The Open Source Data Files that are here are from Cook County.
This Page is a combination of all Files.
The Parcel Universe and most other Cook County files are categorized by PIN and Tax Year.
This page is PIN ONLY. You can expand this page (at the bottom) to see lists of all files related to this Pin.
The 2023 Data is from the Parcel Universe File with Tax_Year = 2023.
| Violation | Inspector Comments | Address | Category | Status | View |
|---|---|---|---|---|---|
| MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS: WORKING PIT LIGHTS AND ACCESSIBLE LIGHT SWITCHES REQUIRED. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS: OBTAIN REQUIRED PERMIT AND MAKE CHANGES TO CONFORM WITH 2017 FIRE SERVICE MANDATE (18-30-320) | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | 4 FIRE SERVICE KEYS REQUIRED IN FIREMAN'S KEY BOX. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| OPEN TYPE VIOLATION | PERFORM PRESSURE TEST ON ALL ELEVATOR; TAG & SEAL VALUES; SUBMIT REPORTS TO CITY. (18-30-010,13-20-120) EV000824 | 2432 N CENTRAL AVE | PERIODIC | CLOSED | View |
| REMOVE DEBRIS FROM PIT PASS | ALL CARS | 2432 N CENTRAL AVE | PERIODIC | CLOSED | View |
| OPEN TYPE VIOLATION | 1. REPAIR OR REPLACE NON-WORKING DOOR RESTRICTORS ON ALL ELEVATORS. 2. REPAIR OR REPLACE NON WORKING EMERGENCY PHONE IN ALL ELEVATORS. 3. REPAIR OR REPLACE NON WORKING SWITCH ON DUMBWAITER PIT DOOR. 4. CLEAN ALL ELEVATOR PITS REMOVE WATER & OIL AND CHECK FOR LEAKS REPAIR AS NEEDED. 5. PROVIDE CERTIFICATES FRAMES FOR DUMBWAITER, AND ELEVATORS. 6. REPAIR OIL LEAK IN TANK #3 ELEVATOR. 18-30-010, 13-20-120. EV000824. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | CLEAN AND REMOVE ALL OIL AND WATER IN ALL THREE PITS | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE SUMP PUMP COVER INBETWEEN CAR ! AND 2. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR OR REPLACE ALL DOOR RESTRICTORS. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR PHONE ON CAR #1 (FRIEGHT) FOR PROPER 2 WAY 24 HOUR COMMUNICATION. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPAIR BROKEN UP BOTTON ON 4TH FLOOR HALL BOTTON CARS 2&3. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | FURNISH PROOF OF WHEN ALL JACKS WERE INSTALLED TO MEET CITY BULK HEAD REQUIRMENTS. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL BRAIL PLATES ALL CARS AS NEEDED. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL CAR ID TAGS ALL CARS ALL FLOORS AS NEEDED. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | INSTALL CAR ID TAGS IN ALL ELEVATORS. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPROGRAM PHONES FOR PROPER OPERATION. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS; CLEAN CARTOPS, INSTALL COVERS ON CARTOP DEVICES, AND REMOVE DOOR RESTRICTOR PARTS NO LONGER IN USE. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATORS 1 AND 2: REPAIR MALFUNCTIONING DOOR RESTRICTORS. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ELEVATOR 1: INSTALL A CARTOP HAND RAIL. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | A CURRENT FIRE SERVICE TEST LOG IS REQUIRED ON SITE. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR DUMBWTR | REPAIR AND MAINTAIN DUMBWAITER OR OBTAIN A PERMIT TO DECOMMISSION. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS: CLEAN ELEVATOR PITS. | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR ELECT ELEVA | DUMBWAITER -PASS | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | ALL ELEVATORS: OBTAIN REQUIRED PERMIT AND MAKE CHANGES TO CONFORM WITH 2017 FIRE SERVICE MANDATE (18-30-320):PREVIOUSLY WRITTEN | 2432 N CENTRAL AVE | PERIODIC | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | CAR #1 NOT RESPONDING TO PHASE1 KEY SWITCH.PERFORM COMPLETE FIRE SERVICE MANDATE INSPECTION ON CAR #1. | 2432 N CENTRAL AVE | PERMIT | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE ALL FIRE KEYSWITCHE'S AND KEYS | 2432 N CENTRAL AVE | PERMIT | FAILED | View |
| MAINTAIN OR REPAIR HYDRO ELEVA | REPLACE ALL FIRE KEYSWITCHE'S AND KEYS:PREVIOUSLY WRITTEN | 2432 N CENTRAL AVE | PERMIT | PASSED | View |
| CONNECT VENT LINE | TO PRV USE 5/8 TYPE K COPPER OR ACR TUBING ALL CONNECTIONS MUST BE BRAZED FOR ONE 1 HP REMOTE REFRIGERATION UNIT SERVING W.I.C. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| PRV RECEIVER | 450# PSIG FOR 0NE COPELAND 2 HP REMOTE REFRIGERATION UNIT SERVING W.I.F. | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |
| PLANS & PERMITS REQ - CONTRCTR | FOR 2 CARRIER 100 TON CHILLER | 2432 N CENTRAL AVE | PERIODIC | PASSED | View |