Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE DEDICATED EMERGENCY PHONE LINE FOR ELEVATOR. CURRENTLY SHARED LINE. | 941 W BELMONT AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE SAFE & EASY ACCESS ACROSS ROOF TO CONTROL SPACE. | 941 W BELMONT AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE PROTECTION FROM ELEMENTS FOR ROOF CONTROL SPACE. | 941 W BELMONT AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE GUARD FOR PIT SPRINKLER HEAD. | 941 W BELMONT AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | PROVIDE & TEST COMMUNICATION FAILURE. | 941 W BELMONT AVE | PERMIT | PASSED | View |
MAINTAIN OR REPAIR ELECT ELEVA | TEMP USE OK UP TO 5TH FLOOR ONLY. | 941 W BELMONT AVE | PERMIT | PASSED | View |
INADEQUATE HANGERS | GAS PIPE ON ROOF IS RESTING ON ROTTED WOOD 2X4'S HANGER SPACING AND SUPPORTS ARE IMPROPER. HANGERS ROTTING, MISSING IMPROPERLY SPACED. | 941 W BELMONT AVE | PERIODIC | FAILED | View |
UNUSED OPENINGS/VENT LINE | EXPOSED OPENINGS ON ROOF GAS LINE. OPEN GAS LINES HAVE VALVES HOWEVER THEY ARE NOT TIED IN TO ANYTHING AND SHOULD BE CAPPED OR SEALED TO PREVENT GAS FROM BEING RELEASED. VALVES APPEAR TO POSSIBLY GO TO SPACE HEATERS OR FIREPLACES FOR ROOF DECK | 941 W BELMONT AVE | PERIODIC | FAILED | View |
PROVIDE | NATURAL GAS METER LOCKED OUT BY PEOPLES GAS AT TIME OF INSPECTION. ENTIRE 941 W. BELMONT BUILDING DID NOT HAVE NATURAL GAS. 311 COMPLIANTS VERIFIED FOR NO HOT WATER, NO COOKING GAS, NO GAS FOR FURNACE TO HEAT UNITS AND BUILDING, NO GAS FOR LAUNDRY, BOILER WAS OUT OF SERVICE AT TIME OF INSPECTION. TEMP IN UNITS RANGED FROM 62 DEGREES - 65. DOMESTIC HOT WATER TEMPS FROM 59-64. FURNACES IN UNITS OUT OF SERVICE NO GAS SUPPLY. ALL VIOLATIONS VERIFIED BY INSPECTOR #070 AND RESULTED IN OTHER VIOLATIONS FOUND | 941 W BELMONT AVE | PERIODIC | FAILED | View |
ARRANGE FOR RE-INSPECTION | ARRANGE FOR INSPECTION ONCE ALL VIOLATIONS ARE FIX/REPAIRED | 941 W BELMONT AVE | PERIODIC | FAILED | View |
REPAIR OR REPLACE | REPAIR AND REPLACE GAS PIPE ON ROOF THAT IS RUSTED, REPLACE GAS HANGERS ON ROOF WITH PROPER SUPPORTS, CAP OR PLUG ALL OPEN UN-USED VALVE OPENINGS ON ROOF GAS PIPE, PAINT GAS PIPE ON ROOF YELLOW WITH TWO LAYERS OF RUST FREE PAINT. ONCE ALL PERMITS AND VIOLATIONS CORRECTED COMPLETED ARRANGE FOR INSPECTION TO CORRECT BUILDING VIOLATIONS | 941 W BELMONT AVE | PERIODIC | FAILED | View |
RUSTED PIPING | GAS PIPE ON ROOF IS RUSTED/ NOT ALL OF IT IS PAINTED YELLOW. | 941 W BELMONT AVE | PERIODIC | FAILED | View |
ARRANGE FOR INSPECTION | CALL THE REFRIGERATION BUREAU AND ARRANGE FOR A SITE INSPECTION. (312)743-3562 | 941 W BELMONT AVE | PERMIT | PASSED | View |
FOLLOW PLANS/RESUBMIT REVISED | 941 W BELMONT AVE | PERMIT | PASSED | View | |
ARRANGE COMPLETED PERMIT INSP. | 941 W BELMONT AVE | PERMIT | PASSED | View |