The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
Violation | Inspector Comments | Address | Category | Status | View |
---|---|---|---|---|---|
ENCLOSE ELE H/W 2 HR FIRE | #3 CAR. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
INST XHEAD ROPE DATA PLATE P | #3 CAR. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
BEVEL H/W LEDGES | #3 CAR. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
REP/REPL FIRE RECALL PASS | FULLY TEST FIREMANS SERVICE UPON COMPLETION OF MODERNIZATION. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | 1. REMOVE ALL PIPING FROM ELEVATOR HOISTWAY NOT ELEVATOR RELATED (WATER & GAS PIPES). 2. PROVIDE MASTER LOBBY PANEL WITH CENTRAL MONITORING. 3. PROVIDE LADDER LEADING TO SECONDARY DECK #3CAR. 4. PROVIDE STOP SWITCH IN SECONDARY DECK IN SERIES WITH #3 CAR SAFETY CIRCUIT. 5. PROTECT MACHINE ROOM LIGHTING #3CAR. 6. PROVIDE CABLE GUARD #3 CAR MACHINE. 18-30-010, 13-20-120 100299974 | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
PROVIDE MINIMUM VENT QUANTITY | SUPPLY/EXHAUST UNIT SERVING SPACES IS UNDERSIZED AND MUST BE INCREASED AS PREVIOUSLY NOTED MUST MEET MINIMUM ORDINANCE REQUIRED CFM OF OUTSIDE AIR AND POWER EXHAUST 18-28-403 18-28-403.3 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
PROVIDE SUPPLY | PROVIDE MINIMUM ORDINANCE REQUIRED C.F.M. TO SUPPLY UNIT 18-28-403.3 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
GIVE VENT OPENINGS % FL. AREA | EXHAUST MINIMUM ORDINANCE REQUIRED C.F.M. THRU UNIT POWER EXHAUSTER 18-28-403.3 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
OUTSIDE AIR 15FT | SEPARATE OUTSIDE AIR INTAKE AND EXHAUST BY MIN. 15FT 18-28-401.5.2 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | ARRANGE FINAL INSPECTION WHEN CORRECTED 13-12-100 13-20-290 13-32-270 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
OPEN TYPE VIOLATION | PIPE LIGHTS ON CAR TOP OUTLET FOR LIGHT ON THE ESCAPE HATCH. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | (VT 1014) AIR TAKE AND EXHAUST MUST BE SIZED CORRECTLY TO PROVIDE MIN 100% CODE REQUIRED SUPPLY/EXHAUST 18-28-401.6 | 3170 N SHERIDAN RD | COMPLAINT | FAILED | View |
OPEN TYPE VIOLATION | PATCH ALL FLOORS IN ELEVATOR MACHINE ROOM. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PATCH ALL HOLES IN ELEVATOR HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | FULLY TEST FIRE SERVICE AND SMOKES DETECTOR & FLOW SWITCHES. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | ADD LIGHTS TO MACHINE ROOM & COVER ALL LIGHTS. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PIPE LIGHTS ON CAR TOP OUTLET FOR LIGHT ON THE ESCAPE HATCH. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | BEVEL ALL LEDGES IN HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | SECURE COMP CHAIN. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | REMOVE OLD 110V IN HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | FINISH ALL FLOORS AND SILLS. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | BUILD RAILS AROUND MACHINE ROOM DECK. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | REPLACE MACHINE ROOM DOOR 2HOUR FIRE RATED. | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | NEW ROPES ON CAR #5 & PUT CWT ROD BACK IN BALANCE CAR. 18-30-010, 13-20-120. 100299980 | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
OPEN TYPE VIOLATION | PATCH ALL FLOORS IN ELEVATOR MACHINE ROOM. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | PATCH ALL HOLES IN ELEVATOR HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | FULLY TEST FIRE SERVICE AND SMOKES DETECTOR & FLOW SWITCHES. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | ADD LIGHTS TO MACHINE ROOM & COVER ALL LIGHTS. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | BEVEL ALL LEDGES IN HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | SECURE COMP CHAIN. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | REMOVE OLD 110V IN HOISTWAY. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | FINISH ALL FLOORS AND SILLS. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | BUILD RAILS AROUND MACHINE ROOM DECK. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | REPLACE MACHINE ROOM DOOR 2HOUR FIRE RATED. | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
OPEN TYPE VIOLATION | COMPLETE MODERNIZATION UNDER PERMIT #100299974 INCLUDING ALL ITEMS CITED ON 1/4/11 INSPECTION CALL THIS BUREAU FOR RE-INSPECTION. 18-30-010, 13-20-120. #100299974 | 3170 N SHERIDAN RD | PERMIT | FAILED | View |
ARRANGE COMPLETED PERMIT INSP. | 3170 N SHERIDAN RD | PERMIT | PASSED | View | |
ARRANGE FOR RE-INSPECTION | NEED PRV'S IN REFRIGERATION EQUIPMENT | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
HOISTNG OVER PUB WAY NO PERMIT | 3170 N SHERIDAN RD | COMPLAINT | CLOSED | View | |
HOISTNG OVER PUB WAY NO PERMIT | LIABLE | 3170 N SHERIDAN RD | COMPLAINT | CLOSED | View |
SEND EX. METAL LETTER | 3170 N SHERIDAN RD | COMPLAINT | PASSED | View | |
OPEN TYPE VIOLATION | NEW ROPES ON CAR #5 & PUT CWT ROD BACK IN BALANCE CAR. 18-30-010, 13-20-120. 100299980 | 3170 N SHERIDAN RD | PERMIT | PASSED | View |
EMPLOYER NO CRANE LISC | LIABLE - BY PLEA | 3170 N SHERIDAN RD | COMPLAINT | CLOSED | View |
EMPLOYER NO CRANE LISC | 3170 N SHERIDAN RD | COMPLAINT | CLOSED | View |