Viewing Parcel Address (PIN)

More Information

The Open Source Data Files that are here are from Cook County.

This Page is a combination of all Files.

The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.

This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.

The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.

Viewing Parcel Address (PIN)


Last Modification Date: 2024-10-23 @ 8:06 PM
PIN: 14292040030000
Property Address: 941 W BELMONT AVE
City - Zip: CHICAGO - 60657
2023 Property Class:
2023 Township: -
2023 Neighborhood:
2023 Tax District:
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 15 Violations
Violation Inspector Comments Address Category Status View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE DEDICATED EMERGENCY PHONE LINE FOR ELEVATOR. CURRENTLY SHARED LINE. 941 W BELMONT AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE & EASY ACCESS ACROSS ROOF TO CONTROL SPACE. 941 W BELMONT AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PROTECTION FROM ELEMENTS FOR ROOF CONTROL SPACE. 941 W BELMONT AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE GUARD FOR PIT SPRINKLER HEAD. 941 W BELMONT AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE & TEST COMMUNICATION FAILURE. 941 W BELMONT AVE PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA TEMP USE OK UP TO 5TH FLOOR ONLY. 941 W BELMONT AVE PERMIT PASSED View
INADEQUATE HANGERS GAS PIPE ON ROOF IS RESTING ON ROTTED WOOD 2X4'S HANGER SPACING AND SUPPORTS ARE IMPROPER. HANGERS ROTTING, MISSING IMPROPERLY SPACED. 941 W BELMONT AVE PERIODIC FAILED View
UNUSED OPENINGS/VENT LINE EXPOSED OPENINGS ON ROOF GAS LINE. OPEN GAS LINES HAVE VALVES HOWEVER THEY ARE NOT TIED IN TO ANYTHING AND SHOULD BE CAPPED OR SEALED TO PREVENT GAS FROM BEING RELEASED. VALVES APPEAR TO POSSIBLY GO TO SPACE HEATERS OR FIREPLACES FOR ROOF DECK 941 W BELMONT AVE PERIODIC FAILED View
PROVIDE NATURAL GAS METER LOCKED OUT BY PEOPLES GAS AT TIME OF INSPECTION. ENTIRE 941 W. BELMONT BUILDING DID NOT HAVE NATURAL GAS. 311 COMPLIANTS VERIFIED FOR NO HOT WATER, NO COOKING GAS, NO GAS FOR FURNACE TO HEAT UNITS AND BUILDING, NO GAS FOR LAUNDRY, BOILER WAS OUT OF SERVICE AT TIME OF INSPECTION. TEMP IN UNITS RANGED FROM 62 DEGREES - 65. DOMESTIC HOT WATER TEMPS FROM 59-64. FURNACES IN UNITS OUT OF SERVICE NO GAS SUPPLY. ALL VIOLATIONS VERIFIED BY INSPECTOR #070 AND RESULTED IN OTHER VIOLATIONS FOUND 941 W BELMONT AVE PERIODIC FAILED View
ARRANGE FOR RE-INSPECTION ARRANGE FOR INSPECTION ONCE ALL VIOLATIONS ARE FIX/REPAIRED 941 W BELMONT AVE PERIODIC FAILED View
REPAIR OR REPLACE REPAIR AND REPLACE GAS PIPE ON ROOF THAT IS RUSTED, REPLACE GAS HANGERS ON ROOF WITH PROPER SUPPORTS, CAP OR PLUG ALL OPEN UN-USED VALVE OPENINGS ON ROOF GAS PIPE, PAINT GAS PIPE ON ROOF YELLOW WITH TWO LAYERS OF RUST FREE PAINT. ONCE ALL PERMITS AND VIOLATIONS CORRECTED COMPLETED ARRANGE FOR INSPECTION TO CORRECT BUILDING VIOLATIONS 941 W BELMONT AVE PERIODIC FAILED View
RUSTED PIPING GAS PIPE ON ROOF IS RUSTED/ NOT ALL OF IT IS PAINTED YELLOW. 941 W BELMONT AVE PERIODIC FAILED View
ARRANGE FOR INSPECTION CALL THE REFRIGERATION BUREAU AND ARRANGE FOR A SITE INSPECTION. (312)743-3562 941 W BELMONT AVE PERMIT PASSED View
FOLLOW PLANS/RESUBMIT REVISED 941 W BELMONT AVE PERMIT PASSED View
ARRANGE COMPLETED PERMIT INSP. 941 W BELMONT AVE PERMIT PASSED View