Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
OPEN TYPE VIOLATION | DUE TO KEY SWITCH REPAIRS ARRANGE FOR FIRE SERVICE RECALL TEST TO BE WITNESSED BY CITY ELEVATOR INSPECTORS. 18-30-010,13-20-120. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
STOP LEAKING WATER | BALLY'S HEATH CLUB AREA UNDER WHIRLPOOL -WATER LEAKING THROUGH LIGHT FIXTURE IN SHOWER ROOM AREA. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | WOMENS LOCKER ROOM CEILING IN BASEMENT WATER DAMAGED AREA'S THROUGH OUT AREA -RUSTED &DETERIORATED CEILING MEMBERS &SAGGING & MISSING TILES. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | INTERIOR STAIRWELLS -PIPE PENATRATIONS ALL TO BE SEALED &CLOSED UP FIRE SEPERATION REQUIREMENT. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS, ADVANCED FREE WEIGHT ROOM POOL, CARDIO, AEROBICS, COED WEIGHT, NAUTILUS WEIGHT. | 25 E WASHINGTON ST | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE POSITION INDICATOR ON LOBBY PANEL | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE INDEPENDENT KEY SWITCHES AT LOBBY PANEL AND LABEL | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 8TH FLR./EAST STAIRWAY EXIT SIGN NOT ILLUMINATED. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY-BUILDING ENGINEER UNAVAILABLE FOR INSPECTION MAKE ARRANGEMENTS FOR INTERIOR INSPECTION | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
NO POSTED ADDRESS | POST PROPER ADDRESS ON WABASH STREET ENTRANCE | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARDS WITH DIAGRAMS FOR ALL ROOMS | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | 25 E WASHINGTON ST | PERIODIC | FAILED | View | |
LIFE SAFETY EVALUATION PLAN | LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY CARDS FOR AB AREA, FREE WEIGHTS, 3B, NAUTILUS 2B & PERSONAL TRAINING AREA. POST DIAGRAMS FOR ALL LEVELS. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
INSTITUTIONAL EXITDOOR RELEASE | PROVIDE PANIC HARDWARE ON ALL EXIT DOORS ON LOWER LEVEL 2B & GRADE LEVEL EXIT DOORS FROM STAIRWELLS. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
INSTITUTIONAL EXITDOOR RELEASE | PROVIDE PANIC HARDWARE ON ALL DOORS THAT ARE PART OF AN EXIT PATH FROM A ROOM OR FLOOR WHERE A COMBINED TOTAL EXCEEDS 200. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | MAINTAIN EXIT SIGNS AND EMERGENCY LIGHTS IN GOOD CONDITION. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY SIGNS AND DRAWINGS FOR 7 SPACES ON LOWER LEVELS 1-3. THIRD YEAR NO COMPLIANCE. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: STABILIZE PIT LADDER HANDRAIL | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PROVIDE MACHINE ROOM (CONTROLL SPACE) WITH LIGHT SWITCH. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 8: PROVIDE ELEVATOR I.D. ON 1ST FLOOR JAMB | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: SCHEDULE CITY FIRE RECALL TEST (FAIDS) | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE BRAILLE TO LOWER FLOORS LL1-LL3 | 25 E WASHINGTON ST | PERMIT | FAILED | View |
ARRANGE PREMISE INSPECTION | NO ENTRY-BUILDING ENGINEER UNAVAILABLE FOR INSPECTION MAKE ARRANGEMENTS FOR INTERIOR INSPECTION | 25 E WASHINGTON ST | PERIODIC | PASSED | View |
NO POSTED ADDRESS | POST PROPER ADDRESS ON WABASH STREET ENTRANCE | 25 E WASHINGTON ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | COMPLETE MACHINE ROOM. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | STOP SWITCHES IN MACHINE DECKS & SECONDARIES. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | HEAVY DUTY FUSED, LOCKABLE DISCONNECTS 11OV & LINE IN SIGHT OF MACHINES AND CONTROLLERS. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CABLE GUARDS ON 22ND FLOOR FOR 1, 3, & 5 CAR, CAR & CWT. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RAILINGS ON MACHINE DECK 22ND FLOOR W/STAIRS. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LIGHTING AND CONVIENCE OUTLETS (GFCI) IN ALL MACHINE CONTROLLER AREAS. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MACHINE ROOM LIGHTING. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SAFE ACCESS TO SECONDARY DECK PROVIDE LADDERS PERMANENT MOUNT. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CABLE GUARDS IN ALL SECONDARY AREAS CAR & CWT. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE AN INTENTIONAL MOVEMENT PROTECTION (ROPE GRIPPERS?). | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | FIRE STOPS ON CAR GIBS & HOISTWAY DOOR GIBS. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEATHER SECURE TRAILING BUFFER. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECURE ABANDONED OPENINGS. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BUFFER SWITCH. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PAN (GUTTERS) UNDER DRAINS & FIRE ORGANIZER PIPES IN MACHINE ROOM. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE ALL ABANDONED CONDUITS, PIPES & EQUIPMENT FROM MACHINE ROOM. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PIT PLATFORMS W/STOP SWITCHES & LIGHTING. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PIT STOP SWITCHES LOCKABLE AT POINT OF ENTRY TO PITS.(CHAPTER 18-30 OF CITY OF CHICAGO BUILDING CODE AND 2007 A.S.M.E. 17.1) #100354773 | 25 E WASHINGTON ST | PERMIT | PASSED | View |
INSTITUTIONAL EXITDOOR RELEASE | PROVIDE PANIC HARDWARE ON ALL STAIRWELL DOORS. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
POST APPROVED OCCUPANCY CARD | POST OCCUPANCY CARD FOR FREE WEIGHT AREA AND AB AREA, PERSONAL TRAINING AREA 3, AND NAUTILUS ROOM. POST DIAGRAMS WITH OCCUPANCY CARDS, ALSO OBTAIN AND POST NEW OCCUPANCY FOR POOL AREA. | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PAN AND DRAIN UNDER PIPE MACH.RM. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PROVIDE SHEAVE GUARD ON TOP OF ELEVATOR | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE SAFE ACCESS TO SERVICE MACHINES ON DECK. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE KICKPLATES AROUND CWT HITCHES IN MACHINE ROOM DECK | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PATCH NOT NEEDED HOLES IN MACHINE ROOM DECK. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: NUMBER HOISTWAY DOORS, CARTOP, TOE GUARD, TAIL SHEAVE | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE PERMANENT PIPING FOR POWER FROM MACHINE ROOM TO TRANSFORMER | 25 E WASHINGTON ST | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 25 E WASHINGTON ST | PERMIT | PASSED | View | |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY CARD FOR ALL ROOMS. BUSINESS ROOM HAS CHANGED FROM BALLY'S FITNESS TO LA FITNESS. AREAS INCLUDE; AEROBICS ROOM, POOL AREA, FREE WEIGHT AREA, CARDIO ROOM AND WEIGHT MACHINE ROOM | 25 E WASHINGTON ST | PERIODIC | CLOSED | View |
INSTITUTIONAL EXITDOOR RELEASE | MISSING PANIC HARDWARE AT STAIRWELL DOORS, ALL EXITING. | 25 E WASHINGTON ST | PERIODIC | CLOSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | IDENTIFY ELEVATOR AT ALL REQUIRED LOCATIONS WITH THE SAME NUMBER. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RETEST FIRE SERVICE. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PHASE ONE KEY SWITCH IN LOBBY PANEL FOR HIGH RISE CARS #1-7 | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR ALL LIGHTS IN LOBBY PANEL | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL FIREMAN'S RECALL HATS IN LOW RISE | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PULL PERMIT FOR WORK AND TEST FIREMAN'S RECALL WITH CITY - LOW RISE CARS | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE WORKING PIT BELL | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CONNECT ALARM BELL TO CAR STOP SWITCH KEY | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL ALL CAR TOPS | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PROPER HANDRAIL ON UPPER MACHINE DECK | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE WATER PIPE - UPPER DECK | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | SECURE STAIRS AND APPROVED HANDRAIL - UPPER DECK | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | GROUT SILLS AND FINISH CAB FLOOR. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | WORKING PHONE AND COMMUNICATION FAILURE REQUIRED. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | LABEL DISCONNECTS WITH VOLTAGE,SOURCE AND USE. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | IDENTIFY ELEVATOR AT ALL REQUIRED LOCATIONS WITH THE SAME NUMBER.(#14 ELEVATOR) | 25 E WASHINGTON ST | PERMIT | PASSED | View |
SELF-CLOSE CLASS B FIRE DOOR | SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS.1) ROOFTOP ACCESS DOOR IN 22ND FLOOR MECHANICAL ROOM (DOES NOT LATCH)2) NORTH EAST CORRIDOR 3RD FLOOR (NO LATCHING HARDWARE)3) 30 S. WABASH ENTRY (NOT LATCHING)4) ALL ELECTRICAL RISER ROOMS THROUGHOUT ALL FLOORS (MAJORITY CONSIST OF NON LABELED DOORS WITHOUT ANY SELF CLOSING DEVICES)5) ALL MECHANICAL EQUIPMENT ROOMS THROUGHOUT ALL FLOORS (MAJORITY CONSIST OF NON LABELED DOORS OR PAINTED LABELS) IN ADDITION, OBSERVATION PANELS MUST INCLUDE STANDARD WIRE GLASS HAVING A EXPOSED AREA NOT EXCEEDING 100 SQUARE FEET6) ALL MECHANICAL CHASE ENCLOSURE DOORS, EXISTING DOORS ARE MISSING SELF CLOSING DEVICES.7) THROUGHOUT BASEMENT MECHANICAL/ELECTRICAL ROOMS.7) 3RD FLOOR NITROGEN & OXYGEN STORAGE CLOSETS, EXISTING DOORS NOT LATCHING PROPERLY. | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
CLASS B DOOR IN STAIRWELL | FIRE RESISTANCE RATING OF THE FOLLOWING DOORS COULD NOT BE VERIFIED DUE TO MISSING OR PAINTED OVERDOOR RATING LABEL.1) 15TH FLOOR EAST & WEST STAIR2) 12TH FLOOR EAST STAIR (2 DOORS)3) 8TH FLOOR EAST STAIR4) 7TH FLOOR EAST & WEST STAIR5) 6TH FLOOR EAST & WEST STAIR6) 5TH FLOOR WEST STAIR7) 4TH FLOOR EAST STAIR8) 2ND FLOOR WEST STAIR9) REAR EXIT FROM AMERICA'S BEST TENANT SPACETHE FOLLOWING DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED.1) 4TH FLOOR WEST STAIR2) 1ST FLOOR EAST & WEST LOBBY (NO LATCHING HARDWARE) | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. FIRE CAULK IS EVIDENT THROUGHOUT STAIR PENETRATIONS BUT IS MISSING AT THE FOLLOWING LOCATIONS.1) 22ND, 21ST AND 3RD FLOOR EAST STAIR2) 20TH, 13TH AND 7TH FLOOR WEST STAIR | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
PIPE OPENING W/NONCOMBUST MATL | PENETRATIONS MUST BE SEALED WITH APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN INFILLED WITH FIREBLOCK FOAMS WHICH ARE NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ALL MECHANICAL ROOMS THROUGHOUT ENTIRE BUILDING2) ALL ELECTRICAL RISER ROOMS THROUGHOUT ENTIRE BUILDING3) ELEVATOR CONTROL ROOM4) ELEVATOR MACHINE PENTHOUSE STORAGE CABINET5) ALL DATA CLOSETS THROUGHOUT ENTIRE BUILDING6) ALL STORAGE ROOMS ON 21ST & 4TH FLOORS7) ALL RATED CORRIDORS (VISIBLE PENETRATIONS OBSERVED ON 21ST AND 10TH FLOORS. ALL OTHER FLOORS HAVE CEILING TILE, VISUAL OBERSERVATION WAS NOT FEASIBLE BUT PENETRATIONS ARE PRESUMED)8) THROUGHOUT ENTIRE LOWER LEVEL 3 | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | EXI SIGN NOT ILLUMINATED AT THE FOLLOWING LOCATIONS1) JOS. A BANKS, ABOVE REAR EXIT DOOR2) AMERICA'S BEST, ABOVE ENTRY AND REAR EXIT DOOR3) STARBUCKS, ABOVE ENTRY DOOR | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
CARB MONOX DETECT IN ASSEMBLY | PROVIDE CARBON MONOXIDE DETECTOR ADJACENT TO GAS EQUIPMENT IN THE ELECTRICAL CLOSETS THAT CONTAIN GAS METERS/PIPING/EQUIPMENT AND ADJACENT TO GAS FIRED EQUIPMENT THROUGHOUT BASEMENT LOWER LEVEL 3. | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
INSTALL ILLUMINATION | PROVIDE EMERGENCY LIGHTING AT 21ST FLOOR STORAGE ROOMS | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
2-HR HEATING PLANT ENCLOSURE | PROVIDE TWO HOUR ENCLOSURE AT MECHANICAL ROOMS ON 21ST & 7TH FLOOR AND AT BASEMENT MECHANICAL ROOMS. EXISTING ENCLOSURES ARE EITHER CONSTRUCTED OF COMBUSTIBLE MATERIALS, HAVE SECTIONS OF WALL MISSING OR HAVE PARTITIONS THAT TERMINATE BELOW THE CEILING DECK. | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
1HR ENCL FLR TO FLR SHAFT/DUCT | ENCLOSE PIPE SHAFTS IN ELECTRICAL CLOSETS, METER ROOM, RISER ROOMS WITH CONSTRUCTION PROVIDING FIRE RESISTANCE OF NOT LESS THAT ONE HOUR. EXISTING ROOMS HAVE MAJOR BREACHES AT FLOORS AND CEILINGS. | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
CONNECT VENT LINE | FOR ONE MULTISTACK 40 TON A/C UNIT LOCATED IN 10TH FLOOR MECHANICAL ROOM- R410A, TWO COMPRESSORS. | 25 E WASHINGTON ST | PERIODIC | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CITY FIRE RECALL TEST | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | MACH. RM. DOOR SIGNAGE | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PATCH NOT NEEDED HOLES IN MACHINE ROOM DECK. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PATCH HOISTWAY, MACHINE ROOM, PIT WITH 2 HOUR RATED MATERIAL WHERE NEEDED. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PROVIDE SAVE ACCESS TO SERVICE MACHINES ON DECK. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ELEVATOR 11: PROVIDE KICKPLATES AROUND CWT HITCHES IN MACHINE ROOM DECK | 25 E WASHINGTON ST | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 25 E WASHINGTON ST | PERMIT | FAILED | View | |
ARRANGE COMPLETED PERMIT INSP. | 25 E WASHINGTON ST | PERMIT | FAILED | View | |
POST APPROVED OCCUPANCY CARD | OBTAIN AND POST OCCUPANCY PLACARD FOR EXPANDED MUSEUM SPACE. WORK COMPLETED UNDER PERMIT #101009677 | 25 E WASHINGTON ST | PERIODIC | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 25 E WASHINGTON ST | PERMIT | PASSED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PATCH HOISTWAY, MACHINE ROOM, PIT WITH 2 HOUR RATED MATERIAL WHERE NEEDED. | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS: PROVIDE ADA REQUIREDED NUMBERING TO LL3, LL1, 4TH, AND 5TH FLOORS | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS - PROVIDE ELEVATOR IDENTIFICATION ON EVERY FLOOR EACH JAMB | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS - PROVIDE SECOND PIT STOP SWITCH FOR DEEP PIT THAT SITS 47" ABOVE PIT FLOOR | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | ALL ELEVATORS TEST: CARD READER ONCE INSTALLED, EMERGENCY POWER, LOSS OF COMMUNICATION, AND PHASE II OPERATION BEFORE PERMIT IS FINALED | 25 E WASHINGTON ST | PERMIT | FAILED | View |
IDENTIFY ELEV POWER LINE DISC | ALL ELEVATORS - PROVIDE SOURCE FEED LOCATION FOR 110V DISCONNECTS | 25 E WASHINGTON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PER CITY OF CHICAGO CODE "VIDEO DISPLAY MONITORS MAY NOT BE USED FOR A FIRE COMMAND PANEL OR CONTROL PANEL. | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PERMANENT NOT VIDEO DIAGRAMMATIC REPRESENTATION OF LOBBY AT LOBBY CONTROL PANEL | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | OPENED COMPLAINT INSPECTION #13850869 FOR 3 OPEN ITEMS | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #8-#11 ELEVATORS: PROVIDE DIAGRAMMATIC REPRESENTATION OF LOBBY AND AFFIX TO LOBBY COMMAND PANEL (COMPLAINT INSPECTION) | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #8-#11 ELEVATORS: PROVIDE CORRECT "FLOORS SERVED" PLATE ON LOBBY COMMAND PANEL (COMPLAINT INSPECTION) | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | #8 ELEVATOR: PROVIDE ELEVATOR IDENTIFICATION ON JAMB AT LOBBY LEVEL (COMPLAINT INSPECTION) | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
SEE INSPECTOR COMMENTS | 25 E WASHINGTON ST | PERMIT | FAILED | View | |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE FIRE SIGNS ON ALL LANDINGS | 25 E WASHINGTON ST | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | CABLE - CAR #3 | 25 E WASHINGTON ST | PERMIT | PASSED | View |
RESTORE EXIT AND EM | EMERGENCY LIGHTING NOT WORKING WHEN TESTED.1)SUITE 17002) SUITE 1500 CONFERENCE ROOM3) SUITE 14004) 3RD FLOOR NORTHWEST SECTION OF BUILDING5) B1 EAST STAIR6) THROUGHOUT ENTIRE BASEMENT LOWER LEVEL 3 | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
PROVIDE | TWO HOUR ENCLOSURE AT ELECTRICAL RISER ROOMS THROUGHOUT ENTIRE BUILDING PER 4(13-76-080)(F). | 25 E WASHINGTON ST | COMPLAINT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 25 E WASHINGTON ST | PERMIT | PASSED | View |