SUBMIT PLANS FOR PLUMBING PRMT | 18-29-106.1 RENOVATION WORK EXCEEDS PERMIT # 100586306 | 1529 N WELLS ST | COMPLAINT | FAILED | View |
POST OWNER/MANAGERS NAME/# | BUILDING - NO OWNER'S ID SIGN POSTED. | 1529 N WELLS ST | PERIODIC | FAILED | View |
CHIMNEY CAPPING | NORTH ELEVATION, CHIMNEY CAPPING - MISSING. | 1529 N WELLS ST | PERIODIC | FAILED | View |
REPAIR WINDOW SILLS | WEST ELEVATION, WINDOW SILLS - OPEN MORTAR JOINTS, SOME CRACKED. | 1529 N WELLS ST | PERIODIC | FAILED | View |
REPAIR EXTERIOR WALL | WEST ELEVATION, EXTERIOR WALL - OPEN MORTAR JOINTS IN BRICK UNDER WINDOWS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
FIRE EXTNGSHR RECHARGE & TAG | 1ST FLOOR RESTAURANT AND BASEMENT STORAGE - FIRE EXTINGUISHER RECHARGE TAGS EXPIRED.NORTH INTERIOR STAIR - FIRE EXTINGUISHER RECHARGE TAGS EXPIRED. | 1529 N WELLS ST | PERIODIC | FAILED | View |
INSTALL SMOKE DETECTORS | NORTH INTERIOR STAIRWELL - MISSING SMOKE DETECTOR AT TOP OF STAIRWELL. | 1529 N WELLS ST | PERIODIC | FAILED | View |
REPAIR BALCONY | EAST EXTERIOR BALCONY SYSTEM AT 3RD FLOOR - COLUMNS AND BEAMS ROTTEN AND SCABBED. BEAMS SAGGING. COLUMN SPLICE BUTT JOINT AND TOE NAILED ONLY. PLANS AND PERMIT REQUIRED FOR REPAIRS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
REPAIR INTERIOR STAIR SYSTEM | MULTIPLE FLOORS, NORTH INTERIOR STAIR STRINGERS AND LANDINGS NOT LEVEL. FLOOR TREADS SAG. PLANS AND PERMIT REQUIRED FOR REPAIRS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
REPAIR INTERIOR WALLS/CEILING | NORTH INTERIOR STAIR - MULTIPLE LOCATIONS, WATER DAMAGE TO CEILING AND WALLS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
1HR PUB.CORRIDOR IN MULT. D.U. | NORTH AND EAST INTERIOR RESIDENTIAL STAIRWELLS - MISSING PROPER FIRE SEPARATION BETWEEN RESIDENTIAL PORTION OF STAIRWELL AND 1ST FLOOR RESTAURANT MERCANTILE AND THEATER ASSEMBLY. BLACK IRON FROM RESTAURANT INSIDE NORTH RESIDENTIAL STAIRWELL. PLANS AND PERMIT REQUIRED FOR REPAIRS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
UNDERSIDE STAIR 1HR FIRE RES | NORTH INTERIOR AND EAST INTERIOR STAIRWELLS - MISSING PROPER FIRE PROTECTION TO COMBUSTIBLE STAIR CONSTRUCTION. | 1529 N WELLS ST | PERIODIC | FAILED | View |
OBSTRUCTIONS IN EXIT WAY | 1ST FLOOR EAST THEATER EXIT AND EAST ENCLOSED PORCH SYSTEM FROM UPPER FLOORS - OBSTRUCTED BY STORAGE ITEMS, JUNK AND DEBRIS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
PLANS & PERMITS REQ - CONTRCTR | 1ST FLOOR THEATER ADDITON TO BUILDING ERECTED WITHOUT PERMITS. SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO 1ST FLOOR THEATER ADDTION, OR RESTORE TO THE SITE TO THE ORIGINAL STATE.NORTH INTERIOR STAIRWELL AND REAR ENCLOSED PORCH STAIR SYSTEM - NO PERMIT OBTAINED TO ENCLOSE STAIRWELLS. BOTH STAIRWELLS HAVE MULTIPLE AREAS OPEN WITH EXPOSED EXISTING NON-CONFORMING FRAMING AND CONSTRUCTION. PLANS AND PERMITS REQUIRED TO REBUILD AND REPAIR DEFICENT SECTIONS. | 1529 N WELLS ST | PERIODIC | FAILED | View |
EXPOSE FOR INSPECT APPROVAL | OPEN WALLS FOR ROUGH INSPECTION | 1529 N WELLS ST | COMPLAINT | FAILED | View |