Chicago Building Violations Data: 60 Violations
Violation Inspector Comments Address Category Status View
OPEN TYPE VIOLATION REPLACE HOIST CABLES ELEVATOR #6, REPLACE COMPENSATION CABLES ELEVATOR #6, PROVIDE CABLE GUARD (CAR AND COUNTER WEIGHT) AND FALL PROTECTION ON SECONDARY DECKS, PROVIDE ESCUSSIONS ON ALL HOISTWAY DOORS, PROVIDE BRAILLE PLATES ON ALL HOISTWAY DOOR JAMBS, PROVIDE LADDERS IN ELEVATOR PITS FOR SAFE AND CONVIENT ACCESS, PROPERLY PIPE LOAD SIDE FEEDERS TO ELEVATOR CONTROLLERS AND 110V DISCONNECTS, PROVIDE WORK PLATFORMS IN PITS, DO NOT USE ELEVATOR #7 UNTIL RE-INSPECTION HAS BEEN PERFORM. (18-30-010,13-20-120) 100121513 77 W WASHINGTON ST PERMIT FAILED View
OPEN TYPE VIOLATION REPLACE HOIST CABLES ELEVATOR #6, REPLACE COMPENSATION CABLES ELEVATOR #6, PROVIDE CABLE GUARD (CAR AND COUNTER WEIGHT) AND FALL PROTECTION ON SECONDARY DECKS, PROVIDE ESCUSSIONS ON ALL HOISTWAY DOORS, PROVIDE BRAILLE PLATES ON ALL HOISTWAY DOOR JAMBS, PROVIDE LADDERS IN ELEVATOR PITS FOR SAFE AND CONVIENT ACCESS, PROPERLY PIPE LOAD SIDE FEEDERS TO ELEVATOR CONTROLLERS AND 110V DISCONNECTS, PROVIDE WORK PLATFORMS IN PITS, DO NOT USE ELEVATOR #7 UNTIL RE-INSPECTION HAS BEEN PERFORM. 77 W WASHINGTON ST PERMIT PASSED View
PROVIDE PROVIDE DOCUMENTATION OF FIRE RETARDANT OF THEATRE CURTAINS SEC. (15-12-060; 15-12-340) 77 W WASHINGTON ST PERIODIC PASSED View
OPEN TYPE VIOLATION PROPERLY MOUNT ELEVATOR DISCONNECTS (PLUMB, LEVEL, AND SQUARE) LINE AND 110V. 18-27-620 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PROPERLY SECURE DISCONNECT (THROUGH BOLT-NO "TECH" SCREWS) 18-27-620 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PROVIDE GROUNDS IN ALL ELEVATOR ELECTRICAL FEEDS (DISCONNECTS) 18-27-620 77 W WASHINGTON ST PERMIT PASSED View
ENCLOSE MACH/RM 2 HR FIRE PATCH AND PAINT ELEVATOR MACHINE ROOM. MAINTAIN 2 HR. FIRE RATING. RULE 100 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PROVIDE FALL PROTECTION AND SAFE ACCESS (LADDERS) TO SECONDARY DECKS. RULE 100.3 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING INSTALL ALL ELECTRICAL BOX COVERS AND DUCT COVERS ALL ELEVATORS. 18-27-620 77 W WASHINGTON ST PERMIT PASSED View
ENCLOSE MACH/RM 2 HR FIRE PATCH ELEVATOR HOISTWAYS MAINTAIN 2HR FIRE RATING. RULE 101 77 W WASHINGTON ST PERMIT PASSED View
PROVIDE ACCESS TO PIT PROVIDE SAFE PIT ACCESS (LADDERS) ELEVATOR #6, #7, AND #8 RULE 106.1D 77 W WASHINGTON ST PERMIT PASSED View
REP/REPL FIRE RECALL PASS PROVIDE LOBBY PANEL RULE 211.10 77 W WASHINGTON ST PERMIT PASSED View
REP/REPL DEF ALARM BELL PASS PROVIDE PERMANENT PHONE LINES RULE 211.1 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION ELIMINATE FLEXIBLE CONDUIT (GREEN FIELD) RUNS LONGER THAN 36" IN MACHINE ROOM. 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PROVIDE HANDRAILS IN ALL ELEVATOR CABS. 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION UPON COMPLIANCE OF ALL ABOVE VIOLATIONS CONTACT THE CITY OF CHICAGO ELEVATOR BUREAU AT (312)743-7305 TO SCHEDULE RE-INSPECTION AND FIRE SERVICE/SMOKE/FROM RECALL TEST. 18-30-010,13-20-120 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION ELEVATOR #3 NOT TO BE INSERVICE FOR PUBLIC USE. 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING PROPERLY INSTALL ELEVATOR ELECTRICAL DISCONNECTS, PLUMB LEVEL 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING PROPERLY SECURE ELEVATOR DISCONNECT ON ELEVATOR #4 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING RELOCATE ELEVATOR #5 DISCONNECT AS DISCUSSED. 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING 110V. DISCONNECTS REQUIRE GROUNDING 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING FLEXIBLE CONDUITS IE. GREEN FIELD MAY BE NO LONGER THAN 36" INCHES LONG. 77 W WASHINGTON ST PERMIT PASSED View
INST PROP RACEWAYS FOR WIRING INSTALL ELECTRICAL DEVICES IN A WORKMAN LIKE MANNER. 77 W WASHINGTON ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CODE COMPLIANT PIT ACCESS TO ELEVATORS 6, 7 & 8. 77 W WASHINGTON ST COMPLAINT FAILED View
OPEN TYPE VIOLATION FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 01/29/10. STICKER LEFT ON DOOR. NO ONE CONTACTED DEPARTMENT OF BUILDINGS TO ALLOW ACCESS. TO ARRANGE INSPECTION OF PREMISES PLEASE CALL (312) 743 - 3538. 77 W WASHINGTON ST PERIODIC PASSED View
OPEN TYPE VIOLATION FAILURE TO PERMIT ACCESS FOR ANNUAL INSPECTION 13-20-020. ATTEMPTED INSPECTION 7/29/13. STICKER LEFT ON DOOR. NO ONE CONTACTED DEPT.OF BUILDINGS TO ALLOW ACCESS. TO ARRANGE INSPECTION PLEASE CALL 312-743-3610 77 W WASHINGTON ST PERIODIC PASSED View
SELF-CLOSE CLASS B FIRE DOOR THE FOLLOWING DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED.1) 22ND FLOOR MECHANICAL VESTIBULE INTO LOBBY2) 23RD FLOOR MECHANICAL ROOM TO ROOFTOP3) COMPARTMENTATION DOORS (PAIR OF 'B' DOORS) NOT LATCHING PROPERLY IN BASEMENT. TYPICAL OF TWO LOCATIONS.SELF CLOSING 1-1/2HR CLASS B FIRE DOOR REQUIRED IN THE FOLLOWING LOCATIONS. EXISTING DOORS ARE MISSING SELF CLOSING DEVICE OR FIRE RATED INFORMATION LABEL OR A COMBINATION OF BOTH. IN ADDITION, VARIOUS DOORS ARE EQUIPPED WITH VENTILATION GRILLES NOT EQUIPPED WITH A FUSIBLE LINK.1) ALL MECHANICAL ROOMS ON ALL FLOORS2) ALL ELECTRICAL CLOSETS / RISER ROOMS ON ALL FLOORS AND THOSE LOCATED WITHIN STAIR ENCLOSURE.3) SHAFT ACCESS PANELS IN NORTH STAIR THROUGHOUT BUILDING.4) ELEVATOR MACHINE ROOM 77 W WASHINGTON ST COMPLAINT FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY PENETRATIONS MUST BE SEALED WITH A APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS:1)NORTH STAIR AT 22ND FLOOR AND PENTHOUSE LEVELS A + B.2) THROUGHOUT SOUTH STAIR AT LOCATIONS OF HORIZONTAL PENETRATION THROUGH RATED ENCLOSURE. 77 W WASHINGTON ST COMPLAINT FAILED View
PIPE OPENING W/NONCOMBUST MATL PENETRATIONS MUST BE SEALED WITH A APPROVED UNDERWRITERS LABORATORIES RATED ASSEMBLY IN THE FOLLOWING LOCATIONS. SOME EXISTING PENETRATIONS HAVE BEEN IN FILLED WITH FIREBLOCK FOAM WHICH ARE NOT APPROVED FOR THIS CONSTRUCTION TYPE AND WILL BURN IN THE EVENT OF FIRE.1) ALL MECHANICAL ROOMS THROUGHOUT ENTIRE BUILDING2) ALL ELECTRICAL CLOSETS / RISER ROOMS THROUGHOUT ALL FLOORS INCLUDING ELECTRICAL RISER CLOSETS IN SOUTH STAIR ENCLOSURE AND ELECTRICAL CLOSET AT SOUTH VESTIBULE OF 1ST FLOOR SANCTUARY SPACE.3) MAIN SANCTUARY ATTIC SPACE.4) THROUGHOUT BASEMENT MECHANICAL ROOMS, BOILER ROOM, ELECTRICAL ROOMS.5) ELEVATOR MACHINE ROOM 77 W WASHINGTON ST COMPLAINT FAILED View
RESTORE EXIT AND EM EMERGENCY LIGHTING NOT WORKING WHEN TESTED AT THE FOLLOWING LOCATIONS:1) 22ND FLOOR MECHANICAL ROOM2) 22ND FLOOR SOUTH STAIR3) 13TH FLOOR NORTH STAIR4) 9TH FLOOR SOUTH STAIR5) THROUGHOUT BASEMENT PIERCE THEATER6) ADJACENT TO PIERCE CLASSROOMS 1 & 3. 77 W WASHINGTON ST COMPLAINT FAILED View
MAINTAIN EXIT SIGN ILLUMINATED EXIT SIGN NOT ILLUMINATED AT THE FOLLOWING LOCATIONS:1) 22ND FLOOR MECHANICAL ROOM2) AT ROOFTOP ADJACENT TO 23RD FLOOR MECHANICAL ROOM3) 23RD FLOOR MECHANICAL ROOM AT STAIR4) AT PENTHOUSE STAIRS C, E & F. 77 W WASHINGTON ST COMPLAINT FAILED View
INSTALL SMOKE DETECTORS 1) INSTALL SMOKE DETECTOR AT TOP MOST PART OF BOTH NORTH AND SOUTH STAIR. INSTALL IN CONJUNCTION WITH HIGH RISE FIRE ALARM SYSTEM. 2) PROVIDE ADDITIONAL BATTERY OPERATED SMOKE DETECTOR IN ALL SUITES CONTAINING A MICROWAVE IN BREAK ROOM. INSTALL AT LEAST 4 INCHES FROM THE WALL, 4 TO 12 INCHES FROM THE CEILING. 77 W WASHINGTON ST COMPLAINT FAILED View
CARB MONOX DETECT IN ASSEMBLY PROVIDE CARBON MONOXIDE DETECTOR ADJACENT TO GAS FIRED EQUIPMENT IN THE BASEMENT BOILER ROOM. 77 W WASHINGTON ST COMPLAINT FAILED View
DEBRIS, EXCESSIVE REMOVE EXCESSIVE STORAGE AT THE FOLLOWING LOCATIONS:1) 22ND FLOOR MECHANICAL ROOM2) 23RD FLOOR MEHCANICAL ROOM3) 2ND FLOOR NORTH STAIR ELECTRICAL RISER CLOSET. 77 W WASHINGTON ST COMPLAINT FAILED View
CLASS B DOOR IN STAIRWELL FIRE RESISTANCE RATING OF THE FOLLOWING DOORS COULD NOT BE VERIFIED DUE TO MISSING DOOR RATING LABEL.1) SOUTH STAIR AT ROOFTOPTHE FOLLOWING DOORS ARE NOT LATCHING PROPERLY, REPAIR AS REQUIRED.1) NORTH STAIR - 18TH, 17TH, 15TH, 11TH, 10TH AND 7TH FLOORS2) SOUTH STAIR - 14TH, 13TH, 9TH, 7TH, 4TH, AND 3RD FLOOR. 3RD FLOOR DOOR PROPPED OPEN. 77 W WASHINGTON ST COMPLAINT FAILED View
1HR PUB.CORIDR NON-RES/SPRNKLD PUBLIC CORRIDOR FIRE RESISTANCE IS COMPROMISED IN THE FOLLOWING LOCATIONS:1) ALL ELECTRICAL CLOSETS AND MECHANICAL ROOMS ON ALL FLOORS. PIPE BREACHES INTO PUBLIC CORRIDOR WALL WERE OBSERVED IN THE AFOREMENTIONED ROOMS. 77 W WASHINGTON ST COMPLAINT FAILED View
EXPOSED WIRING PROPERLY SECURE EXPOSED WIRING AT THE FOLLOWING LOCATIONS:1) THROUGHOUT ALL ELECTRICAL CLOSETS AND MECHANICAL ROOMS.2) THROUGHOUT BASEMENT3) ELEVATOR MACHINE ROOM 77 W WASHINGTON ST COMPLAINT FAILED View
COVER OUTLETS AND JBS FURNISH / INSTALL JUNCTION BOX COVERS WHERE MISSING AT THE FOLLOWING LOCATIONS:1) THROUGHOUT ALL ELECTRICAL CLOSETS AND MECHANICAL ROOMS.2) THROUGHOUT BASEMENT3) ELEVATOR MACHINE ROOM 77 W WASHINGTON ST COMPLAINT FAILED View
CLOSE BOX OPENINGS FURNISH / INSTALL COVER ON OPEN ELECTRICAL EQUIPMENT IN THE FOLLOWING LOCATIONS:1) ALL ELECTRICAL ROOMS & CLOSETS ON ALL FLOORS. OPEN EQUIPMENT PANELS EXIST THROUGHOUT BUILDING. 77 W WASHINGTON ST COMPLAINT FAILED View
PROVIDE 1) ANY COMBUSTIBLE PAINTS/OILS/VARNISHES/ETC. IN 22ND & 23RD FLOOR MECHANICAL ROOMS AND THROUGHOUT BASEMENT SHALL BE STORED IN FIREPROOF CABINET PER 15-28-970.2)SOUTH STAIR DOES NOT ALLOW RE-ENTRY INTO 9TH AND 20TH FLOOR DUE TO SINGLE TENANT SECURITY CONCERNS, PROVIDE RE-ENTRY PER 13-196-084 77 W WASHINGTON ST COMPLAINT FAILED View
REPAIR EXTERIOR DOOR EXTERIOR DOOR TO ROOFTOP AT 23RD FLOOR MECHANICAL ROOM CONSISTS OF A LOOSELY MOUNTED MAKESHIFT WOOD DOOR. 77 W WASHINGTON ST COMPLAINT FAILED View
REPAIR INTERIOR WALLS/CEILING REPAIR PLASTER CEILING AS REQUIRED AT 22ND FLOOR MECHANICAL ROOM, EXISTING CEILING ABOVE ENTRY DOOR HAS 6 S.F. SECTION MISSING. 77 W WASHINGTON ST COMPLAINT FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY STAIR ENCLOSURE TERMINATES AT 3RD FLOOR. LOBBY STAIR IS OPEN FROM 2ND FLOOR TO LOBBY. 2HR SEPARATION REQUIRED. 77 W WASHINGTON ST COMPLAINT FAILED View
PROVIDE FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) 77 W WASHINGTON ST COMPLAINT FAILED View
POST APPROVED OCCUPANCY CARD OCCUPANCY CAPACITY CARDS REQUIRED AT 1ST FLOOR SANCTUARY, 2ND FLOOR HAL AND SKY CHAPEL. 77 W WASHINGTON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED ILLUMINATE ALL EXIT SIGNS 77 W WASHINGTON ST PERIODIC FAILED View
FIRE EXTNGSHR RECHARGE & TAG RETAG FIRE EXTINGUISHERS 77 W WASHINGTON ST PERIODIC FAILED View
MAINTAIN EXIT SIGN ILLUMINATED ILLUMINATE ALL EXIT SIGNS 77 W WASHINGTON ST PERIODIC CLOSED View
ARRANGE COMPLETED PERMIT INSP. 18-28-106.1 INSPECTION REQUIRED 13-32-270 WARM AIR FURNACE * ARRANGE FOR COMPLETE PERMIT INSPECTIONS AND OBTAIN 77 W WASHINGTON ST COMPLAINT FAILED View
PROVIDE PROVIDE 4(5-270) IT SHALL BE THE DUTY OF ANY PERSON OWNING OR CONTROLLING THE HEATING PLANT WHICH FURNISHES HEAT TO ANY OFFICE,STORE OR OTHER PLACE OF EMPLOYMENT TO MAINTAIN A TEMPERATURE THEREIN OF NOT LESS THAN 68 DEGREE'S FARENHEIT WITHOUT SUCH UNDUE RESTRICTION OF VENTILATION AND TO INTERFERENCE WITH PROPER SANITARY CONDITIONS THEREIN BETWEEN THE HOURS OF 8:00AM AND 6:00PM FROM OCT 1 OF EACH YEAR TO JUNE 1ST OF THE SUCCEEDING YRS SUNDAYS AND FULL HOLIDAYS LEGAL HOLIDAYS EXCEPTED 77 W WASHINGTON ST COMPLAINT FAILED View
FIRE EXTNGSHR RECHARGE & TAG RETAG ALL FIRE EXTINGUISHERS 77 W WASHINGTON ST PERIODIC CLOSED View
REPL/DEF COMP ROPES PASS REPLACE COMPENSATION ROPES ON ELEVATOR #4. 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION RELOCATE DISCONNECT FOR #5 ELEVATOR 18-27-620 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION REMOVE RECEPITICLE (110V) SUSPENDED IN CENTER OF MACHINE ROOM. 18-27 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION PROVIDE WORK PLATFORMS IN PIT RULE 106.1D 77 W WASHINGTON ST PERMIT PASSED View
OPEN TYPE VIOLATION 77 W WASHINGTON ST PERIODIC PASSED View
I-A I-B I-C AND II FIRE RESIST MAKESHIFT STORAGE AREA HAVE BEEN CONSTRUCTED WITH COMBUSTIBLE MATERIALS IN 22ND AND 23RD FLOOR MECHANICAL ROOMS. 77 W WASHINGTON ST COMPLAINT FAILED View
MAINTAIN MECH. VENT SYSTEM OUTSIDE AIR INTAKE GRILLES ARE PROPPED OPEN WITH 2X4'S, TYPICAL IN MECHANICAL ROOMS ON EACH FLOOR. 77 W WASHINGTON ST COMPLAINT FAILED View
REPLCE WINDOW PANES, PLEXGLAS REPLACE BROKEN GLAZING IN ELEVATOR MACHINE ROOM. 77 W WASHINGTON ST COMPLAINT FAILED View
ENCLSE FLOOR OPENINGS W/IHR FR ENCLOSE PIPE SHAFTS IN MECHANICAL & ELECTRICAL ROOMS/CLOSETS ON ALL FLOORS WITH MATERIALS HAVING A FIRE RESISTANCE OF NOT LESS THAN ONE HOUR. 77 W WASHINGTON ST COMPLAINT FAILED View