Chicago Building Violations Data: 107 Violations
Violation Inspector Comments Address Category Status View
REPAIR INTERIOR WALLS/CEILING 51ST UTILITY AREA UNDER PHONE ACCESS PANEL: HOLE IN DRYWALL-SOUTH CORRIDOR HIGH RISE AREA VERTICAL FRACTURES IN DRYWALL-NORTH & SOUTH STAIRWELL AREAS AT CEILINGS-WIRE & PIPE PENETRATIONS-SEAL HOLES AROUND AREAS 111 E CHESTNUT ST PERIODIC FAILED View
WORKING SPACE MAIN ELECTRICAL ROOM IN REALTY OFFICE SPACE 18-27-110.26 111 E CHESTNUT ST COMPLAINT FAILED View
TENANT ACCESS TO SERVICE ALL TENANTS SHALL HAVE ACCESS AT ALL TIMES 18-27-230.72 111 E CHESTNUT ST COMPLAINT FAILED View
INSTALL COVERS MAIN ELECTRICAL ROOM IN REALTY OFFICE SPACE 18-27-370.25 EXPOSE LIVE PARTS DANGEROUS AN HAZARDOUS CONDITION 111 E CHESTNUT ST COMPLAINT FAILED View
RESTORE EXIT AND EM EMERGENCY AND EXIT LITES NOT WORKING IN STAR BUCK STORE 18-27-700.6 111 E CHESTNUT ST COMPLAINT FAILED View
NO PERMIT WIRING INSTALLATION OF PANELS AND WIRING CONDUIT WITHOUT PERMIT 13-12-360 111 E CHESTNUT ST COMPLAINT FAILED View
STOP ALL WORK UNTIL PROPER PLANS AND PERMITS HAVE BEEN ISSUED. SEC. 13-32-035; 13-12-080 111 E CHESTNUT ST COMPLAINT FAILED View
FOLLOW APPROVED PLANS BUILDING PERMIT #1021671 ISSUED 10/14/03 IS REVOKED FOR WORKING CONTRARY TO APPROVED PLANS AND PERMIT AND 9TH FLOOR RECREATION ROOM RELOCATED RESTROOMS, PANTRY, MECHANICAL ROOM. 111 E CHESTNUT ST COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR FOR INTERIOR ALTERATIONS TO THE 9TH AND 10TH FLOORS INCLUDING BUT NOT LIMITED TO: 9TH FLOOR RECREATION ROOM, 9TH FLOOR CONSERVATORY ROOF STRUCTURE; CORRIDOR REMODELING 9TH AND 10TH FLOORS; 10TH FLOOR OFFICE AREA; 9TH FLOOR PATIO AREA. 111 E CHESTNUT ST COMPLAINT FAILED View
STOP ALL WORK UNTIL PROPER PLANS AND PERMITS HAVE BEEN ISSUED. SEC. 13-32-035; 13-12-080PERMIT #100179111 ISSUED 08-02-07 - PSO FEES PAID 111 E CHESTNUT ST COMPLAINT CLOSED View
FOLLOW APPROVED PLANS BUILDING PERMIT #1021671 ISSUED 10/14/03 IS REVOKED FOR WORKING CONTRARY TO APPROVED PLANS AND PERMIT AND 9TH FLOOR RECREATION ROOM RELOCATED RESTROOMS, PANTRY, MECHANICAL ROOM.PERMIT #100179111 ISSUED 08-02-07 - PSO FEES PAID 111 E CHESTNUT ST COMPLAINT CLOSED View
PLANS & PERMITS REQ - CONTRCTR FOR INTERIOR ALTERATIONS TO THE 9TH AND 10TH FLOORS INCLUDING BUT NOT LIMITED TO: 9TH FLOOR RECREATION ROOM, 9TH FLOOR CONSERVATORY ROOF STRUCTURE; CORRIDOR REMODELING 9TH AND 10TH FLOORS; 10TH FLOOR OFFICE AREA; 9TH FLOOR PATIO AREA.PERMIT #100179111 ISSUED 08-02-07 - PSO FEES PAID 111 E CHESTNUT ST COMPLAINT CLOSED View
MAINTAIN OR REPAIR HYDRO ELEVA REPAIR PIT LIGHTS 111 E CHESTNUT ST COMPLAINT PASSED View
ARRANGE COMPLETED PERMIT INSP. 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN MECH. VENT SYSTEM MAINTAIN MECHANICAL EQUIPMENT DURING HOURS OF OCCUPANCY EXHAUST FANS NEED TO BE REPAIRED R.O. TO BE UNCOVERED 111 E CHESTNUT ST COMPLAINT PASSED View
ARRANGE ANNUAL INSP. ARRANGE ANNUAL MECHANICAL VENTILATION INSPECTION (13-20-290) 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN MECH. VENT SYSTEM OPERABLE EXHAUST FAN CONTINUOUSLY (13-176-300) 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PATCH ALL HOLES IN HOISTWAY 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CLEAN ELEVATOR MACHINE ROOM 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA KEEP MONTHLY FIRE SERVICE CHECK LOG AND MAINTENANCE LOG 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PULL PERMIT FOR REPAIRS BEING DONE ON CAR #8 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROPERLY REPAIR AND MAINTAIN CAR #8 IN A SAFE WORKING ORDER 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA CLEAN ALL CAR #9 MACHINES FROM ALL CABLE ROUGES 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPLACE BEARINGS FOR CAR #8 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PUT ROPE GRIPPERS ON ELEVATOR CARS # 9, 7, 6,8 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA HOOK UP LOBBY PANEL TO ALL ELEVATORS IN THE BUILDING 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA FIX ALL HALL CALLS ON FREIGHT CAR 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA COVER ALL LIGHTS ON FREIGHT CAR 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PERFORM CATEGORY ONE TEST ON ALL ELEVATORS AND TAG GOVERNORS 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REMOVE WATER AND REPLACE SUMP PUMP - FREIGHT CAR 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE PICTOGRAPHS(IN CASE OF FIRE) AT ALL HALL CALL STATIONS 111 E CHESTNUT ST PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA ALL PHASE I + II KEYS ARE TO BE ALIKE IN BUILDING CHARGE SERVICE CAR 111 E CHESTNUT ST PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA REPAIR CCTV IN LOW RISE MACHINE ROOM CURRENTLY INOPERATIVE 111 E CHESTNUT ST PERMIT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA MAINTAIN 2HR FIRE RATING IN HOISTWAY PATCH ALL PIPE CHASES FOR DETECTORS 111 E CHESTNUT ST PERMIT FAILED View
SEE INSPECTOR COMMENTS SEE NOTICE # 12137 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA CCTV MONITORS AND CAMERAS NOT FUNCTIONING ORG. 11/05/13 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE REGISTER FOR HVAC DUCT OVER #6 ELEVATOR CONTROLLER 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE CABLE CUARD ON MACHINE IN HIGH RISE MACHINE ROOM 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE COVER FOR RIPPLE FILTER/ CHOICE ON #10 ELEVATOR 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE DOOR ON ELEVATOR #10 CONTROLLER 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PERMANENTLY SEAL MACHINE ROOM ELEVATORS #8, #9, #10 2HR RATING ALL PIPE CLOSES #10 MACHINE ROOM FLOOR - WOOD AND SHEET METAL WALL PATCH IS UNACCEPTABLE 111 E CHESTNUT ST PERMIT PASSED View
OBTN PERMIT FOR PLUMBING WORK 111 E CHESTNUT ST COMPLAINT FAILED View
LICENSED BONDED PLMBG CONTRCTR 111 E CHESTNUT ST COMPLAINT FAILED View
ARRANGE PREMISE INSPECTION 111 E CHESTNUT ST COMPLAINT FAILED View
ARRANGE PERMIT INSP. 111 E CHESTNUT ST PERMIT FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE "LINE OF SOGHT" FROM MACHINE ROOMS ON 36TH & 37TH FLOOR 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE REGULATOR FOR 111 E CHESTNUT ST PERMIT FAILED View
PLANS & PERMITS REQ - CONTRCTR 50TH FLOOR UNIT A AND K; 51ST FLOOR UNIT A - UNIT DOORS MOVED INTO COMMON CORRIDOR, THUS INCREASING THE UNIT INTERIOR EXIT TRAVEL DISTANCE TO THE FIRE RATED CORRIDOR. SUBMIT PLANS TO VERIFY LIFE SAFETY REQUIREMENTS AND OBTAIN A BUILDING PERMIT. 111 E CHESTNUT ST COMPLAINT FAILED View
SELF-CLOSE DOOR >4 STORY RES. ---DEFECTIVE AND/OR MISSING CLOSERS AND/OR LATCHES AT: 26G,25AB,24K BACK DOOR,24F,24C,24A BACK DOOR,23A BACK DOOR,23K BACK DOOR,22K,22F,22A BACK DOOR,21A BACK DOOR,21K BACK DOOR,20K BACK DOOR,20J,20F,20C BACK DOOR,20A BACK DOOR,19A BACK DOOR,19K BACK DOOR,18K BACK DOOR,18J,18E,18D, 18C,18A BACK DOOR,17A BACK DOOR,17D,17H,17K BACK DOOR,16K BACK DOOR,15A BACK DOOR,15D,15K BACK DOOR,14K BACK DOOR,14J,14C BACK DOOR,14A BACK DOOR,12A BACK DOOR,12C,12H,11K BACK DOOR,11F,11D; 57A,57K,57H,57G,56F,56C,56B,55A,55B,55F,54K,54H,54F,54C BACK DOOR,54J,53A BACK DOOR,53G,53K BACK DOOR,52K BACK DOOR,52F,52C BACK DOOR,52B,51C,51F,51G,51H,51K,51J,50G,50A,49H,49J,49K,48A,48K BACK DOOR,48J,48C BACK DOOR,48H,47A BACK DOOR,47K BACK DOOR,47C BACK DOOR,47F,46K BACK DOOR,46D,46A BACK DOOR,45A,45F,45K BACK DOOR,44C BACK DOOR,44A BACK DOOR,44K BACK DOOR,43K BACK DOOR,42K BACK DOOR,42G,42A BACK DOOR,41A BACK DOOR,40K BACK DOOR,40C BACK DOOR,40C FORNT DOOR,40H,40A BACK DOOR,39B,39D,39K BACK DOOR,38K BACK DOOR,38C,38A BACK DOOR,36A BACK DOOR,38B,36K BACK DOOR,36G,36E,36A,35A BACK DOOR,35B,35F,35J,34H,34A BACK DOOR,33A,32K BACK DOOR,32F,32E,32C BACK DOOR,32A BACK DOOR,31A BACK DOOR,31C,31H,31K BACK DOOR,30A,30K BACK DOOR,29A BACK DOOR,29J,29K BACK DOOR,28C BACK DOOR,28A BACK DOOR,28B,27A,27K BACK DOOR 111 E CHESTNUT ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT UNABLE TO CHECK DOORS AT: 47B,47D,32D,12C BOOKMARK13-196-170 SELF-CLOSING DEVICES REQUIRED FOR CORRIDOR DOORS. IN RESIDENTIAL BUILDINGS EXCEEDING FOUR STORIES IN HEIGHT, ALL APARTMENT DOORS OPENING UPON PUBLIC CORRIDORS SHALL BE EQUIPPED WITH APPROVED SELF-CLOSING DEVICES. IN ALL NEW AND EXISTING SINGLE-ROOM OCCUPANCY BUILDINGS, IRRESPECTIVE OF HEIGHT, ALL DWELLING UNIT DOORS OPENING TO PUBLIC CORRIDORS SHALL BE EQUIPPED WITH APPROVED SELF-CLOSING DEVICES. BOOKMARK13-12-100 OFFICIAL RIGHT OF ENTRY ¿ INTERFERENCE UNLAWFUL. THE APPROPRIATE OFFICIALS CHARGED WITH THE ADMINISTRATION OF ANY OF THE PROVISIONS OF THIS CODE ENUMERATED IN SECTION 13-12-010, OR ANY OF THEM AND THEIR RESPECTIVE ASSISTANTS, SHALL HAVE THE RIGHT TO ENTER ANY BUILDING, OR PREMISES, AND ANY AND ALL PARTS THEREOF, AT ANY REASONABLE TIME, AND AT ANY TIME WHEN OCCUPIED BY THE PUBLIC IN ORDER TO EXAMINE SUCH BUILDINGS OR PREMISES TO JUDGE OF THE CONDITION OF THE SAME AND TO DISCHARGE THEIR RESPECTIVE DUTIES, AND IT SHALL BE UNLAWFUL FOR ANY PERSON TO INTERFERE WITH THEM IN THE PERFORMANCE OF THEIR DUTIES. 111 E CHESTNUT ST COMPLAINT FAILED View
SELF-CLOSE DOOR >4 STORY RES. DEFECTIVE AND/OR MISSING CLOSERS AND/OR LATCHES AT: 26G,25AB,24K BACK DOOR,24F,24C,24A BACK DOOR,23A BACK DOOR,23K BACK DOOR,22K,22F,22A BACK DOOR,21A BACK DOOR,21K BACK DOOR,20K BACK DOOR,20J,20F,20C ABCK DOOR,20A BACK DOOR,19A BACK DOOR,19K BACK DOOR,18K BACK DOOR,18J,18E,18D, 18C,18A BACK DOOR,17A BACK DOOR,17D,17H,17K BACK DOOR,16K BACK DOOR,15A BACK DOOR,15D,15K BACK DOOR,14K BACK DOOR,14J,14C BACK DOOR,14A BACK DOOR,12A BACK DOOR,12C,12H,11K BACK DOOR,11F,11D; 57A,57K,57H,57G,56F,56C,56B,55A,55B,55F,54K,54H,54F,54C BACK DOOR,54J,53A BACK DOOR,53G,53K BACK DOOR,52K BACK DOOR,52F,52C BACK DOOR,52B,51C,51F,51G,51H,51K,51J,50G,50A,49H,49J,49K,48K BACK DOOR,48J,48C BACK DOOR,48H,47A BACK DOOR,47K BACK DOOR,46K BACK DOOR,46D,46A BACK DOOR,45A,45F,45K BACK DOOR,44C BACK DOOR,44A BACK DOOR,43K BACK DOOR,42K BACK DOOR,42A BACK DOOR,41A BACK DOOR,40K BACK DOOR,40C BACK DOOR,40C,40A BACK DOOR,39B,39D,39K BACK DOOR,38K BACK DOOR,38C,38A BACK DOOR,36A BACK DOOR,38B,36K BACK DOOR,36G,36E,36A,35A BACK DOOR,35B,35F,35J,34H,34A BACK DOOR,33A,32K BACK DOOR,32F,32E,32C BACK DOOR,32A BACK DOOR,31A BACK DOOR,31C,31H,31K BACK DOOR,30A,29A BACK DOOR,29J,29K BACK DOOR,28C BACK DOOR,28A BACK DOOR,28B,27A,27K BACK DOOR 111 E CHESTNUT ST COMPLAINT PASSED View
BLANK-TEXT MUST CITE CODE SECT UNABLE TO CHECK DOORS AT: 55J,53B,51A,50J,50K,48F,47F,47C,47D,46F,46B,44K,44H,44K,43B,42D,40H,36J,34B,33K,32J,32D,30K,29C,29D,28K,28B,26D,25B,25K,24G,23D,23J,20B,17B,17C,16H,16A,15F,12F BOOKMARK13-196-170 SELF-CLOSING DEVICES REQUIRED FOR CORRIDOR DOORS. IN RESIDENTIAL BUILDINGS EXCEEDING FOUR STORIES IN HEIGHT, ALL APARTMENT DOORS OPENING UPON PUBLIC CORRIDORS SHALL BE EQUIPPED WITH APPROVED SELF-CLOSING DEVICES. IN ALL NEW AND EXISTING SINGLE-ROOM OCCUPANCY BUILDINGS, IRRESPECTIVE OF HEIGHT, ALL DWELLING UNIT DOORS OPENING TO PUBLIC CORRIDORS SHALL BE EQUIPPED WITH APPROVED SELF-CLOSING DEVICES. 111 E CHESTNUT ST COMPLAINT PASSED View
2HR SEP FOR STORAGE >100SF STORAGE ROOMS INSTALLED 45 MINUTE DOORS, DUCTS GO THRU STORAGE ROOMS; 10TH FLOOR NORTH END ROOM PLYWOOD AT TOP, DOOR NOT RATED. 9TH FLOOR STORAGE ROOM MISSING FIRE SEPARATION. STORAGE ROOM IN BASEMENT HAS ONE HOUR FIRE SEPARATION AND COMBUSTIBLE FLOOR 111 E CHESTNUT ST COMPLAINT FAILED View
GARAGE TO RESIDENTIAL-4HR SEP GARAGE STORAGE ROOMS---IMPROPER FIRE SEPARATION FROM GARAGE 111 E CHESTNUT ST COMPLAINT FAILED View
GARAGE HEATINGPLANT SEPARATION BOILER ROOM FRACTURED WALLS, DOORS DO NOT HAVE 3 HOUR RATING 111 E CHESTNUT ST COMPLAINT FAILED View
1HR PUB.CORIDR NON-RES/SPRNKLD 9TH AND 10TH FLOOR CORRIDORS---GLASS NOT RATED, DOORS HAVE VENTS. FIRST FLOOR BACK LOOBY DOOR TO CORRIDOR--GLASS NOT RATED;FIRST FLOOR PANECALDO BACK DOOR TO CORRIDOR GLASS NOT RATED 111 E CHESTNUT ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT TRASH CHUTE DOORS AT 32ND AND 33RD FLOORS---NOT LATCHING; 57TH FLOOR ACCESS PANEL NOT RATEDBOOKMARK15-8-170 ENCLOSURE OF WELLS AND CHUTES. WELLS, CHUTES AND SIMILAR OPENINGS THROUGH A FLOOR SHALL BE ENCLOSED WITH CONSTRUCTION PROVIDING FIRE RESISTANCE OF NOT LESS THAN ONE HOUR, EXCEPT THAT ENCLOSURE OF WELLS SHALL NOT BE REQUIRED WHERE OPEN STAIRWAYS ARE PERMITTED. (A) IN ALL BUILDINGS EXCEEDING THREE STORIES IN HEIGHT AND IN INSTITUTIONAL BUILDINGS EVERY LAUNDRY AND RUBBISH CHUTE ENCLOSURE SHALL BE OF NOT LESS THAN TWO- HOUR FIRE-RESISTIVE CONSTRUCTION. THE MINIMUM INSIDE DIMENSIONS OF THE CHUTE SHALL BE 18 INCHES. ALL CHUTES SHALL DISCHARGE DIRECTLY INTO A ROOM HAVING WALLS, CEILING AND FLOOR OF TWO-HOUR FIRE-RESISTIVE CONSTRUCTION USED SOLELY FOR THE RECEPTION OF LAUNDRY OR RUBBISH. THE ROOM SHALL BE EQUIPPED WITH ONE SPRINKLER HEAD FOR THE FIRST 130 SQUARE FEET OF FLOOR AREA AND ONE ADDITIONAL HEAD FOR EACH ADDITIONAL 130 SQUARE FEET OR LESS. ONE SPRINKLER HEAD SHALL BE INSTALLED IN THE CHUTE AT THE TOP SERVICE OPENING; AND ONE ADDITIONAL SPRINKLER HEAD AT EVERY SECOND FLOOR LEVEL BELOW THE TOP FLOOR. A SELF- CLOSING ONE AND ONE-HALF-HOUR CLASS B LABELED FIRE DOOR ASSEMBLY SHALL BE INSTALLED AT THE SERVICE OPENING AT EACH LEVEL AND AT THE BOTTOM OF THE CHUTE AND IN THE SERVICE DOOR OPENING OF THE ROOM INTO WHICH THE LAUNDRY OR RUBBISH IS DISCHARGED. 111 E CHESTNUT ST COMPLAINT FAILED View
CLASS B DOOR IN STAIRWELL 32S---WARPED DOOR; 3BN,3BS,2BN,2BS,1BS---DEFECTIOVE AND/OR MISSING CLOSERS AND/OR LATCHES 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE ---FIRE SEPARATION FOR ELEVATOR ROOMS---10TH FLOOR ELEVATOR ROOM DOOR MISSING CLOSER, REMOVE COMPRESSED CARDBOARD FROM WALLS AND CEILING. 36TH FLOOR ELEVATOR ROOM ACCESS PANEL NOT RATED.BASEMENT ELEVATOR ROOM DOOR DEFECTIVE. 36TH AND 37TH FLOOR DOORS HAVE ONLY 45 MINUTE RATING. BOOKMARK15-8-150 ELEVATOR AND ESCALATOR ENCLOSURES. (A) ELEVATOR ENCLOSURES. (1) ELEVATOR SHAFTS AND DUMBWAITER SHAFTS SHALL BE ENCLOSED WITH WALLS OR PARTITIONS PROVIDING FIRE RESISTANCE OF NOT LESS THAN TWO HOURS, EXCEPT THAT WALLS AND PARTITIONS SEPARATING ADJACENT SHAFTS SHALL PROVIDE FIRE RESISTANCE OF NOT LESS THAN ONE HOUR. 111 E CHESTNUT ST COMPLAINT FAILED View
INSTALL SMOKE DETECTORS NORTH STAIRWELL AT 57TH FLOOR MISSING 111 E CHESTNUT ST COMPLAINT FAILED View
CARB MONOX DETECT IN ASSEMBLY LAUNDRY ROOM-MISSING; GARAGE---MISSING 111 E CHESTNUT ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT BOOKMARK13-56-280 MIXED OCCUPANCY ¿ FIRE-RESISTIVE SEPARATIONS REQUIRED. EACH OCCUPANCY IN A BUILDING OF MIXED OCCUPANCY SHALL BE SEPARATED HORIZONTALLY AND VERTICALLY FROM ANY ADJOINING OCCUPANCY BY CONSTRUCTION MATERIALS PROVIDING FIRE RESISTANCE AS ESTABLISHED IN TABLE 13-56-280 AS SET OUT IN THIS SECTION. SEPARATION BETWEEN TYPE III SCHOOLS AND A, B, C-1, C-2, AND E OCCUPANCIES, EXCEPT DAY CARE CENTERS WITH CHILDREN LESS THAN TWO YEARS OF AGE, MAY BE REDUCED TO ONE HOUR. SEPARATION BETWEEN TYPE III SCHOOLS WITH CHILDREN LESS THAN TWO YEARS OF AGE AND A, B, C-2, E AND F OCCUPANCIES MAY BE REDUCED TO TWO HOURS. SEPARATION IN BUILDINGS OF MIXED OCCUPANCIES MAY BE REDUCED BY ONE HOUR FROM THE FIRE RESISTANCE REQUIREMENTS AS ESTABLISHED IN TABLE 13-56-280 AS SET OUT IN THIS SECTION WHEN THE BUILDING IS EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM WHICH IS SUPERVISED EXCEPT THAT SEPARATIONS BETWEEN DAY CARE CENTERS WITH CHILDREN LESS THAN TWO YEARS OF AGE AND A, B, C, C-1, C-2, E AND F OCCUPANCIES SHALL NOT BE REDUCED TO LESS THAN TWO HOURS.(PRIOR CODE § 48-12.5; AMEND COUN. J. 9-13-89, P. 4604; AMEND COUN. J. 7-14-93, P. 35324; AMEND COUN. J. 10-30-96, P. 31214)REQUIRED GARAGE TO RESTAURANT SEPARATION IS 3 HOURS---DUCT GOES THRU WALL SEPARATION AT LOCATION (2A-37)---SECTION 13-56-280.STORAGE ROOMS IN GARAGE HAVE ONLY ONE HOUR SEPARATION---REQUIRED SEPARATION IS 4 HOURS PER----SECTION 13-56-280. 111 E CHESTNUT ST COMPLAINT FAILED View
REMOVE ---57N VESTIBULE----PLYWOODBOOKMARK13-160-380 SMOKEPROOF TOWERS ¿ VESTIBULES AND BALCONIES. ACCESS TO THE STAIRWAY AT EACH STORY SHALL BE THROUGH A VESTIBULE OR BALCONY COMPLYING WITH THE FOLLOWING REQUIREMENTS: (A) EXCEPT WHEN AN INTERIOR SMOKE SHAFT IS PROVIDED, THE VESTIBULE OR BALCONY SHALL BE LOCATED ON AN EXTERIOR WALL NOT SUBJECT TO A SEVERE FIRE EXPOSURE HAZARD. (B) EVERY VESTIBULE OR BALCONY SHALL HAVE AN OPENING TO A PUBLIC WAY, YARD OR COURT OR TO AN INTERIOR SMOKE SHAFT COMPLYING WITH THE REQUIREMENTS OF SECTION 13-160-420. (C) SUCH OPENINGS SHALL HAVE AN AREA NOT LESS THAN ONE-HALF THE AREA OF THE EXIT DOORS LEADING FROM THE BUILDINGS TO THE VESTIBULE OR BALCONY AND SHALL BE LOCATED NOT LESS THAN FOUR FEET ABOVE THE FLOOR AND NOT MORE THAN SIX INCHES BELOW THE CEILING OF THE VESTIBULE OR BALCONY. UNLESS SUCH OPENING FACES A PUBLIC WAY, YARD OR COURT NOT LESS THAN 40 FEET WIDE, THE OPENING SHALL BE PROTECTED WITH A FIRE SHIELD COMPLYING WITH THE REQUIREMENTS OF SECTION 13-160-390. IN ANY CASE, THE YARD OR COURT SHALL HAVE A MINIMUM WIDTH OF 20 FEET AND A MINIMUM AREA OF 400 SQUARE FEET. (D) THE FLOORS, WALLS AND CEILINGS OF ALL VESTIBULES OR BALCONIES SHALL BE OF CONSTRUCTION PROVIDING FIRE PROTECTION OF NOT LESS THAN THREE HOURS. FIRST FLOOR GARAGE SPACE SEPARATIONS BUILT OF COMBUSTIBLE MATERIALS BOOKMARK15-8-260 FIRE-RESISTIVE REQUIREMENTS. EXCEPT AS PROVIDED IN SECTION 15-8-270, NON-LOAD- BEARING PARTITIONS OTHER THAN THOSE REQUIRED FOR ENCLOSURES OR SEPARATIONS AS PROVIDED IN SECTIONS 15-8-120, 15-8-190 AND 15-8-240 SHALL COMPLY WITH THE FOLLOWING MINIMUM REQUIREMENTS: (A) IN BUILDINGS OF TYPES I-A, I-B, I-C AND II CONSTRUCTION, PARTITION FRAMING SHALL BE OF EITHER OR BOTH OF THE FOLLOWING MATERIALS: (1) NONCOMBUSTIBLE MATERIALS; (2) FIRE-RETARDANT TREATED WOOD WITHIN ASSEMBLIES OF ONE-HOUR MAXIMUM RATING. (B) IN BUILDINGS OF TYPE III-A CONSTRUCTION PARTITION FRAMING SHALL BE OF HEAVY TIMBER CONSTRUCTION PROVIDING FIRE RESISTANCE AS REQUIRED FOR FLOOR CONSTRUCTION OR ROOF CONSTRUCTION ABOVE OR SHALL BE OF NONCOMBUSTIBLE MATERIALS OR FIRE-RETARDANT TREATED WOOD WITHIN A ONE-HALF-HOUR TO ONE-HOUR FIRE-RATED ASSEMBLY. (C) IN BUILDINGS OF TYPES III-B AND IV-A CONSTRUCTION, PARTITIONS SHALL BE OF EITHER OF THE FOLLOWING TYPES: (1) COMBUSTIBLE CONSTRUCTION PROTECTED TO PROVIDE FIRE RESISTANCE OF NOT LESS THAN ONE-HALF HOUR; (2) NONCOMBUSTIBLE CONSTRUCTION. 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE ---STARBUCKS REAR EXIT IMPROPER GRADINGBOOKMARK13-160-430 RAMPS. RAMPS REQUIRED AS A MEANS OF EXIT SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS FOR INTERIOR STAIRS AND WITH THE PROVISIONS OF SECTIONS 13-160-440 TO 13-160-460, INCLUSIVE.(PRIOR CODE § 67-12)BOOKMARK13-160-440 RAMPS ¿ GRADES. RAMPS USED IN LIEU OF STAIRS SHALL HAVE A GRADE OF NOT MORE THAN ONE IN EIGHT. RAMPS USED IN LIEU OF STAIRS IN PUBLIC BUILDINGS AS DEFINED IN SECTION 13-4-010 OF THIS CODE SHALL HAVE A GRADE OF NOT MORE THAN ONE IN 12. PANECALDO REAR EXIT TRIP HAZARD BOOKMARK13-160-070 OBSTRUCTIONS PROHIBITED. FOR PURPOSES OF THIS SECTION AND SECTION 13-96-135 ONLY: THE TERM ¿SMALL BUILDING¿ SHALL MEAN A RESIDENTIAL BUILDING THAT IS BOTH LESS THAN FOUR STORIES HIGH AND CONTAINS FEWER THAN FOUR RESIDENTIAL UNITS; AND THE TERM ¿LARGE BUILDING¿ SHALL MEAN A RESIDENTIAL BUILDING THAT IS FOUR OR MORE STORIES HIGH, OR CONTAINS FOUR OR MORE RESIDENTIAL UNITS, OR BOTH. THERE SHALL BE NO OBSTRUCTION IN ANY EXITWAY THAT MAY HAMPER TRAVEL AND EVACUATION. THIS SECTION DOES NOT PROHIBIT THE LOCKING OF A GATE IN A FENCE THAT SECURES A RESIDENTIAL BUILDING: (A) FROM EITHER OR BOTH FACES OF THE GATE IN THE CASE OF A SMALL BUILDING, OR (B) FROM THE EXTERIOR FACE OF THE GATE IN THE CASE OF A LARGE BUILDINGSO LONG AS THE LOCKED GATE DOES NOT PREVENT EGRESS FROM THE BUILDING TO THE EXTERIOR. 111 E CHESTNUT ST COMPLAINT FAILED View
ADDITIONAL EXIT BAR TOMA EXIT INTO GARAGE BEING ELIMINATED BECAUSE IT IS CONTRARY TO CODE---SECTION 13-56-280. 111 E CHESTNUT ST COMPLAINT FAILED View
2-HR STAIR ENCLOSURE, 4+ STORY SOUTH STAIRWELL FIRST TO SECOND FLOOR---PLYWOOD PARTITIONS 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE ---TRASH ROOM ADDITIONAL SPRINKLER HEADS PER : BOOKMARK15-8-170 ENCLOSURE OF WELLS AND CHUTES. WELLS, CHUTES AND SIMILAR OPENINGS THROUGH A FLOOR SHALL BE ENCLOSED WITH CONSTRUCTION PROVIDING FIRE RESISTANCE OF NOT LESS THAN ONE HOUR, EXCEPT THAT ENCLOSURE OF WELLS SHALL NOT BE REQUIRED WHERE OPEN STAIRWAYS ARE PERMITTED. (A) IN ALL BUILDINGS EXCEEDING THREE STORIES IN HEIGHT AND IN INSTITUTIONAL BUILDINGS EVERY LAUNDRY AND RUBBISH CHUTE ENCLOSURE SHALL BE OF NOT LESS THAN TWO- HOUR FIRE-RESISTIVE CONSTRUCTION. THE MINIMUM INSIDE DIMENSIONS OF THE CHUTE SHALL BE 18 INCHES. ALL CHUTES SHALL DISCHARGE DIRECTLY INTO A ROOM HAVING WALLS, CEILING AND FLOOR OF TWO-HOUR FIRE-RESISTIVE CONSTRUCTION USED SOLELY FOR THE RECEPTION OF LAUNDRY OR RUBBISH. THE ROOM SHALL BE EQUIPPED WITH ONE SPRINKLER HEAD FOR THE FIRST 130 SQUARE FEET OF FLOOR AREA AND ONE ADDITIONAL HEAD FOR EACH ADDITIONAL 130 SQUARE FEET OR LESS. ONE SPRINKLER HEAD SHALL BE INSTALLED IN THE CHUTE AT THE TOP SERVICE OPENING; AND ONE ADDITIONAL SPRINKLER HEAD AT EVERY SECOND FLOOR LEVEL BELOW THE TOP FLOOR. A SELF- CLOSING ONE AND ONE-HALF-HOUR CLASS B LABELED FIRE DOOR ASSEMBLY SHALL BE INSTALLED AT THE SERVICE OPENING AT EACH LEVEL AND AT THE BOTTOM OF THE CHUTE AND IN THE SERVICE DOOR OPENING OF THE ROOM INTO WHICH THE LAUNDRY OR RUBBISH IS DISCHARGED. NO LAUNDRY OR RUBBISH CHUTE SHALL BE LOCATED IN ANY STAIRWELL NOR WITHIN TEN FEET OF ANY OPEN STAIRWAY. THE CHUTE SHALL EXTEND NOT LESS THAN FOUR FEET ABOVE THE ROOF, AND SHALL BE COVERED WITH A METAL SKYLIGHT AND PLAIN GLASS OR ANY APPROVED AUTOMATIC VENTING DEVICE. (B) EVERY REFUSE CHUTE ENCLOSURE LOCATED OUTSIDE OF A BUILDING SHALL BE CONSTRUCTED OF AT LEAST 16 U.S. GAUGE METAL WITH A MINIMUM DIMENSION OF AT LEAST 18 INCHES. A CLEARANCE OF AT LEAST SIX INCHES SHALL BE PROVIDED BETWEEN THE CHUTE AND ANY COMBUSTIBLE MATERIAL; PROVIDED, HOWEVER, THAT THIS CLEARANCE MAY BE REDUCED TO THREE INCHES WHERE THE SPACE BETWEEN THE CHUTE AND COMBUSTIBLE MATERIAL IS PROTECTED BY THREE INCHES OF TILE, CELLULAR ASBESTOS BOARD OR SOME SIMILAR FIRE-RESISTIVE MATERIAL. THE BOTTOM OF THE CHUTE SHALL DISCHARGE DIRECTLY INTO A METAL OR OTHER NONCOMBUSTIBLE RECEPTACLE WHICH WILL BE MAINTAINED CLOSED AT ALL TIMES. (C) IN NURSING HOMES, HOSPITALS AND SHELTERED CARE FACILITIES, NO CHUTES SHALL OPEN DIRECTLY ON ANY CORRIDOR BUT SHALL BE IN A SEPARATE ROOM OF ONE-HOUR FIRE-RESISTIVE CONSTRUCTION AND THE DOOR OPENING SHALL BE PROTECTED WITH A SELF-CLOSING ONE-AND-ONE-HALF-HOUR CLASS B LABELED FIRE DOOR ASSEMBLY. 111 E CHESTNUT ST COMPLAINT FAILED View
REPAIR OR REPLACE BAR TOMA---DEFECTIVE EMERGENCY LIGHTS; EXIT AND/OR DIRECTIONAL SIGNS HAVE NO BATTERY BACKUP; TRASH ROOM BY BIKE ROOM EMERGENCY LIGHT NOT WORKING; 54N,48S,43N,39N,31N---EMERGENCY LIGHTS NOT WORKING. STAIRWELLS AT:54N,50S,46N,42S,29N,20N,16S,15S,11N--STAIR LIGHTS NOT WORKING 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE BOOKMARK15-8-570 FIRESTOPPING. FIRESTOPPING, COMPLYING WITH THE PROVISIONS OF SECTIONS 15-8-580 TO 15-8-640, INCLUSIVE, SHALL BE DESIGNED AND CONSTRUCTED TO CLOSE ALL CONCEALED DRAFT OPENINGS AND TO FORM EFFECTIVE FIRE BARRIERS BETWEEN STORIES OF EVERY BUILDING AND IN ALL CONCEALED SPACES THEREIN AGAINST THE SPREAD OF FIRE.(PRIOR CODE § 62-12; AMEND COUN. J. 6-14-95, P. 2841)FIRESTOP ALL PENETRATIONS AT BUT NOT LIMITED TO: BOILER ROOM, MECHANICAL ROOMS, STORAGE ROOMS, STAIRWELLS, MAINTENANCE BREAK ROOM AND SHOP, SMOKE LOBBIES, GARAGE, CORIDORS, METER ROOMS, ELEVATOR ROOMSBOOKMARK15-8-580 MATERIALS. ALL FIRE-STOPPING SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS, EXCEPT THAT FIRE-STOPPING OF WOOD NOT LESS THAN TWO INCHES IN NOMINAL THICKNESS SHALL BE PERMITTED IN OPEN SPACES OF WOOD FRAMING. 111 E CHESTNUT ST COMPLAINT FAILED View
NO KEY TO USE EXIT DOOR ROOF USE OF KEY TO EXIT 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE OPENINGS IN SHAFT IN METER ROOMS: IF THE SHAFT IS FOR PIPES:BOOKMARK15-8-160 ENCLOSURE OF PIPE SHAFTS AND DUCTS. PIPE SHAFTS AND DUCTS PASSING FROM ONE FLOOR TO ANOTHER SHALL BE ENCLOSED WITH CONSTRUCTION PROVIDING FIRE RESISTANCE OF NOT LESS THAN ONE HOUR EXCEPT THAT PIPES AND DUCTS REQUIRING OPENINGS THROUGH FLOORS NOT EXCEEDING NINE SQUARE FEET IN AREA SHALL NOT REQUIRE ENCLOSURE; PROVIDED, THAT OPENINGS BETWEEN SUCH PIPES OR DUCTS AND THE FLOOR CONSTRUCTION SHALL BE FILLED WITH NONCOMBUSTIBLE MATERIALS SECURELY HELD IN PLACE TO PREVENT THE PASSAGE OF FIRE. -----IF THE SHAFT IS AN ELECTRICAL RISER SHAFT: BOOKMARK13-76-080 EMERGENCY ELECTRICAL SYSTEMS. EMERGENCY ELECTRICAL SYSTEMS SHALL BE PROVIDED IN BUILDINGS AS FOLLOWS: (A) ALL BUILDINGS INCLUDED IN THIS CHAPTER SHALL BE SUPPLIED BY A SYSTEM 2 EMERGENCY SYSTEM THAT SHALL SUPPLY THE ELEVATOR REQUIRED BY SECTION 13-76-130 OF THIS CODE, ALL EMERGENCY AND EXIT LIGHTS, THE COMMUNICATION SYSTEMS REQUIRED BY SECTION 13-76-050 OF THIS CODE, THE FIRE COMMAND PANEL REQUIRED BY SECTION 13-76-030 OF THIS CODE, AND THE FIRE ALARM SYSTEM REQUIRED BY SECTION 13-76-040 OF THIS CODE. THE SYSTEM 2 EMERGENCY SYSTEM SHALL CONFORM WITH ALL APPLICABLE PROVISIONS OF SECTION 14-48-010* OF THIS CODE.* EDITOR'S NOTE ¿ COUN. J. 11-3-99, P. 13842, § 5, REPEALED TITLE 14, WHICH PERTAINED TO ELECTRICAL EQUIPMENT AND INSTALLATION, WITH THE EXCEPTION OF CH. 14-46, WHICH WAS RENUMBERED AS CH. 4-400 AND ALSO AMENDED. (B) ALL BUILDINGS OVER 400 FEET ABOVE GRADE SHALL HAVE A DIESEL DRIVEN EMERGENCY GENERATOR TO SUPPLY THE FIRE PUMPS REQUIRED BY SECTIONS 15-16-770 AND 15-16-780 OF THIS CODE AND THE ELEVATOR REQUIRED BY SECTION 13-76-130 OF THIS CODE. THE FIRE PUMP MAY BE DIESEL ENGINE OPERATED. (C) EMERGENCY GENERATORS, FIRE PUMPS AND THEIR CONTROLS ARE TO BE IN A SEPARATE TWO-HOUR-FIRE-RATED PUMP ROOM WHICH ALSO MAY CONTAIN THE DOMESTIC BOOSTER PUMPS. IN ADDITION, THE ELECTRICAL CONTROLS ARE TO BE ENCASED IN DRIP PROOF ENCLOSURES. (D) ALL MAIN ELECTRIC SERVICE EQUIPMENT SHALL BE INSTALLED IN VAULTS OR APPROVED OUTDOOR LOCATIONS. THE MAIN ELECTRIC SERVICE VAULTS AND MAIN SERVICE SWITCH ROOMS SHALL BE ENCLOSED WITH THREE-HOUR-FIRE-RATED CONSTRUCTION. DISTRIBUTION SWITCHBOARD ROOMS SHALL BE ENCLOSED WITH TWO-HOUR-FIRE-RATED CONSTRUCTION. (E) ALL ELECTRIC SERVICE VAULTS AND MAIN SERVICE SWITCHBOARD ROOMS LOCATED ON THE LOWEST LEVEL SHALL BE EQUIPPED WITH A SUMP PUMP CONNECTED TO THE EMERGENCY ELECTRICAL SUPPLY. (F) ALL ELECTRIC RISERS AND SHAFTS SERVING ELEVATORS, EMERGENCY AND EXIT LIGHTS, VOICE COMMUNICATION SYSTEMS AND SMOKE CONTROL FANS ARE TO BE ENCLOSED WITH TWO-HOUR CONSTRUCTION AND ARE TO INCLUDE CONTINUOUS THREE-INCH-HIGH WATER STOPS ON ALL SIDES. MINERAL INSULATED CABLE HAVING A TWO-HOUR FIRE RESISTIVE CLASSIFICATION FROM A RECOGNIZED THIRD-PARTY ELECTRICAL TESTING LABORATORY SHALL BE ACCEPTABLE IN RETROFIT WORK, PROVIDED THAT DISTRIBUTION PANELS AND CONTROL PANELS ARE ENCLOSED WITH CONSTRUCTION PROVIDING TWO-HOUR PROTECTION. (G) ALL EXISTING AND NEWLY CONSTRUCTED BUILDINGS USED IN WHOLE OR IN PART FOR RESIDENTIAL OCCUPANCY WHICH ARE MORE THAN 80 FEET ABOVE GRADE, SHALL PROVIDE AN AUXILIARY SOURCE OF CURRENT SUPPLY FROM EITHER AN APPROVED, ON-SITE GENERATOR IN ACCORDANCE WITH SECTION 14-48-100*, AN APPROVED CENTRAL BATTERY SYSTEM, OR APPROVED UNIT BATTERY FIXTURES IN ACCORDANCE WITH SECTION 14-48-090(B) AND (C)* TO SUPPLY ALL REQUIRED EMERGENCY LIGHTS THROUGHOUT THE BUILDING. THE FUEL SOURCE FOR ON-SITE GENERATORS INSTALLED IN BUILDINGS OVER 80 FEET IN HEIGHT AND UNDER 400 FEET IN HEIGHT MAY BE NATURAL GAS OR DIESEL FUEL. THE FUEL FOR ON-SITE GENERATORS INSTALLED IN BUILDINGS OVER 400 FEET IN HEIGHT SHALL BE DIESEL, IN ACCORDANCE WITH THE PROVISIONS OF SECTION 13-76-080(B) OF THIS CODE. 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE -----SMOKE VESTIBULES AT ALL FLOORS HAVE ONE HOUR OF FIRE PROTECTIONBOOKMARK13-160-380 SMOKEPROOF TOWERS ¿ VESTIBULES AND BALCONIES. ACCESS TO THE STAIRWAY AT EACH STORY SHALL BE THROUGH A VESTIBULE OR BALCONY COMPLYING WITH THE FOLLOWING REQUIREMENTS: (A) EXCEPT WHEN AN INTERIOR SMOKE SHAFT IS PROVIDED, THE VESTIBULE OR BALCONY SHALL BE LOCATED ON AN EXTERIOR WALL NOT SUBJECT TO A SEVERE FIRE EXPOSURE HAZARD. (B) EVERY VESTIBULE OR BALCONY SHALL HAVE AN OPENING TO A PUBLIC WAY, YARD OR COURT OR TO AN INTERIOR SMOKE SHAFT COMPLYING WITH THE REQUIREMENTS OF SECTION 13-160-420. (C) SUCH OPENINGS SHALL HAVE AN AREA NOT LESS THAN ONE-HALF THE AREA OF THE EXIT DOORS LEADING FROM THE BUILDINGS TO THE VESTIBULE OR BALCONY AND SHALL BE LOCATED NOT LESS THAN FOUR FEET ABOVE THE FLOOR AND NOT MORE THAN SIX INCHES BELOW THE CEILING OF THE VESTIBULE OR BALCONY. UNLESS SUCH OPENING FACES A PUBLIC WAY, YARD OR COURT NOT LESS THAN 40 FEET WIDE, THE OPENING SHALL BE PROTECTED WITH A FIRE SHIELD COMPLYING WITH THE REQUIREMENTS OF SECTION 13-160-390. IN ANY CASE, THE YARD OR COURT SHALL HAVE A MINIMUM WIDTH OF 20 FEET AND A MINIMUM AREA OF 400 SQUARE FEET. (D) THE FLOORS, WALLS AND CEILINGS OF ALL VESTIBULES OR BALCONIES SHALL BE OF CONSTRUCTION PROVIDING FIRE PROTECTION OF NOT LESS THAN THREE HOURS. 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA PROVIDE SIGNAGE ON MACHINE ROOM DOOR 111 E CHESTNUT ST COMPLAINT PASSED View
ARRANGE ANNUAL INSP. 13-20-290, 13-20-020,ARRANGE FOR ANNUAL INSPECTION OF VENTILATION EQUIPMENT 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN MECH. VENT SYSTEM APPLICABILITY 18-28-102 MAINTAIN MECHANICAL=AL VENTILATION EQUIPMENT IN GOOD REPAIR AND OPERATED TO PROVIDE ADEQUATE VENTILATION DURING HOURS OF OCCUPATION 111 E CHESTNUT ST COMPLAINT FAILED View
BLANK-TEXT MUST CITE CODE SECT STOP ALL WORK ON PREMISES UNTIL PLANS ARE APPROVED AND PERMIT IS OBTAINEDSECTION 12-080, 13-32-035. 111 E CHESTNUT ST COMPLAINT FAILED View
PLANS & PERMITS REQ - CONTRCTR STRUCTURAL CONCRETE AND REBAR REPAIRS TO DECKS AND WALLSREPAIR WORK TO AMELIORATE CONCRETE CONTAMINATION 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL CATWALK IN ELEVATOR PIT. (OVER 10" ) 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA DRILL HOLES IN EMERGENCY BRAKE ARM FOR LOCK OUT TAG 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA DO A COMPLETE EMERGENCY POWER TEST AND FIRE SERVICE TEST WITH SMOKE DETECTORS. 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA FAID'S NOT TESTED 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA EXTEND HAND HOLD ON PIT LADDERS 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA DOUBLE NUT COUNTER WEIGHT TIE DOWNS. 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL CAT-WALKS IN PITS FOR BOTTOM OF CAR ACCESS. 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA DETERMINE IF MACHINE ROOM WALL INSULATION IS FIREPROOF. 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE A GFI OUTLET BETWEEN CONTROLLERS. 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA INSTALL PROPER VENTILATION AC UNIT IN MACHINE ROOM 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA DO COMPLETE FIRE SERVICE TEST 111 E CHESTNUT ST PERMIT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA NOT READY RE-SCHEDULE 111 E CHESTNUT ST PERMIT PASSED View
FIRE EXTNGSHR RECHARGE & TAG VARIOUS LOCATIONS THROUGHOUT THE PARKING GARAGE - FIRE EXTINGUISHER RECHARGE TAGS EXPIRED - BUILDING CODE SECTIONS (14X-5-504.5, 14B-9-906.2 AND NFPA 10) 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN EXIT SIGN ILLUMINATED EXIT SIGNS AND DIRECTIONAL SIGNS NOT ILLUMINATED - BUILDING CODE SECTIONS(14X-5-505.13 AND 14B-10-1013) 111 E CHESTNUT ST COMPLAINT FAILED View
BUILDING IN DISREPAIR INTERIOR OF PARKING STRUCTURE FLOORS 1 THROUGH 8 -(1) FIRST THROUGH FIFTH FLOORS CEILINGS WEST END COUNTERLEVERED CONCRETE SLABS - HORIZONTAL CRACKS OBSERVED SPANNING FROM NORTH TO SOUTH ALONG THE WEST EDGE OF THE COLUMNS DROP PANELS(2) NORTHWEST COLUMNS AT FIRST, SECOND AND THIRD FLOORS - CONCRETE DROP PANELS ABOVE EXHIBIT WIDE CRACKS WHERE THEY CONNECT TO THE CONCRETE SLAB(3) VARIOUS COLUMNS UPPER DROP PANELS - WIDE OPEN STRUCTURAL FRACTURES SPANNING FROM COLUMN TO EDGE OF PANEL(4) THREE LOCATIONS AT CEILINGS - APPROXIMATELY 36 INCHES LONG BY 24 INCHES WIDE SEVERELY SPALLED CONCRETE WITH EXPOSED STEEL TENSION REINFORCEMENT BARS(5) NORTH AND SOUTH EXTERIOR WALLS ADJACENT TO CENTRAL CANTILEVERED SLAB EDGES - SPALLED CONCRETE CORNERS WITH EXPOSED STEEL REINFORCEMENT BARS(6) ALL LEVELS DRIVE AISLE FLOORS IN VARIOUS LOCATIONS - POTHOLES RECENTLY FILLED WITH ASPHALT(7) ALL LEVELS DRIVE AISLE AND PARKING FLOORS AT VARIOUS LOCATIONS - CRACKS WITH BROKEN AND LOOSE ASPHALT(8) LEVEL 7B CEILING AT DRAIN PIPE PENETRATION BELOW THE BOILER ROOM - CRACKED AND SPALLING CONCRETE WITH LIQUID DRIPPING FROM PIPE(9) VARIOUS SLAB EDGES ABOVE RAMPS - CRACKS(10) VARIOUS RAMP EXPOSED CONCRETE EDGES - CRACKS(11) DRAWINGS REQUIRED TO OBTAIN A PERMIT FOR IMMEDIATE TEMPORARY STRUCTURAL SHORING OF ALL PARKING LEVELSBUILDING CODE SECTIONS 14X-3-305.1, 14X-3-305.1.1 111 E CHESTNUT ST COMPLAINT FAILED View
SUBMIT 2 COPIES CRITICAL EXAM SUBMIT CRITICAL EXAM REPORT FOR THE EXISTING HIGH-RISE PARKING GARAGE SECTION OF BUILDING BY A REGISTERED DESIGN PROFESSIONAL. THE EXAM IS A CLOSE-UP VISUAL EXAMINATION OF THE ENTIRE EXTERIOR ENVELOPE IS TO IDENTIFYING DEFICIENCIES AND DETERMINE IF REPAIR IS REQUIRED. EXTERIOR ENVELOPE TO INCLUDE BUT NOT LIMITED TO ROOF, EXTERIOR WALLS, WINDOWS, DOORS, BALCONIES, FIRE ESCAPES, CHIMNEYS, MECHANICAL EQUIPMENT, MARQUEES, CANOPIES, SIGNS, FLAG POLES AND EXTERIOR MAINTENANCE SYSTEMS. A SIGNED AND SEALED REPORT, DETAILING THE SCOPE AND FINDINGS OF THE EXAMINATION, TOGETHER WITH RECOMMENDATIONS FOR REPAIR WHERE DEFICIENCIES ARE FOUND, SHALL BE PROVIDED TO THE OWNER AND FILED WITH THE BUILDING DEPARTMENT. IT IS THE OWNER'S RESPONSIBILITY TO OBTAIN REQUIRED PERMITS, ACCOMPANIED BY SUPPORTING DOCUMENTS AND CONSTRUCTION DOCUMENT PLANS. THE OWNER MUST KEEP A COPY OF THE MOST RECENT REPORT, PERMIT AND CONSTRUCTION DOCUMENTS ON FILE AT THE PREMISES AND MAKE AVAILABLE FOR INSPECTION REVIEW AND APPROVAL. SEE MAINTENANCE OF HIGH-RISE EXTERIOR WALLS AND ENCLOSURES RULES AND REGULATIONS. SUBMIT TO DEPARTMENT OF BUILDINGS, ATTENTION: EXTERIOR WALL PROGRAM 3RD FLOOR, 2045 W. WASHINGTON BLVD. 60612 (14A-6-603.2 THROUGH 14A-6-603.2.6, 14A-4-401.1 AND 14A-4-411.1) 111 E CHESTNUT ST COMPLAINT FAILED View
SUBMIT 2 COPY STRUCTURAL RPT SUBMIT CONDITION ASSESSMENT REPORT FOR ENTIRE PARKING STRUCTURE FLOORS 1 THRU 8. REPORT SHALL BE SIGNED AND SEALED BY A REGISTERED DESIGN PROFESSIONAL, AND BASED ON A CRITICAL, COMPREHENSIVE, AND DETAILED PHYSICAL INSPECTION OF THE PREMISES IDENTIFIED AND DETAILED IN THE VIOLATION. THE CONDITION REPORT MUST IDENTIFY THE DATE, NATURE, SCOPE, FINDINGS, AND DEFICIENCIES OF THE INSPECTION/INVESTIGATION. THE REPORT MUST IDENTIFY EACH TECHNICAL PRINCIPLE OR STANDARD THAT IS THE BASIS OF ANY PROFESSIONAL JUDGMENT AND COMPREHENSIVE RECOMMENDATIONS FOR REPAIRS EXPRESSED IN THE REPORT. RECOMMENDATION OF REPAIRS MUST INCLUDE PHOTOS, DRAWINGS, DETAILS, AND CALCULATIONS WHICH CAN BE SUBMITTED FOR A REPAIR PERMIT IF NECESSARY. THE CONDITION REPORT, PERMIT, AND CONSTRUCTION DOCUMENTS MUST BE KEPT ON FILE AT THE PREMISES AND MADE AVAILABLE FOR FIELD INSPECTION REVIEW AND APPROVAL BY ALL RELATED TRADES. SUBMIT ELECTRONIC REPORT FOR REVIEW AND APPROVAL TO: DOB_CAR@CITYOFCHICAGO.ORG (14X-1-104.1 THRU 14X-1-104.4, 14A-6-603.5, AND 14A-4-411.1) 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA SHOW PROOF OF FINAL INSPECTION OR CALL FOR FULL INSPECTION AND FIRE SERVICE TEST 111 E CHESTNUT ST PERMIT CLOSED View
PROVIDE PROVIDE FOR (1) EXHAUST NEEDS TO RUN CONTINUOUSLY IN THE GARAGE RUN ON A TIME WITH A C/O SYSTEM! 111 E CHESTNUT ST COMPLAINT PASSED View
ARRANGE COMPLETED PERMIT INSP. 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN OR REPAIR ELECT ELEVA PROVIDE FIRE SERVICE KEY BOX NEAR ELEVATOR LOBBY PANEL 111 E CHESTNUT ST PERMIT FAILED View
ARRANGE PERMIT INSP. 111 E CHESTNUT ST PERMIT FAILED View
BLANK-TEXT MUST CITE CODE SECT SEAL OPENING FROM BAR TOMA INTO GARAGE---IT IS NOT ALLOWED PER: SECTION 13-56-280 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE CLASS A FIRE DOOR GARAGE LOCATION-1BS- 'B' LABEL DOOR; FIRST FLOOR GARAGE TO BUILDING MISSING LEVATOR LOBBY; FIRST FLOOR STAIRWELL EXIT INTO GARAGE-MISSING FIRE LOBBY SEPARATION 111 E CHESTNUT ST COMPLAINT FAILED View
OBSTRUCTIONS IN EXIT WAY METAL BOXES BLOCKING EGGRESS IN SATIRWELLS AT: 12S,37S,32S,26S,20S; APARTMENT 41K---REAR DOOR SEALED 111 E CHESTNUT ST COMPLAINT FAILED View
1HR PUB.CORRIDOR IN MULT. D.U. PLASTIC ACCESS PANELS AT: 54 FLOOR,28 FLOOR; CORRIDORS VENTS AT ALL FLOORS IN METER ROOMS 111 E CHESTNUT ST COMPLAINT FAILED View
PROVIDE ---MAINTENANCE SHOP EXPOSED STEEL BEAMS---SECTION 13-60-100 111 E CHESTNUT ST COMPLAINT FAILED View
MAINTAIN OR REPAIR HYDRO ELEVA ELEVATOR #13 REPAIR REAR WALL CAR HITTING HOISTWAY 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA ELEVATOR #13 INSTALL CAR NUMBERS ON LEFT JAMB AND CAR STATION 111 E CHESTNUT ST COMPLAINT PASSED View
MAINTAIN OR REPAIR HYDRO ELEVA FINISH LOBBY PANEL INSTALLATION WITH #13 CAR 111 E CHESTNUT ST PERMIT PASSED View