Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
PRV HIGH SIDE | 450 P.S.I.G. FOR ONE 120 TON MAMOTH A/C UNIT WITH TWO 60 TON COMPRESSORS LOCATED ON ROOF. (18-28-1102.3,18-28-1006.5,18-28-1006.3) | 240 E ONTARIO ST | PERIODIC | FAILED | View |
OBTAIN REFRIGERATION PERMIT | FOR THE ABOVE UNIT. (SEC.18-28-106.1) | 240 E ONTARIO ST | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | 1. REPAIR STOP SWITCH ON WHEELCHAIR LIFT. 2. PRESSURE TEST #3 PASSENGER ELEVATOR DATED & SEAL. 3. PROVIDE FIRE EXTINGUISHER IN ALL MACHINE ROOMS. 4. INSTALL LAMP GUARDS IN MACHINE ROOM. 5. PROVIDE GFI OUTLET IN MACHINE ROOM. 6. REPAIR DISCONNECT DOOR-NOT TO OPEN WITH POWER ON #1. 18-30-010,13-20-120. EV005112. | 240 E ONTARIO ST | PERIODIC | FAILED | View |
OPEN TYPE VIOLATION | 1. INSTALL LAMP GUARDS IN MACHINE ROOM. 2. GFI OUTLET MACHINE ROOM. 3. PROVIDE FIRE EXTINGUISHER IN MACHINE ROOM. 4. REPAIR DISCONNECT DOOR-NOT TO OPEN WITH POWER ON EAST. 18-30-010,13-20-120 (100070171) | 240 E ONTARIO ST | PERMIT | FAILED | View |
PRV HIGH SIDE | 450 P.S.I.G. FOR ONE 120 TON MAMOTH A/C UNIT WITH TWO 60 TON COMPRESSORS LOCATED ON ROOF. (18-28-1102.3,18-28-1006.5,18-28-1006.3) | 240 E ONTARIO ST | PERIODIC | CLOSED | View |
SEE INSPECTOR COMMENTS | ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED AND BEAR THE LABEL OF A RECOGNIZED TESTING LABORATORY MAMMOTH ROOFTOP A/C AND HEATING UNIT 18-27-110.2 | 240 E ONTARIO ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | PROVIDE REQUIRED EQUIPMENT GROUNDING AND BONDING OF ALL RACEWAY IN MAMMOTH UNIT 18-27-250.110 | 240 E ONTARIO ST | COMPLAINT | FAILED | View |
PROVIDE APPROVED RACEWAY FOR ALL CONDUCTOR IN BOTH AIR HANDLING AND NON AIR HANDLING AREAS 18-27-300.22 | 240 E ONTARIO ST | COMPLAINT | FAILED | View | |
SHALL BE LOCATED IN SIGHT FROM THE MOTOR LOCATION AND DRIVEN MACHINERY LOCATION 18-27-430.102B | 240 E ONTARIO ST | COMPLAINT | FAILED | View | |
OBTAIN REFRIGERATION PERMIT | FOR THE ABOVE UNIT. (SEC.18-28-106.1) | 240 E ONTARIO ST | PERIODIC | CLOSED | View |