PIN: 17031010220000
Property Address: 1500 N LAKE SHORE DR
City - Zip: CHICAGO - 60610
2023 Property Class: 213
2023 Township: 74 - North Chicago
2023 Neighborhood: 74022
2023 Tax District: 74002
Cook Viewer GIS: External GIS Website
Chicago Building Violations Data: 91 Violations
Violation Inspector Comments Address Category Status View
SEND EX. METAL LETTER EXPOSED METAL LETTER 1500 N LAKE SHORE DR COMPLAINT CLOSED View
REPAIR EX. MET. ENGINEER REPORT 1500 N LAKE SHORE DR COMPLAINT CLOSED View
CONSTRUCTION GARAGE FLRS&RAMPS EAST GARAGE STAIRWAY DOORS ALL LEVELS PROPPED OPEN 1500 N LAKE SHORE DR PERIODIC FAILED View
REPAIR INTERIOR WALLS/CEILING EAST GARAGE STAIRWAY OPEN CONCRETE CEILING EXPOSED OPEN CONCRETE AND RUSTED REBAR 1ST TO 2ND FLOORS. 1500 N LAKE SHORE DR PERIODIC FAILED View
REPAIR/REBUILD GARAGE OR SHED BASEMENT GARAGE RUSTED REBAR SHOWING BY NORTH ENTRANCE. 1500 N LAKE SHORE DR PERIODIC FAILED View
OBSTRUCTIONS IN EXIT WAY 2ND AND 3RD BY EAST STAIRWAY OF GARAGE CARS BLOCKING EGRESS. 1500 N LAKE SHORE DR PERIODIC FAILED View
TWISTED COUNTERBALANCE TWISTED C/BAL 1500 N LAKE SHORE DR COMPLAINT PASSED View
STIFFENER PIPE F.E. REPAIR OR REPLACE STIFFENER PIPE (AND CU BOLT) 1500 N LAKE SHORE DR COMPLAINT PASSED View
PROTECT METAL MEMBERS PROTECT METAL MEMBERS 1500 N LAKE SHORE DR COMPLAINT PASSED View
REPAIR EX. MET. ENGINEER REPORT 1500 N LAKE SHORE DR COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY 1 TESTING ON ALL ELEVATORS AND SUBMIT TEST RESULTS TO ELEVATOR BUREAU 1500 N LAKE SHORE DR PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE FENCE BY COUNTERWEIGHT SIDE IN ELEVATOR S#3 MACHINE ROOM TO PREVENT INJURY 1500 N LAKE SHORE DR PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PULL THE PROPER PERMITS FOR ALL FIRE SERVICE UPGRADES ON ELEVATORS AND INSPECTION STATIONS BEING PUT ON TOP OF ELEVATORS 1500 N LAKE SHORE DR PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA ADD MORE LIGHTS TO GARAGE CAR MACHINE ROOM 1500 N LAKE SHORE DR PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA ADD FIRE SERVICE CHECK CHARTS AND MAINTENANCE CHECK LOGS TO ELEVATOR MACHINE ROOM 1500 N LAKE SHORE DR PERIODIC PASSED View
2-HR STAIR ENCLOSURE, 4+ STORY PER CODE SECTION 15-8-140.REMOVE ALL NON RATED ACCESS PANELS THROUGHOUT ENTIRE BUILDING THAT ARE IN STAIRWELLS.FIRE STOPPING IS TO BE COMPLETED PER APPROVED U.L. ASSEMBLY DOCUMENTATION. PROPERLY FIRE STOP ALL PENETRATIONS THROUGHOUT STAIRWELLS BUT NOT LIMITED TO: CONDUIT FROM ELECTRICAL PANEL IN STAIRWELL TO DWELLING UNITS, GAS PIPE IN STAIRWELL TO DWELLING UNITS (SOUTH TOWER). 1500 N LAKE SHORE DR PERIODIC PASSED View
CLASS B DOOR IN STAIRWELL PRE CODE SECTION 15-8-180 (EXISTING HIGH RISE BUILDINGS- 13-196-209)STAIRWELL DOORS MUST BE CLASS ¿B¿ FIRE RATED DOORS. RATED DOORS MUST BE SELF-CLOSING AND MUST HAVE A POSITIVE LATCH. DURING INSPECTION- NORTH AND SOUTH ELEVATOR MACHINE ROOM /NO LABEL /VENT IN DOORS, SOUTH TOWER-20A /NO LATCH, 7B /NO LATCH-MISSING STRIKE, 4B /NO CLOSER, 4B /NO CLOSER, 3B /NO LATCH, 1A TO LOBBY /NO CLOSER, NORTH STAIR TOWER "C"- 24C /NO LATCH, BETWEEN 24TH AND 23RD FLOOR TO ELEVATOR ROOM (2) TWO DOORS /NO LABEL /NO CLOSER /OPEN SCREEN VENT IN DOORS, 15C /NO ENTRY, 12C /NO LATCH /RUBS ON CARPER, 10C /NO LATCH, 3C /NO LATCH, GARAGE STAIR TOWER- 3RD. FLOOR /NO LATCH. 1500 N LAKE SHORE DR PERIODIC FAILED View
ARRANGE PREMISE INSPECTION PER CODE SECTION 13-12-100PROVIDE ACCESS TO ALL DWELLING UNIT ENTRY DOORS TO VERIFY THAT THEY SELF-CLOSE AND POSITIVE LATCH . UNABLE TO VERIFY FIRE ESCAPE DOORS IN DWELLING UNIT 16A AND 10C . 1500 N LAKE SHORE DR PERIODIC PASSED View
HOLDOPEN DEVICE ON APT DOOR PER CODE SECTION 15-8-240(A)(5) AND 13-196-170.REMOVE ALL DOOR HOLD OPEN DEVICES ON DOORS THROUGHOUT ENTIRE BUILDING. 1500 N LAKE SHORE DR PERIODIC PASSED View
PROVIDE PER CODE SECTION 10(13-160-640)(F) REMOVE EXHAUST VENT THROUGH FIRE RATED WINDOW ADJACENT TO FIRE ESCAPE DOOR OR PROVIDE PROPER FIRE DAMPER.NOTE: SOME TENANTS HAVE REMOVED THE FIRE RATED GLASS PANEL COMPLETELY AND INSTALLED EXHAUST VENT THRU WINDOW. OPENING 1500 N LAKE SHORE DR PERIODIC FAILED View
PROVIDE PER CODE SECTION 4(13-76-080)(F)TWO HOUR ENCLOSURE AT ELECTRICAL RISER ROOMS THROUGHOUT ENTIRE BUILDING. 1500 N LAKE SHORE DR PERIODIC PASSED View
I-A I-B I-C AND II FIRE RESIST PER CODE SECTION15-8-260(A) AND 13-60-020 REMOVE WOOD PARTITION WALLS CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL BUT NOT LIMITED TO: LEVEL ONE IN GARAGE /VALET SHED BUILT OUT OF PLYWOOD AND PLEXIGLAS WINDOWS, RUBBER TIRES BEING USED AS CAR BUMPERS ON WALL, LOWER LEVEL GARAGE /COMBUSTIBLE MATERIAL (WOOD) BEING STORED DURING INSPECTION, ELEVATOR MACHINE ROOM AT PENTHOUSE /WOOD STAIRS TO UPPER CRAWL SPACE /COMBUSTIBLE MATERIAL (WOOD) BEING STORED IN CRAWL SPACE DURING INSPECTION.(23RD ½ FLOOR) ELEVATOR ROOM-BETWEEN 24TH AND 23RD FLOOR OPENINGS THROUGH FIRE RATED WALLS INTO AREA THAT IS THE CEILING OF THE 23RD FLOOR DWELLING UNIT /COMBUSTIBLE MATERIAL (WOOD) BEING USED FOR PLANKING.NOTE: COMBUSTIBLE MATERIAL NOT ALLOWED IN CONSTRUCTION TYPE 1A, 1B, 1C, OR TYPE 2 NON- COMBUSTIBLE CONSTRUCTION OR FIRE RESISTIVE ASSEMBLIES. 1500 N LAKE SHORE DR PERIODIC FAILED View
PIPE OPENING W/NONCOMBUST MATL PER CODE SECTION 15-8-640. FIRE STOPPING IS TO BE COMPLETED PER APPROVED U.L. ASSEMBLY DOCUMENTATION. PROPERLY FIRE STOP ALL PENETRATIONS THROUGHOUT BUT NOT LIMITED TO: NORTH AND SOUTH ELEVATOR MACHINE ROOM, CRAWL SPACE ABOVE ELEVATOR MACHINE ROOMS, LEVEL ONE IN GARAGE TO VEHICLE ELEVATOR SHAFT, LOWER LEVEL GARAGE, BIKE ROOM, BOILER ROOM, LEVEL ONE /JANITORS CLOSET, (23RD ½ FLOOR) ELEVATOR ROOM-BETWEEN 24TH AND 23RD FLOOR /OPEN DUCT WORK / OPEN RISER PIPES /OPEN ELEVATOR SHAFT, /OPENINGS THROUGH FIRE RATED WALLS INTO AREA THAT IS THE CEILING OF THE 23RD FLOOR DWELLING UNIT /PENETRATION FROM DWELLING UNIT TO ELEVATOR ROOM. 1500 N LAKE SHORE DR PERIODIC FAILED View
ILLUMINATE PUBLIC STAIR/HALL PER CODE SECTION 13-196-080, 13-196-450, 13-160-660 AND 13-160-670.EMERGENCY LIGHTING NOT WORKING DURING INSPECTION AT BUT NOT LIMITED TO: 17TH. BC, 15TH. BC, 9TH. BC, 5TH. BC, 2ND. BC (N/S) STAIRWELL, OUTSIDE BOILER ROOM, SWITCH GEAR ROOM. 1500 N LAKE SHORE DR PERIODIC PASSED View
OBSTRUCTIONS IN EXIT WAY PRE CODE SECTION 13-160-640(D), 13-160-220(B), 13-160-070 AND 13-196-080.MAINTAIN ACQUIT MEANS OF EGRESS IN STAIRWELLS /TWO GARBAGE CANS-PER STAIRWELL LANDING JUST OUTSIDE REAR DWELLING UNIT DOOR REDUCING THE REQUIRED WIDTH OF EXIT WAY. NOTE: FIRE ESCAPE DOORS MUST BE FREE OF OBSTRUCTIONS THAT MAY HAMPER TRAVEL AND EVACUATION. EVERY FIRE ESCAPE DOOR SHALL BE KEPT CLEAR AND UNENCUMBERED AT ALL TIMES. DURING LSE INSPECTION THERE WERE FIRE ESCAPE DOORS WITH WASHER /DRYER /SLOP SINKS /HVAC UNITS /WINDOW BLINDS THAT ARE ATTACHED TO THE HEADER /SCREEN DOORS THAT SWING INTO THE DWELLING UNIT /SOLID WOOD PANEL DOORS THAT SWING INTO THE DWELLING UNIT. /BUILD IN KITCHEN CABINETS /BUILD IN RADIATOR BENCHES THAT HAMPER MEANS OF EGRESS. 1500 N LAKE SHORE DR PERIODIC PASSED View
REPAIR EXTERIOR DOOR PER CODE SECTION 15-8-110 AND 15-12-110.REPAIR EXTERIOR FIRE ESCAPE DOORS AND DOOR JAMS THAT ARE DETERIORATING, HAVE HOLES IN THEM, DO NOT SELF CLOSE AND POSITIVE LATCH. 1500 N LAKE SHORE DR PERIODIC PASSED View
CARB MONOX DETECT IN RESID PER CODE SECTION 13-64-190 AND 13-64-210CARBON MONOXIDE DETECTORS MISSING DURING INSPECTION INCLUDE BUT ARE NOT LIMITED TO; LOWER LEVEL LAUNDRY ROOM FOR ENGINEER. 1500 N LAKE SHORE DR PERIODIC PASSED View
INSTALL SMOKE DETECTORS PER CODE SECTION 13-196-110, 13-196-130 AND 13-196-140.SMOKE DETECTORS MISSING DURING INSPECTION INCLUDE BUT ARE NOT LIMITED TO; NORTH STAIRWELL AT TOP BY ELEVATOR MACHINE ROOM, GARAGE PENTHOUSE ELEVATOR ROOM, GARAGE STAIRWELL, EXERCISE ROOM. 1500 N LAKE SHORE DR PERIODIC PASSED View
SELF-CLOSE CLASS B FIRE DOOR PER CODE SECTION 15-8-180ABANDONED TRASH CHUTE DOORS MUST BE SEALED COMPLETELY TO MAINTAIN (2) TWO HOUR SEPARATION. PENTHOUSE ELEVATOR ROOMS /WOOD ACCESS PANELS TO ELEVATOR SHAFT. NOTE: IN ALL (3) THREE ELEVATOR ROOMS /ACCESS THROUGH FIRE WALLS THAT DO NOT HAVE FIRE RATED DOOR OR NO DOOR IS MISSING. 1500 N LAKE SHORE DR PERIODIC PASSED View
I-A I-B I-C AND II FIRE RESIST PER CODE SECTION15-8-260(A) AND 13-60-020 REMOVE WOOD PARTITION WALLS CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL BUT NOT LIMITED TO: LEVEL ONE IN GARAGE /VALET SHED BUILT OUT OF PLYWOOD AND PLEXIGLAS WINDOWS, RUBBER TIRES BEING USED AS CAR BUMPERS ON WALL, LOWER LEVEL GARAGE /COMBUSTIBLE MATERIAL (WOOD) BEING STORED DURING INSPECTION, ELEVATOR MACHINE ROOM AT PENTHOUSE /WOOD STAIRS TO UPPER CRAWL SPACE /COMBUSTIBLE MATERIAL (WOOD) BEING STORED IN CRAWL SPACE DURING INSPECTION.(23RD ½ FLOOR) ELEVATOR ROOM-BETWEEN 24TH AND 23RD FLOOR OPENINGS THROUGH FIRE RATED WALLS INTO AREA THAT IS THE CEILING OF THE 23RD FLOOR DWELLING UNIT /COMBUSTIBLE MATERIAL (WOOD) BEING USED FOR PLANKING.NOTE: COMBUSTIBLE MATERIAL NOT ALLOWED IN CONSTRUCTION TYPE 1A, 1B, 1C, OR TYPE 2 NON- COMBUSTIBLE CONSTRUCTION OR FIRE RESISTIVE ASSEMBLIES. 1500 N LAKE SHORE DR PERIODIC PASSED View
PIPE OPENING W/NONCOMBUST MATL PER CODE SECTION 15-8-640. FIRE STOPPING IS TO BE COMPLETED PER APPROVED U.L. ASSEMBLY DOCUMENTATION. PROPERLY FIRE STOP ALL PENETRATIONS THROUGHOUT BUT NOT LIMITED TO: NORTH AND SOUTH ELEVATOR MACHINE ROOM, CRAWL SPACE ABOVE ELEVATOR MACHINE ROOMS, LEVEL ONE IN GARAGE TO VEHICLE ELEVATOR SHAFT, LOWER LEVEL GARAGE, BIKE ROOM, BOILER ROOM, LEVEL ONE /JANITORS CLOSET, (23RD ½ FLOOR) ELEVATOR ROOM-BETWEEN 24TH AND 23RD FLOOR /OPEN DUCT WORK / OPEN RISER PIPES /OPEN ELEVATOR SHAFT, /OPENINGS THROUGH FIRE RATED WALLS INTO AREA THAT IS THE CEILING OF THE 23RD FLOOR DWELLING UNIT /PENETRATION FROM DWELLING UNIT TO ELEVATOR ROOM. 1500 N LAKE SHORE DR PERIODIC PASSED View
CLASS B DOOR IN STAIRWELL PRE CODE SECTION 15-8-180 (EXISTING HIGH RISE BUILDINGS- 13-196-209)STAIRWELL DOORS MUST BE CLASS ¿¿B¿¿ FIRE RATED DOORS. RATED DOORS MUST BE SELF-CLOSING AND MUST HAVE A POSITIVE LATCH. DURING INSPECTION- NORTH AND SOUTH ELEVATOR MACHINE ROOM /NO LABEL /VENT IN DOORS, SOUTH TOWER-20A /NO LATCH, 7B /NO LATCH-MISSING STRIKE, 4B /NO CLOSER, 4B /NO CLOSER, 3B /NO LATCH, 1A TO LOBBY /NO CLOSER, NORTH STAIR TOWER "C"- 24C /NO LATCH, BETWEEN 24TH AND 23RD FLOOR TO ELEVATOR ROOM (2) TWO DOORS /NO LABEL /NO CLOSER /OPEN SCREEN VENT IN DOORS, 15C /NO ENTRY, 12C /NO LATCH /RUBS ON CARPER, 10C /NO LATCH, 3C /NO LATCH, GARAGE STAIR TOWER- 3RD. FLOOR /NO LATCH. 1500 N LAKE SHORE DR PERIODIC PASSED View
PROVIDE FAILED TO OBTAIN APPROVAL FOR IMPLEMENTATION OF LIFE SAFETY EVALUATION COMPLIANCE PLAN. (13-196-206D) 1500 N LAKE SHORE DR COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA TEST FAIDS WHEN INSTALLED. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE TEMPERATURE CONTROL MACHINE. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE VENT MACHINE ROOM. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE WEST CAR OLD MAINLINE DISCONNECT. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE DRIP PAN UNDER ROOF DRAIN OVER CONTROLLER FOR ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PIT LADDER FOR ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE AND CONVENIENT ACCESS TO SECONDARY AREA IN OVERHEAD, GOVERNOR OF SINGLE HOISTWAY ELEVATOR. PROVIDE ACCESS DOOR WITH SAFETY CHAIN SWITCH, LIGH NG, AND GFCI OUTLET. CURRENTLY ACCESS THROUGH OPPISITE OF HOISTWAY. ELEVATOR #S3 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE GUARDING/FENCE SEPARATING BASEMENT MACHINE ROOM FROM HOISTWAY. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE 2 HOUR FIRE RATED ACCESS DOOR TO SECONDARY DECK OF ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A BUILDING GROUND TO ALL ELEVATOR 110V AND LINE DISCONNECTS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA THE ELEVATORS THAT UTILIZE THE CAR SWITCH FOR OPERATION MUST RECALL AUTOMATICLLY ON PHASE I OR ANY FIRE RECALL; IE: FAID, LOBBY PANEL 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA THE ELEVATORS THAT POSSESS MANUAL CAR GATES OPERATION MUST RECALL AUTOMATICLLY WITHOUT ASSIST. IE: GATE CLOSERS? 1500 N LAKE SHORE DR PERMIT FAILED View
ARRANGE COMPLETED PERMIT INSP. 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SELF LOCKING MACH. DOOR AND SIGNAGE 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CITY FIRE RECALL TEST 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PERMENANT PHONE LINE 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SCREW TO SECURE COVER FOR JUNCTION BOX FOR FEEDERS IN MACHINE ROOM FOR ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ALL WOOD THROUGHOUT ALL HOISTWAYS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ABANDONED DUCT WORK THROUGHOUT ALL HOISTWAYS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA TO COMPLETE FIRE SERVICE TESTING ON THE GARAGE CARS;PIT STOP SWITCH, TOP OF CAR #2 CONTROLS, LOBBY PANEL ONLY RECALL BOTH SWITCHES, AND SHOULD RECALL ON FAID RECALL IN BUILDING 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA FAID TESTING ON #N1, #N2, #S!,AND #S2 INCOMPLETE. #N1 ALL FLOORS TESTED EXCEPT FOR FLOORS; LOBBY, PS, AND 15. PS AND 22 HAVE NO DEVICES. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA #N2 22ND FLOOR RESTRICTED EGRESS (UNITS ENTRY DOOR LOCKED ON HOISTWAY SIDE) DOOR MAY BE LEFT BUT STRIKE ON THE DOOR MUST BE REMOVED 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL OF THE FAID RECALL TEST HAVE BEEN COMPLETED SATIFACTORY IN THE MACHINE ROOMS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE LOCKING MECHINISM ON DOOR RESTRICTING ACCESS OF 15TH FLOOR SOUTH UNITS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA RE-SCHEDULE TESTING OF FIREMANS SERVICE, 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL COUNTERWEIGHT GUARDS BOTH CARS. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL ALL DISCONNECTS IN MACHINE ROOM. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL TOE GUARDS BOTH CARS. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSULATE COPPER DRAIN PIPE IN MACHINE ROOM. 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA COMPLETELY SECURE AND SEAL AIR DUCT ILLEGALLY INSTALLED IN ELEVATOR #N1 HOISTWAY 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE 2HOUR FIRE RATED ACCESS DOOR TO SECONDARY DECK OF ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE ELEVATOR CONTROL PANEL IN LOBBY 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ALL WOOD THROUGHOUT HOISTWAYS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A BUILDING GROUND TO ELEVATOR 110V AND LINE DISCONNECTS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ABANDONED DUCT WORK THROUGHOUT HOISTWAYS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE AND CONVENIENT ACCESS TO ELEVATOR PIT OF #S3 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA LABEL/STENCIL CONDUITS AND JUNCTION BOXES ROUTED AND MOUNTED THROUGHOUT HOISTWAY OF ELEVATOR #S3 EVERY 20 FEET WITH VOLTAGE AND PURPOSE. (CONDO UNITS FEEDERS?) 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A STOP SWITCH AT POINT OF ENTRY TO THE SECONDARY DECK #S4 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A FIRE RESISTANT STAIRS/LADDER WITH RAILINGS FOR SAFE AND CONVENIENT ACCESS TO THE MACINE/CONTROLLER DECK #S4 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE AND CONVENIENT ACCESS TO THE SECONDARY DECK #N2 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A STOP SWITCH ON THE MACHINE/CONTROLLER DECK #S4 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE DRIP PAN UNDER DRAIN PIPE OVER ELEVATOR MACHINE #N2 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A STOP SWITCH AT THE ACCESS POINT TO THE SECONDARY DECK #N2 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SIGNAGE ON ALL ACCESS DOORS TO MACHINE ROOMS, SECONDARY DECKS, AND PITS. ALL ELEVATORS 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE AN ENCLOSURE (SOFFIT) AROUND GAS/STEAM?? PLUMBING IN HOISTWAY OF ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A GAS DETECTOR/SENSOR TO TRIP AS A FAID AT TOP END OF SOFFIT ENCAPSILATING PIPES(SOFFIT) IN HOISTWAY OF ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA MECHNICALLY PROTECT AND SECURE ALL LOW VOLTAGE CABLES DRAPED THROUGH OUT HOIST WAY IN ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE THE INSULATION OFF OF DRAIN PIPE RUN DIRECTLY OVER ELEVATOR MACHINE #N2 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CAR SWITCH ELEVATORS WITH A KEY SWITCH TO PLACE THE ELEVATOR INTO ACCESS MODE. 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CAR SWITCH ELEVATORS WITH A WRITTEN OR VIDEO LESSON ON HOW TO ACCESS HOISTWAY (NO ESCUSIONS OR ACCESS KEY SWITCHES)FOR AUTHORIZED PERSONNEL BECAUSE OF THE NATURE OF THE DOOR INTERLOCKS DESIGN A FLAT PIECE OF STEEL IS UTILIZED IN THIS PROCESS. DIRECTIONS SHOULD BE WITHIN THE PREMISES POSSIBLY IN THE MANAGEMENT OFFICE. 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY I TESTING ON ALL ELEVTORS. THIS WORK MUST BE COMPLETED AS LONG AS THE ELEVATORS ARE ALLOWED TO OPERATE FOR PUBLIC USE EVEN OPERATING AS TEMP. USE UNDER A MODERNIATION PERMIT. 1500 N LAKE SHORE DR PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A STOP SWITCH ON THE MACHINE/CONTROLLER DECK #S4 1500 N LAKE SHORE DR PERMIT FAILED View
SEND EX. METAL LETTER EXPOSED METAL LETTER 1500 N LAKE SHORE DR COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE ALL PLASTIC CONTAINERS ABOVE CONTROLLERS WHERE CEILING IS LEAKING AND REPAIR CEILING 1500 N LAKE SHORE DR PERIODIC PASSED View
PROVIDE PER CODE SECTION 18-27-700. PROVIDE SUFFICIENT NUMBER OF EMERGENCY LIGHTING THROUGHOUT ENTIRE BUILDING. DURING INSPECTION EMERGENCY LIGHTS WERE MISSING AT BUT NOT LIMITED TO: NORTH AND SOUTH ELEVATOR MACHINE ROOMS 1500 N LAKE SHORE DR PERIODIC PASSED View
EXPOSED WIRING DURING INSPECTION /EXPOSED ELECTRICAL WIRE AT BUT NOT LIMITED TO: 24TH FLOOR SOUTH STAIRWELL. 1500 N LAKE SHORE DR PERIODIC PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE SAFE AND CONVENIENT ACCESS TO THE SECONDARY DECK OF ELEVATOR #N1 1500 N LAKE SHORE DR PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE WATER FROM PIT. PROVIDE SUMP PUMP 1500 N LAKE SHORE DR PERMIT FAILED View