Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPAIR INTERIOR WALLS/CEILING | CEILING TILES ON THE 4TH AND 5TH FLR.WATER DAMAGE WITH MOLD,MISSING OR BROKEN SOUTH INTERIOR STAIRS WALLS AND CEILING;CRACKED CONCRETE | 801 S PAULINA ST | COMPLAINT | FAILED | View |
INT WALL/CEILING PEELING PAINT | SOUTH INTERIOR STAIRS WALLS AND CEILING;PEELING | 801 S PAULINA ST | COMPLAINT | FAILED | View |
INSTALL COVERS | 5TH FLR.LECTURE HALL CORRIDOR CEILING LIGHT FIXTURE COVER;LOOSE | 801 S PAULINA ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE MAINTENANCE CONTROL PROGRAM IN MACHINE ROOMS | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MONTHLY FIREMAN'S SERVICE RECALL TEST LOG ON SITE | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WHEN MAIN FLOOR RECALL FAID ARE TRIPPLED AND RECALL TO ALTERNATE LEVEL PHASE I KEY SWITCH TURN ON WILL RECALL CARS FROM ALTERNATE LEVEL AND WHEN PHASE I KEY SWITCH IS RETURNED TO THE OFF POSITION ELEVATORS SHOULD RECALL TO INITIAL MODE OF OPERATIONS IE"ALTERNATE FLOOR" | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS SERVING FLOORS WHEN FAID(SMOKE DETECTOR)RULE 211.3B(1). ACTIVATED ELEVATORS 94001,94002,94003,94005 SHOULD ALL RECALL AND BOTH LOBBIES SHOULD BE CROSS-ZONED. | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | IDENTIFY ALL MACHINES, GOVERNORS, CONTROLLERS, CROSSHEAD DISCONNECTS AND ALL RELATING ELEVATOR EQUIPMENT SHOULD BE STENCILED WITH ACTUAL CAR NUMBERS IE:94001 | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE DOCUMENTATION OF FIRE RATING OF WOOD USED FOR SAFE ACCESS TO GORVENORS HATCHES AND PROVIDE ALL GOVERNORS W/ SAFE ACCESS. | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | UPON COMPLETION AND REPROGRAMMING OF SMOKES,CONTACT THE ELEVATOR BUREAU OF CITY OF CHICAGO AT 312-743-7308 TO SCHEDULE RE-INSPECTION. | 801 S PAULINA ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | CONTACT THE ELEVATOR BUREAU OF THE CITY OF CHICAGO TO SCHEDULE FIREMAN SERVICE SMOKE RESEND TEST, PROVIDE MAN POWER TO TEST RECALL AND RESET LOBBY PANEL | 801 S PAULINA ST | PERMIT | PASSED | View |