Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
RELOCATE THE CONDENSING UNIT TO A READILY ACCESIBLE LOCATION TO PROVIDE FOR INSPECTION AND SERVICE. (18-28-1101.10) | 101 W MADISON ST | PERIODIC | FAILED | View | |
PROVIDE | ALL DOORS MUST BE UNLOCKED AT ALL TIMES OR PROVIDE FAIL SAFE SYSTEM. 34(19-196-084) PROVIDE PLANS & PERMITS MULTIPLE DOORS FROM 2 THRU 20 HAVE DOORS LOCKED IN TENANT SPACE | 101 W MADISON ST | PERIODIC | FAILED | View |
REMOVE | THE CONDENSING UNIT THAT IS CURRENTLY INSTALLED HANGING OFF THE WEST WALL OF THE BUILDING IN THE ALLEY AND RELOCATE IT TO THE ROOF OR GRADE. (13-20-790) | 101 W MADISON ST | PERIODIC | FAILED | View |
OBTAIN REFRIGERATION PERMIT | 101 W MADISON ST | PERIODIC | FAILED | View | |
ARRANGE FOR RE-INSPECTION | CONCERNING COMPLIANCE WITH A PENDING NOTICE OF VIOLATIONS. | 101 W MADISON ST | PERIODIC | FAILED | View |
REMOVE | THE TWO(2) CONDENSING UNITS THAT ARE CURRENTLY INSTALLED HANGING OFF THE WEST WALL OF THE BUILDING IN THE ALLEY AND RELOCATE THEM TO THE ROOF OR GRADE. (13-20-790). ONE FOR AIR CONDITIONING,ONE FOR THE COOLER. | 101 W MADISON ST | PERIODIC | FAILED | View |
RELOCATE THE CONDENSING UNITS TO A READILY ACCESIBLE LOCATION TO PROVIDE FOR INSPECTION AND SERVICE. (18-28-1101.10) | 101 W MADISON ST | PERIODIC | FAILED | View | |
REMOVE | THE CONDENSING UNIT THAT IS CURRENTLY INSTALLED HANGING OFF THE WEST WALL OF THE BUILDING IN THE ALLEY AND RELOCATE IT TO THE ROOF OR GRADE. (13-20-790) | 101 W MADISON ST | PERIODIC | FAILED | View |
RELOCATE THE CONDENSING UNIT TO A READILY ACCESIBLE LOCAATION TO PROVIDE FOR INSPECTION AND SERVICE. (18-28-1101.10) | 101 W MADISON ST | PERIODIC | FAILED | View | |
ARRANGE FOR RE-INSPECTION | CONCERNING COMPLIANCE WITH A PENDING NOTICE OF VIOLATIONS. | 101 W MADISON ST | PERIODIC | FAILED | View |
RELOCATE THE CONDENSING UNIT TO A READILY ACCESIBLE LOCATION TO PROVIDE FOR INSPECTION AND SERVICE. (18-28-1101.10) | 101 W MADISON ST | PERIODIC | FAILED | View | |
OBTAIN REFRIGERATION PERMIT | THIS PERTAINS TO THE RELOCATION OF THE UNIT CURRENTLY HANGING ON THE WALL IN THE ALLEY. THE TWO (2) UNITS IN THE SUB BASEMENT SERVING THE FOOD COURT(CARLYLES). THE ONE (1) UNIT ON THE 2ND FLOOR(CARLYLE) | 101 W MADISON ST | PERIODIC | FAILED | View |
LIFE SAFETY EVALUATION PLAN | LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266 | 101 W MADISON ST | COMPLAINT | FAILED | View |
CONNECT VENT LINE | PIPE THE VENT LINE TO THE OUTSIDE ATMOSPHERE ON THE FOLLOWING UNITS: 2-CARLYLE UNITS IN THE SUB BASEMENT SERVING THE FOOD COURT. 1- WESTINGHOUSE UNIT IN THE SUB BASEMENT SERVING THE ENGINEERS WORK SHOP. 1- CARRIER UNIT ON THE 14TH FLOOR IN THE MECHANICAL ROOM. 1- CARRIER UNIT ON THE 17TH FLOOR IN THE MECHANICAL ROOM.1- CARRIER UNIT ON THE 11TH FLOOR IN THE MECHANICAL ROOM. | 101 W MADISON ST | PERIODIC | FAILED | View |
PRV PLUGGED/CAPPED | PRV VALVE CAPPED ON THE CARRIER UNIT ON THE 5TH FLOOR IN THE MECHANICAL ROOM. | 101 W MADISON ST | PERIODIC | FAILED | View |
RECONNECT VENT LINE | SEAL OPEN END OF VENT LINE ON THE 8TH FLOOR IN THE MECHANICAL ROOM | 101 W MADISON ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | SUITE 2100, 19TH, 18TH AND 7TH FLR- EXIT SIGNS NOT ILLUMINATED. | 101 W MADISON ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | 21ST FLR/CORRIDOR-DOOR WILL NOT CLOSE PROPERLY. | 101 W MADISON ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | BASEMENT AT WEST EXIT- FIRE EXTINGUISHER MISSING TAG. | 101 W MADISON ST | PERIODIC | FAILED | View |
RECONNECT VENT LINE | 101 W MADISON ST | PERIODIC | FAILED | View | |
ARRANGE FOR RE-INSPECTION | 101 W MADISON ST | PERIODIC | FAILED | View | |
RECONNECT VENT LINE | MACHINE ROOM | 101 W MADISON ST | PERIODIC | PASSED | View |
ARRANGE FOR RE-INSPECTION | MACHINE ROOM | 101 W MADISON ST | PERIODIC | PASSED | View |
RELOCATE THE CONDENSING UNIT CURRENTLY HANGING ON THE WALL ON THE WEST SIDE OF THE BUILDING. THE UNIT AND SUPPORT HAVE BEEN DAMAGED BY A TRUCK AND MUST BE REPLACED AND MOVED TO A HIGHER LOCATION TO PREVENT FUTURE OCCURENCES. THE SUPPORT MUST BE CAPABLE OF SUPPORTING THE WEIGHT OF THE UNIT AND THRU BOLTED THROUGH THE MASONRY WALL.(18-28-1101.10) | 101 W MADISON ST | PERIODIC | FAILED | View | |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312)743-3562 | 101 W MADISON ST | PERIODIC | FAILED | View |
RELOCATE THE CONDENSING UNIT CURRENTLY HANGING ON THE WALL ON THE WEST SIDE OF THE BUILDING. THE UNIT AND SUPPORT HAVE BEEN DAMAGED BY A TRUCK AND MUST BE REPLACED AND MOVED TO A HIGHER LOCATION TO PREVENT FUTURE OCCURENCES. THE SUPPORT MUST BE CAPABLE OF SUPPORTING THE WEIGHT OF THE UNIT AND THRU BOLTED THROUGH THE MASONRY WALL.(18-28-1101.10) | 101 W MADISON ST | PERIODIC | CLOSED | View | |
ARRANGE FOR RE-INSPECTION | CALL INSPECTOR MARK HOUTSMA (312)743-3562 | 101 W MADISON ST | PERIODIC | CLOSED | View |
REPAIR INTERIOR WALLS/CEILING | INTERIOR STAIRS- EVERY FLOOR WITH SECTION OF WALL CUT OPEN FOR ACCESS. WATER DAMAGE, FLAKING PAINT AT 24 AND AT ROOF LEVEL. BOILER ROOM CLAY TILE FIRE WALL DISINTEGRATING, CRUMBLING. | 101 W MADISON ST | PERIODIC | FAILED | View |
REPAIR DOOR HARDWARE | 21RST FLOOR HALL DOOR BEFORE STAIR DOOR WITH BROKEN HANDLE AND MISSING LATCH 6TH FLOOR HALL DOOR BEFORE STAIRWELL- BROKEN HANDLE AND NO LATCH. | 101 W MADISON ST | PERIODIC | FAILED | View |
REPAIR DOOR, INT. | 21RST FLOOR STAIR DOOR RUBS FRAME. STAIR DOOR AT 7 RUBS FRAME, DIFFICULT TO OPEN. 3RD FLOOR STAIR DOOR DIFFICULT TO OPEN, RUBS FRAME. | 101 W MADISON ST | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | 5TH FLOOR STAIRWELL DOOR - NO CLOSER. | 101 W MADISON ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR REQ, RESDNTL | SUITE 2100- EXPIRED FIRE EXTINGUISHER IN KITCHEN AREA. | 101 W MADISON ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | INTERIOR STAIRS- EVERY FLOOR WITH SECTION OF WALL CUT OPEN FOR ACCESS. WATER DAMAGE, FLAKING PAINT AT 24 AND AT ROOF LEVEL. BOILER ROOM CLAY TILE FIRE WALL DISINTEGRATING, CRUMBLING. | 101 W MADISON ST | PERIODIC | PASSED | View |
REPAIR DOOR HARDWARE | 21RST FLOOR HALL DOOR BEFORE STAIR DOOR WITH BROKEN HANDLE AND MISSING LATCH 6TH FLOOR HALL DOOR BEFORE STAIRWELL- BROKEN HANDLE AND NO LATCH. | 101 W MADISON ST | PERIODIC | PASSED | View |
REPAIR DOOR, INT. | 21RST FLOOR STAIR DOOR RUBS FRAME. STAIR DOOR AT 7 RUBS FRAME, DIFFICULT TO OPEN. 3RD FLOOR STAIR DOOR DIFFICULT TO OPEN, RUBS FRAME. | 101 W MADISON ST | PERIODIC | PASSED | View |
CLASS B DOOR IN STAIRWELL | 5TH FLOOR STAIRWELL DOOR - NO CLOSER. | 101 W MADISON ST | PERIODIC | PASSED | View |
FIRE EXTNGSHR REQ, RESDNTL | SUITE 2100- EXPIRED FIRE EXTINGUISHER IN KITCHEN AREA. | 101 W MADISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 101 W MADISON ST | PERIODIC | PASSED | View | |
FIRE BOX BRICKWORK | ON #1 TITUS FIX BRICK WORK IN FIRE BOX. | 101 W MADISON ST | PERIODIC | PASSED | View |
OWNER OR LICENSED CONTRACTOR | 101 W MADISON ST | PERIODIC | CLOSED | View | |
FIRE BOX BRICKWORK | #1 TITUS - REPAIR OR REPLACE DEFECTIVE BRICK WORK IN BOILER FIRE BOX. | 101 W MADISON ST | PERIODIC | CLOSED | View |
OBTAIN REFRIGERATION PERMIT | 101 W MADISON ST | PERIODIC | FAILED | View | |
REPLACE | ON #2 TITUS REPLACE SAFETIES. | 101 W MADISON ST | PERIODIC | PASSED | View |
MAINTAIN EXIT SIGN ILLUMINATED | SUITE 2100, 19TH, 18TH AND 7TH FLR- EXIT SIGNS NOT ILLUMINATED. | 101 W MADISON ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | BASEMENT AT WEST EXIT- FIRE EXTINGUISHER MISSING TAG. | 101 W MADISON ST | PERIODIC | FAILED | View |
SEE INSPECTOR COMMENTS | #1 TITUS - REPAIR FLOOR OR BASE OF BOILER.. | 101 W MADISON ST | PERIODIC | CLOSED | View |
SUBMIT 2 COPIES CRITICAL EXAM | SUBMIT EXTERIOR WALL CITICAL EXAM REPORT. LAST REPORT SUBMITTED 2014. SUBMIT TO DEPARTMENT OF BUILDINGS, ATTN: ALLISON SULLIVAN 2045 W. WASHINGTON BLVD. CHICAGO, IL 60612. | 101 W MADISON ST | PERIODIC | FAILED | View |
PROVIDE | WEST ELEVATION FIRE ESCAPE - OROVIDE PER CODE SECTION 13-96-820, 13-96-830, 13-96-840, 13-96-850, 13-96-870, 100% HANDS-ON CRITICAL EXAM OF FIRE ESCAPE. SUBMIT TO: DEPARTMENT OF BUILDINGS, ATTN: CODE COMPLIANCE GROUP, 2045 W. WASHINGTON BLVD. CHICAGO, IL 60612. | 101 W MADISON ST | PERIODIC | FAILED | View |
MAINTAIN EXIT SIGN ILLUMINATED | 24TH FLOOR - MISSING FIRE ESCAPE EXIT SIGN AT EXIT DOOR. STAIRWELL EXIT SIGN OUT OF SERVICE. MOST FIRE ESCAPE VESTIBLUE AREAS, FIRE ESCAPE SIGN OUT OF SERVICE. 13TH FLOOR EXIT SIGN OUT OF SERVICE. | 101 W MADISON ST | PERIODIC | FAILED | View |
DEBRIS, EXCESSIVE | 24TH FLOOR CORRIDOR - LARGE AMOUNTS OF JUNK AND DEBRIS 6TH FLOOR OFFICE STORAGE ROOM - ROOM EXCESSSIVLY FILLED WITH BOXES OF PAPER DOCUMENTS - FIRE HAZARD. | 101 W MADISON ST | PERIODIC | FAILED | View |
2-HR STAIR ENCLOSURE, 4+ STORY | 25TH FLOOR, ELEVATOR PENTHOUSE FLOOR - TOP OF EAST STAIR, MISSING DRYWALL ON INTERIOR SIDE OF WALL. MISSING PROPER FIRE RATED ASSEMBLY AND ENCLOSURE.ALL FLOORS INTEROR EAST STAIR - MULTIPLE HOLES IN FIRE RATED WALLS, PIPE PENETRATIONS MISSING FIRE SEAL MATERIALS. BASEMENT WEST STAIR - PIPE PENETRATIONS IN WALLS MISSING FIRE SEAL MATERIALS. | 101 W MADISON ST | PERIODIC | FAILED | View |
CLASS B DOOR IN STAIRWELL | 24TH FLOOR STAIR DOOR - FIRE RATED DOOR DOES NOT PROPERLY CLOSE AND LATCH SHUT. 10TH FLOOR INTERIOR STAIR - WOOD PIPE CHASE ACCESS PANEL NOT PROPERLY FIRE RATED. 14TH FLOOR STAIR DOOR - WOOD APPLIED TO INTERIOR SIDE OF FIRE RATED DOOR. DOOR FIRE RATING COMPERMISED. BASEMENT EAST STAIR - LANDING WALL MISSING FIRE RATED PANEL - PIPE ACCESS TO BASEMENT RESTAURANT. | 101 W MADISON ST | PERIODIC | FAILED | View |
PROVIDE | 23RD FLOOR STAIR DOOR IS LOCKED AND MISSING DOOR KNOB. PREVENTING ACCESS. PROVIDE PER CODE SECTION 13-196-084 DOOR LOCKING HARDWARE MUST MEET STAIRWELL RE-ENTRY ORDINANCE. STAIRWELL DOOR LOCKED AND REQUIRES KEY FOR RE-ENTRY ONTO FLOORS, NO FAIL-SAFE DOOR UNLOCKING SYSTEM INSTALLED. | 101 W MADISON ST | PERIODIC | FAILED | View |
ILLUMINATE PUBLIC STAIR/HALL | 22ND FLOOR CORRIDOR - EMERGENCY LIGHT OUT OF SERVICE. | 101 W MADISON ST | PERIODIC | FAILED | View |
PROVIDE | PROVIDE PER CODE SECTION, 15-16-971, IDENTIFICATION OF HOE VALVES - 2ND FLOOR, 5TH FLOOR, 21ST FLOOR AND MULTIPLE OTHER FLOORS - FIRE HOSE LOCATED INSIDE A RESTROOM LAVATORY OR CLOSET WITHOUT PROPER IDENTIFICATION OF HOSE VALVE. | 101 W MADISON ST | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 2ND FLOOR, 20TH FLOOR, 21ST FLOOR AND MOST OTHER FLOORS - WEST FIRE ESCAPE VESTIBULES AREAS LEADING FROM MAIN CORRIDOR TO FIRE ESCAPE DOOR ARE FILLED WITH JUNK, DEBRIS, CONSTRUCTION MATERIALS, OBSTRUCTING EGRESS AND CLEAR ACCESS TO FIRE ESCAPE DOOR. DANGEROUS AND HAZARDOUS.15TH FLOOR STAIR DOOR DOES NOT OPEN - DOOR STUCK SHUT. DANGEROUS AND HAZARDOUS. | 101 W MADISON ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR DOOR | WEST ELEVATION, FLOORS 11, 14, 13, 17, 20 AND MULTIPLE OTHER FLOORS - EXTERIOR FIRE ESCAPE FIRE RATED DOORS HAVE BROKEN OR MISSING DOOR CLOSERS. SOME DOORS RUB AND ARE VERY DIFFICULT TO OPEN. | 101 W MADISON ST | PERIODIC | FAILED | View |
NO KEY TO USE EXIT DOOR | 15TH FLOOR, FIRE ESCAPE ACCESS DOOR FROM CORRIDOR LOCKED AND REQUIRES A KEY TO ACCESS FIRE ESCAPE. DANGEROUS AND HAZARDOUS. | 101 W MADISON ST | PERIODIC | FAILED | View |
PROVIDE | WEST ELEVATION, PROVIDE PER CODE SECTION 15-8-110(B) PROTECTION OF OPENINGS. 15TH FLOOR OFFICE WINDOWS AT FIRE ESCAPE REPLACE WITH NON- FIRE RATED WINDOWS. EXTERIOR WALL AT FIRE ESCAPE MISSING PROPER FIRE PROTECTION. | 101 W MADISON ST | PERIODIC | FAILED | View |