Chicago Building Violations Data: 31 Violations
Violation Inspector Comments Address Category Status View
MAINTAIN EXIT SIGN ILLUMINATED LL, MZ & 31/EXIT SIGNS - NOT ILLUMINATED. 50 W WASHINGTON ST PERIODIC PASSED View
OPEN TYPE VIOLATION PROVIDE DRIP PANS UNDER DRAIN PIPES OVER 21 & 28 CARS. 18-30-010, 13-20-120. 100279114 50 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION REMOVE AIR DUCTS RESTRICTING ACCESS TO SECONDARY AREAS #37. 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PATCH HOISTWAYS REMOVE WOOD IN HOISTWAY. 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION UPON COMPLETION OF ALL ELEVATORS FIRE SERVICE/SMOKE/FLOW RECALL TEST AND EMERGENCY POWER TEST. 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION LOBBY PANEL W/MASTER FIRE SERVICE KEY SWITCH. 18-30-010, 13-20-120. #100279114 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PATCH CEILING IN MID RISE MACHINE ROOM. 50 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION PATCH HOLES IN MACHINE ROOMS. 50 W WASHINGTON ST PERMIT PASSED View
SEND EX. METAL LETTER 50 W WASHINGTON ST COMPLAINT PASSED View
PIPE OPENING W/NONCOMBUST MATL PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH IS NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE. IN ADDITION, ANNULAR INFILL AND PENETRATION PATCHING ARE ALSO REQUIRED AT CEILING LEVEL.1) ELECTRICAL CLOSETS, ELECTRICAL SWITCHGEAR ROOMS, ELECTRICAL EQUIPMENT ROOMS AND DATA CLOSETS THROUGHOUT THE BUILDING. 2) ELEVATOR MACHINE ROOMS THROUGHOUT BUILDING3) MECHANICAL 1 LEVEL, ELEVATOR EQUIPMENT ROOMS 1 & 2 4) MECHANICAL 2 LEVEL, LAUNDRY ROOM5) MECHANICAL ROOMS THROUGHOUT BUILDING6) LOWER LEVEL - PUMPROOM, BOLLARD HYDRAULIC ROOM 50 W WASHINGTON ST PERIODIC FAILED View
1HR PUB.CORIDR NON-RES/SPRNKLD 1)PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED IN THE FOLLOWING LOCATIONS:ROOMS ADJACENT TO FIRE RATED PUBLIC CORRIDOR ON PENTHOUSE LEVEL, MECHANICAL 1, 2 & 3 LEVELS, CONCOURSE LEVEL & LOWER LEVEL. HORIZONTAL PENERATIONS INTO FIRE RATED CORRIDOR EXISTS AT MULTIPLE LOCATIONS. PENENTRATIONS HAVE BEEN INFILLED WITH NON APPROVED FIRE BLOCKED FOAM OR MISSING ANY TYPE OF INFILL ALLTOGETHER. IN ADDITION, FIRE RESISTANCE RATING OF DOORS ALONG AFOREMENTIONED CORRIDORS COULD NOT BE VERIFIED DUE TO MISSING DOOR RATING LABEL.2) FIRE RESISTANCE RATING OF THE FOLLOWING DOORS COULD NOT BE VERIFIED DUE TO MISSING DOOR RATING LABEL: A) ELECTRICAL CLOSETS AND DATA ROOMS THROUGHOUT ENTIRE BUILDING. IN ADDITION, SELF CLOSING DEVICES ARE REQUIRED AT ELECTRICAL CLOSETS AND DATA ROOMS THROUGHOUT ENTIRE BUILDING.3) THE FOLLOWING DOORS ALONG THE FIRE RATED CORRIDOR ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED. A) 31ST FLOOR, PAINT ROOM - NO SELF CLOSING DEVICE B) MECHANICAL 1 LEVEL, ELEVATOR EQUIPMENT ROOM - NO SELF CLOSING DEVICE 50 W WASHINGTON ST PERIODIC FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY ACCESS PENETRATIONS IN ALL STAIR ENCLOSURES MUST BE SEALED WITH A APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY. EXISTING ACCESS PENETRATIONS HAVE BEEN ENCLOSED WITH NON RATED ACCESS PANELS AT MULTIPLE LOCATIONS THROUGHOUT BUILDING. REMOVE EXISTING NON RATED PANELS AND INFILL WITH FIRE RATED ACCESS PANELS. 50 W WASHINGTON ST PERIODIC FAILED View
SELF-CLOSE CLASS B FIRE DOOR SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK:1) LOWER LEVEL - PUMP ROOM2) CONCOURSE LEVEL - MECHANICAL ROOM3) ELECTRICAL CLOSETS WITH VENTED DOOR AND TRANSOM THROUGHOUT ENTIRE BUILDING. 50 W WASHINGTON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED MAINTAIN EXIT SIGN ABOVE ENTRY DOOR IN WORKING ORDER, EXIT SIGNAGE NOT ILLUMINATED AT TIME OF INSPECTION. 50 W WASHINGTON ST PERIODIC FAILED View
CARB MONOX DETECT IN ASSEMBLY FURNISH / INSTALL CARBON MONOXIDE DETECTOR IN LAUNDY ROOM AT THE 2ND MECHANICAL LEVEL. INSTALL ADJACENT TO GAS FIRED EQUIPMENT. 50 W WASHINGTON ST PERIODIC FAILED View
PROVIDE 1) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. SHALL BE STORED IN FIREPROOF CABINET PER 13-76-075. PAINT WAS FOUND THROUGHOUT PENTHOUSE LEVEL, MECHANICAL 1, 2 & 3 LEVELS, CONCOURSE LEVEL & LOWER LEVEL. 50 W WASHINGTON ST PERIODIC FAILED View
REPLCE WINDOW PANES, PLEXGLAS REPLACE CRACKED WINDOWS PANES AT THE FOLLOWING LOCATIONS:1) STAIR 3 SMOKE TOWER AT 11TH, 9TH & 8TH FLOORS 50 W WASHINGTON ST PERIODIC FAILED View
CLASS B DOOR IN STAIRWELL THE FOLLOWING STAIR DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED.1) STAIR 3 - PENTHOUSE LEVEL, MECHANICAL 3 LEVEL, 29TH FLOOR & 9TH FLOOR MEZZANINEFIRE RESISTANCE RATING OF THE FOLLOWING DOORS COULD NOT BE VERIFIED DUE TO EXISTING DOOR LABEL HAVING BEEN PAINTED OVER. CLEAN/RESTORE LABEL AS REQUIRED TO ALLOW FOR VISIBLE CONFIRMATION OF FIRE RATING1) STAIR 3 & 2, MECHANICAL 3 LEVEL2) STAIR 4 & 5, 29TH, 26TH, 25TH & 24TH LEVEL 50 W WASHINGTON ST PERIODIC FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #38 CAR ROPE REPLACEMENT ACCEPTED 50 W WASHINGTON ST PERMIT PASSED View
PIPE OPENING W/NONCOMBUST MATL ALL FLOORS, - TELEPHONE, TELECOM CLOSETS, - AS PER BUILDING CODE 15-8-640 OPENINGS AROUND EXPOSED PIPES OR POWER SHAFTING SHALL BE FILLED WITH APPROVED NONCOMBUSTIBLE MATERIAL, OR SHALL BE CLOSED OFF BY CLOSE-FITTING METAL CAPS AT THE CEILING AND FLOOR LINE, AND ON EACH SIDE OF A WALL, CEILING OR PARTITION. 50 W WASHINGTON ST COMPLAINT FAILED View
PROVIDE AS PER CODE SECTION 15-8-060 (C) 3HR FIRE RATED DOORS BETWEEN GARAGE AND COURT LOBBY.THE SEPARATION WALL BETWEEN THE PARKING GARAGE AND COURT AREAS MUST BE 4 HR FIRE RATED, - DOOR OPENINGS MUST BE PROTECTED WITH (2) 3HR FIRE RATED DOORS IN SERIES. EXISTING DOORS WERE CORRECT, FOR SOME REASON SOMEONE REMOVED AND INSTALL AN AUTOMATIC NONE FIRE RATED DOORS, SECOND DOOR WAS REMOVE COMPLETELY. 50 W WASHINGTON ST COMPLAINT FAILED View
PROVIDE THROUGHOUT ENTIRE BUILDING ALL FLOORS, ALL OFFICES AND COURT ROOMS, - AS PER SECTION 33 (13-124-350 )DOORS INCLUDING ADJACENT WINDOWS NEXT TO ANY DOORS, PROVIDE TEMPERED GLASS AT ANY DOOR AND ANY GLASS PANEL MORE THEN 18 INCHES IN WIDTH IMMEDIATELY ADJACENT TO ANY DOOR LESS THEN 24 INCHES ABOVE THE FLOOR. 50 W WASHINGTON ST COMPLAINT FAILED View
NO KEY TO USE EXIT DOOR AT GARAGE LEVEL BETWEEN GARAGE AND COURT LOBBY CORRIDOR , - 3 HR FIRE RATED DOORS ARE LOCKED, - FAIL TO EQUIP DOOR LOCK HARDWARE WHICH ALLOWS DOOR TO OPEN WITHOUT KEY OR SPECIAL KNOWLEDGE FROM SIDE OF EGRESS 50 W WASHINGTON ST COMPLAINT FAILED View
CARB MONOX DETECT IN ASSEMBLY AT BOILER ROOM, - CARBON MONOXIDE DETECTOR MISSING. 50 W WASHINGTON ST COMPLAINT FAILED View
WORKING SPACE PROVIDE 3' OF CLEAR SPACE AROUND ELECTRICAL EQUIPMENT 50 W WASHINGTON ST COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA CONTACT THE CITY OF CHICAGO ELEVATOR BUREAU TO SCHEDULE THE INSPECTION OF REPAIR ON ELEVATOR #5 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION REPLACE CAR HOIST ROPES ON ELEVATOR #39. 50 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION REPLACE ALL HOISTWAY ACCESS SWITCHES AT TOP TERMINAL LANDINGS, SWITCHES ARE STICKING AND CAN BE OPERATED WITH A COIN OR SCREWDRIVER. 50 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION BRAKE TEST REQUIRMENTS RULE 1002.3D (2.3.4) #28,#18,#27,#42,#19. 50 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION REPLACE ALL DEFECTIVE ACCESS KEY SWITCHES IN BUILDING. 50 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION RELOCATE ACTUATOR FOR ROPE GRIPER ON ELEVATOR #40 FOR PROPER ACCESS AROUND ELEVATOR EQUIPMENT. 50 W WASHINGTON ST PERMIT FAILED View