INSTALL EXIT SIGN | NON-WORKING EMERGENCY LIGHTS, 2ND FLOOR, EAST STAIRWAY | 5600 W ADDISON ST | PERIODIC | FAILED | View |
RESTORE EXIT AND EM | THIRD FLOOR EMERGENCY III LIGHTING NOT WORKING (EAST ELEVATION) | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL FAID'S AND SCHEDULE AND PERFORM FIREMAN'S RECALL TEST. | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | DISCONTINUE BLOCKING THE MACHINE ROOM WITH CHAIRS AND EXAMINATION TABLES | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE KEYED SWITCH ACCESS AT THE BOTTOM TERMINAL LANDING OF ELEVATOR "N" | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | THE MODERNIZATION HAS NOT BEEN COMPLETED, RED TAG #01493 APPLIED TO ELEVATOR#M. MODERNIZATION PERMIT #100926109 | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE HVAC IN THE MACHINE ROOM | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | COMPLETE UNFINISHED WORK OF THE OPEN MODERNIZATION PERMIT #100926109 | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE BUILDING GROUNDS TO THE DISCONNECTS 110 VAC & LINE VOLTAGE | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE LIGHTING IN THE MACHINE ROOM | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE CONVENIENCE GFCI OUTLETS IN THE MACHINE ROOM | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | IDENTIFY SOURCE PANEL ON THE DISCONNECTS | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A METAL SUMP HOLE COVER | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL FAID, SMOKE DETECTORS OR FLOW SWITCHES TO ACTIVATE PHASE I FIREMANS RECALL AND SCHEDULE TESTINGOF SUCH. ELEVATORS # "M" & "N" | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PATCH/CAULK THE PIPE CHASES AND HOLES IN THE HOISTWAYS AND PITS | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A SINGLE GANG NON-GFCI OUTLET IN THE PIT | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE GFCI CONVENIENCE OUTLETS IN THE PITS | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE LIGHTING IN THE PITS | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE HVAC IN THE MACHINE ROOM | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | ADJUST HOISTWAY DOOR LOCKS | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE ACCESS TO THE MACHINE ROOM | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE IN THE MACHINE ROOM; MAINTENANCE RECORDS, CATEGORY TESTING, FIRE SERVICE TESTING, MAINTENANCE CONTROL PROGRAM | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY 1 TESTING | 5600 W ADDISON ST | PERMIT | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PROVIDE A SINGLE GANG NON-GFCI OUTLET FOR SUMP PUMP | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | RE-PROGRAM THE EMERGENCY PHONE IN THE ELEVATORS CURRENTLY DIALING THE HOSPITAL ACROSS THE STREET | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PERFORM CATEGORY I TESTING | 5600 W ADDISON ST | PERIODIC | FAILED | View |
MAINTAIN OR REPAIR HYDRO ELEVA | PATCH AND SEAL PIPE CHASES FROM PIT TO MACHINE ROOM MAINTAIN 2 HOUR FIRE RATING | 5600 W ADDISON ST | PERIODIC | FAILED | View |