRY 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE MAIN LINE DISCONNECTS FOR ELEVATORS #7 & #8 IN MACHINE ROOM MAINTAINING LINE OF SIGHT FROM MACHINES 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PROVIDE ADEQUATE VENYILATION IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PATCH HOISTWAY /REMOVE OLD EQUIPMENT FROM HATCH 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #1 & #2: REPAIR FIRE COMMAND PANEL EMERGENCY JEWEL 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #7: PROVIDE MISSING SIGHTGUARD AT LOBBY LEVEL 333 N MICHIGAN AVE COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #3 - #5: 2 POSITION KEY SWITCH IS NEEDED FOR ALTERNATE RECALL. CURRENTLY CANNOT DRAG CARS FROM ALTERNATE LANDING AT COMMAND PANEL. 333 N MICHIGAN AVE COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE 110 VOLT CAB LIGHTING DISCONNECTS FOR ELEVATORS #9 & #10 WITHIN LINE OF SIGHT IN THE SAME VINCINITY OF THE CONTROLLERS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA MAINTAIN 2 HOUR FIRE RATING THROUGHOUT MACHINE ROOM FOR ELEVATORS #7- #10 WITH ATTENTION TO ENTRANCE DOOR HEADER 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SWITCH IN THE SAFETY CIRCUIT TO TRIP WHEN THE ACCESS DOOR IN THE OVERHEAD OF HOISTWAY #9 IS OPENED 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA RELOCATE PIT DOOR FOR SAFE AND CONVENIENT ACCESS TO THE PITS OF ELEVATORS #9 & #10. CURRENTLY ACCESS PATH IS IMPEDED BY SHEAVES AND OTHER MOVING ELEVATOR EQUIPMENT 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE (OR EXPLAIN THAT THE DEVICES DO NOT PROPOSE AND ELECTRICAL SHORTING SAFETY SITUATION) FIRE SUPPRESSION/EXTINGUISHERS WITH SPRINKLIER HEADS MOUNTED THROUGHOUT THE MACHNE ROOM CEILINGS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PROVIDE PROPER LOCK ON ACCESS DOOR GOING TO TOP OF HOISTWAY 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROTECT DUCT IN MACHINE ROOM ( SHARP EDGE'S 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PATCH MACHINE ROOM HOLES 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PROVIDE FIRE EXTINGUSHER IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PROVIDE PROPER MACHINE ROOM DOOR'S & STEPS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 PROVIDE SAFE ACCESS TO PIT'S 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA 32 STENCIL POWER IN HOISTWAY 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 LABEL ACCESS DOOR'S ON 26TH FLOOR FOR #2 ACCESS PROVIDE PROPER SIGNAGE ON DOOR'S 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 ADJUST GIBS & SILLS AS NEEDED 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 PROVIDE LIGHT'S & GFI OUTLETS IN PIT 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #2 PROVIDE HANDRAILS AND PROPER LADDER FOR SECONDARY 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #1 & #2: PROVIDE LOBBY EMERGENCY POWER JEWEL 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA ALL ELEVATORS: PROVIDE FLOORS SERVICED ON FIRE COMMAND PANEL 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #7 - #10: PROVIDE FIREMAN'S KEY BOX IN LOBBY WITH CORRECT NUMBER OF FIRE SERVICE KEYS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE FIREMAN'S KEY BOX AT FIRE COMMAND PANEL WITH CORRECT NUMBER OF KEYS 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #3 - #5: 2 POSITION KEY SWITCH IS NEEDED FOR ALTERNATE RECALL. CURRENTLY CANNOT DRAG CARS FROM ALTERNATE LANDING AT COMMAND PANEL. 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #7: PROVIDE MISSING SIGHTGUARD AT LOBBY LEVEL 333 N MICHIGAN AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA #9 PROVIDE ADEQUATE VENTILATION IN MACHINE ROOM 333 N MICHIGAN AVE PERMIT PASSED View