Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
REPL DEF HOIST ROPES FRT | ELEVATOR #18. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
INSTALL ROPE DATA TAG FRT | ELEVATOR #18. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | ELEVATOR #17 BRAILLE PLATES AT ALL FLOORS. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
INSTALL NON-VISION H/W DR FRT | ELEVATOR #17 NON-VISION PANELS ON 22ND AND LL FLOORS. REMOVE GATE AT 4TH FLOOR LANDING ON ELEVATOR #17 RESTRICTING EGGRESS FOR FIRES. RULE 110.6. REMOVE ALL NON-ELEVATOR EQUIPMENT FROM ELEVATOR #19 MACHINE ROOM RULE 101.2. PERFORM ANNUAL RELIEF PRESSURE TEST AND TAG VALVE ON ELEVATOR #19 RULE 1005.2. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
PROV FIRE KEY BOX & KEYS PASS | PROVIDE FIRE SERVICE KEY BOX ADJACENT TO MAIN ELEVATOR LOBBY PANEL. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | PERFORM ANNUAL GOVERNOR SAFETY TEST AND TAG GOVERNOR. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | SCHEDULE FIRE SERVICE/SMOKE/FLOW RECALL TEST AND EMERGENCY POWER TEST ON ALL ELEVATORS. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | MAINTAIN LOG FOR MONTHLY FIRE SERVICE PHASEI AND PHASE II TEST. 18-30-010, 13-20-120. EV007257. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
ARRANGE COMPLETED PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | DISCONTINUE LOCKING GATE AT 2ND FLOOR HOISTWAY OPENING RESTRICTING ACCESS FROM HOISTWAY ELEVATOR #18 | 69 W WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CONTACT THE CITY OF CHICAGO ELEVATOR BUREAU TO SCHEDULE TESTING OF FAID RECALL ON ELEVATOR #18 | 69 W WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DISCONTIUNE LOCKING GATE AT 2ND FLOOR HOIST OPENING RESTRICTING ACCESS FROM HOISTWAY ELEVATOR #18 | 69 W WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CONTACT THE CITYOF CHICAGO ELEVATOR BUREAU TO SCHEDULE TESTING OF HARD RECALL ON ELEVATOR #18 | 69 W WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CONTACT CITY OF CHICAGO ELEVATOR BUREAU TO SCHEDULE FIRE SERVICE TESTING | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | GATE - REMOVE FROM 2ND FLOOR LANDING. MAY NOT PREVENT EGRESS FROM ELEVATOR HOISTWAY - ELEVATOR #18 | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CROSS HEAD DATA PLATE WRONG - READS 5500 LB CAP | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIREMANS SERVICE TESTING - SCHEDULE WITH THE ELEVATOR BUREAU OF THE CITY OF CHICAGO | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WEDGE AND POURED SHACKLES -SUSPENSION MEANS MUST BE ALIKE - ELEVATOR #8 | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | HOIST ROPE CABLE DATA TAG | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SEIZE WIRE ENDS PROPERLY - NOT WITH ELECTRICAL TIES | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LOBBY PANEL NEED TEUTING ALL PHASE I HELATES ARE NOT LIGHTING | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SIGNAGE ON PIT DOORS AND MACHINE ROOM | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE MAN SERVICE ALTERNATE FLOOR RECALL MUST RECALL TO DESIGNATED FLOOR WITH PHASE I AND AUX.PHASE I ON LOBBY | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL FIRE SERVICE KEYS ARE TO BE KEYED ALIKE IN BUILING | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | KEYED STOP SWITCH IN CAB ACTIVE DURING PHASE I RECALL | 69 W WASHINGTON ST | PERMIT | PASSED | View |
APPROVE PLANS ON SITE | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
ARRANGE PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
PROVIDE MINIMUM VENT QUANTITY | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM LOSS OF TRACTION (SLIP TRACTION) TEST FOR FINAL. | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE CAR DOOR RESTRICTION PROTECTION THROUGHOUT ALL HOISTWAYS (BLIND). CURRENTLY RESTRICTORS AR NOT OPERATIONAL WITHIN THESE ZONES | 69 W WASHINGTON ST | COMPLAINT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | TIE-IN #20 CAR WITH LOBBY PANEL | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TIE WRAPS ON HOIST CABLES - REMOVE | 69 W WASHINGTON ST | PERMIT | PASSED | View |
ARRANGE COMPLETED PERMIT INSP. | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
PROVIDE MINIMUM VENT QUANTITY | 69 W WASHINGTON ST | PERMIT | PASSED | View | |
PROV FIRE KEY BOX & KEYS PASS | AT MASTER KEY SWITCH/LOBBY PANEL WITH PROPER AMOUNT OF KEYS. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | REPAIR FIRE SERVICE RECALL SYSTEM TO OPERATE PROPERLY ALL FUNCTIONS. UPON COMPLETION OF ALL REPAIRS CONTACT THE ELEVATOR BUREAU AT 312-746-8419 TO SCHEDULE A RE-INSPECTION AND TESTING OF ALL FIRE RECALL SYSTEMS, EMERGENCY POWER, AND NEW SECURITY ACCESS | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
OPEN TYPE VIOLATION | REPAIR FIREMANS RECALL SYSTEM TO OPERATE PROPERLY, ALL FUNTIONS. UPON COMPLETION OF ALL NECESSARY REPAIRS CONTACT THE ELEVATOR BUREAU TO SCHEDULE A RE INSPECTION AND TESTING OF ALL FIRE SERVICE RECALL, EMERGENCY POWER, AND CARD SECONDARY ACCESS SYSTEM. | 69 W WASHINGTON ST | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PROPER RUMBY | 69 W WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CALL FOR RE INSPECTION FOR #3-NOT READY | 69 W WASHINGTON ST | PERMIT | PASSED | View |