Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | DISPLAY CORRECT CAPACITY IN CAB. CAR 1 | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERMANENTLY ID MACHINE ROOM. | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DISPLAY VOLTAGE & SOURCE FEED ON DISCONNECT SWITCHES. | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | DISPLAY CORRECT CAPACITY IN CAB. BOTH CARS | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-LOCATE PIT LADDER OR STOP SWITCH. CAR 2 | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PERFORM REQ'D. MECHANICAL TEST'S & SAFETY TEST WITH FINISHED CAB. CAR 1 | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR/COMPLETE THE TOUCHSCREEN WHEN MACHINE ROOM, HOISTWAY SMOKE ARE ACTIVATAED.2C | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST F.A.I.D.'S | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST EMERGENCY POWER OPERATION. | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | INSTALL CONTROLLER ROOM CEILING. | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | RE-LOCATE PIT LADDER OR STOP SWITCH. CAR 1 | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE LIGHTING IN OVERHEAD. CAR 1 | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REMOVE WATER PIPE FROM EQUIPMENT ROOM. | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE A FIRE SERVICE BOX WITH KEY FOR FIRE PANEL | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE THE FIRE SERVICE PANEL AND EMERGENCY EVAC.SIGNAGE AT LOBBY AND ALL LANDINGS | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | BEVEL THE SILLS AT THE 2ND FLOOR AND LOBBY | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | REPAIR/CORRECT THE TOUCHSCREEN WHEN MACHINE ROOM, HOISTWAY SMOKE ARE ACTIVATAED.2C | 215 N PEORIA ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEST CARD READER WHEN READY | 215 N PEORIA ST | PERMIT | PASSED | View |